Fire alarm systems

Analog base 3312F / FL

???Common base for the different analog detectors

???Fast connectors

???Label holder recess

Common base

The analog base 3312F / FL is connected to a COM loop. Analog heat, smoke and multi detector types 33xx / 43xx can be plugged in the base. (See Product Leaflet for the detector type respectively, for type of base.)

Fast connectors

3312F has fast connectors (blue) for the COM loop (in/out). 3312FL also has fast connectors (grey) for an external indicator (LED), e.g. 2218.

Label holder

A label holder could be mounted in the base (in the label holder recess). The label holder is intended for a label showing "zone- address" or "technical number" information, which can be read also when the detector is plugged in the base.

Miscellaneous

The base has an address label (Al) where the detector's COM loop address is to be written.

Individual fault signal is obtained if wrong type of detector (compared with the programming) is plugged in the base or if the detector is unplugged.

When a detector with a locking screw is plugged in the base, the detector can be locked in its base to prevent theft.

The position of the detector's built-in LED is marked in the base for correct mounting position of the base.

For more information regarding detector types, connections, etc. see Planning Instructions and connection diagrams for the system respectively.

Product applications

Used for analog detectors in the systems EBL512 / 128 / 1000 / 2000.

The base is intended for indoor use and in dry premises.

Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malm??, Sweden

Tel: +46 (0)40 697 70 00 ??? Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com ??? www.panasonic-fire-security.com

Type number

3312F

3312FL

3390

3391

Ext.

Analog base with fast connectors (blue) for the COM loop.

Analog base with fast connectors (blue) for the COM loop and fast connectors (grey) for one ext. LED (e.g. 2218).

Label holder (100 holders per packet, excl. labels)

Labels for 3390 (10 sheets ?? 132 labels)

LED

Al

IN

A

S

Lss (430x)

B

S

50 mm

73 mm

E +

E -

Connectors E+ and E- not on 3312F

Lss (33xx)

OUT

SA Fast connector for COM loop (in/out) SB Fast connector for COM loop (in/out) Al Address Label

Lss Locking screw stopper (for detector type 33xx and 430x respectively)

E- Fast connector for external LED

15

6.2

E+ Fast connector for external LED

NOTE! E- and E+ on 3312FL only.

102 mm

The base is prepared for mechanical locking of the detector, when a detector with a locking screw is plugged into the base. Connector wire ??? 0.6 ??? 1.2 mm (approx. 0.28 ??? 1.13 mm2). If wire ??? 0.6 mm is used the release button may be pushed as the wire is pressed into the connector. Analog detector types 33xx and 43xx can be plugged in the base 3312F / FL.

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.