IMPORTANT NOTICE
The instructions contained in this manual are not intended to cover all of the details or variations in equipment, or to provide for every possible contingency concerning installation, operation, or maintenance. Should further information be required or if problems arise which are not covered sufficiently, contact your Toshiba sales office at
The contents of this instruction manual shall not become a part of or modify any prior or existing agreement, commitment, or relationship. The sales contract contains the entire obligation of Toshiba International Corporation (TIC) 's UPS Division. The warranty contained in the contract between the parties is the sole warranty of Toshiba International Corporation's UPS Division and any statements contained herein do not create new warranties or modify the existing warranty.
Any electrical or mechanical modifications to this equipment without prior written consent of Toshiba International Corporation will void all warranties and may void the UL/CUL listing. Unauthorized modifications can also result in personal injury, death, or destruction of the equipment.
I
UNINTERRUPTIBLE POWER SUPPLY
Complete the information below for the UPS system received.
Unless otherwise specified on the warranty card, the warranty period for the UPS or UPS part is 36 months from the shipment date (see TIC bill of lading).
Unless otherwise specified on the warranty card, the warranty period for a UPS battery is 24 months from the shipment date (see TIC bill of lading).
Please complete the following information and retain for your records.
Job Number: ________________________________________________________
Model Number: _____________________________________________________
Serial Number: ______________________________________________________
Application: ________________________________________________________
Shipment Date: _____________________________________________________
Installation Date: ____________________________________________________
Inspected By: _______________________________________________________
July, 2005
Document Number:
II
III
Manual???s Purpose and Scope
This manual provides information on how to safely install, operate, and maintain your TIC power electronics product. This manual includes a section of general safety instructions that describes the warning labels and symbols that are used throughout the manual. Read the manual completely before installing, operating, or performing maintenance on this equipment.
This manual and the accompanying drawings should be considered a permanent part of the equipment and should be readily available for reference and review. Dimensions shown in the manual are in metric and/or the English equivalent.
Toshiba International Corporation reserves the right, without prior notice, to update information, make product changes, or to discontinue any product or service identified in this publication.
TOSHIBA INTERNATIONAL CORPORATION is a registered trademark of the Toshiba International Corporation. All other product or trade references appearing in this manual are registered trademarks of their respective owners.
Toshiba International Corporation (TIC) shall not be liable for direct, indirect, special, or consequential damages resulting from the use of the information contained within this manual.
This manual is copyrighted. No part of this manual may be photocopied or reproduced in any form without the prior written consent of Toshiba International Corporation.
?? Copyright 2005 Toshiba International Corporation. All rights reserved.
Printed in the U.S.A.
IV
Contacting Toshiba International Corporation???s Customer
Support Center
Toshiba International Corporation???s Customer Support Center can be contacted to obtain help in resolving any Uninterruptible Power Supply system problems that you may experience or to provide application information.
The center is open from 8 a.m. to 5 p.m. (CST), Monday through Friday. The Support Center???s toll free number is US (800)
The email address is toshibaups@tic.toshiba.com.
You may also contact Toshiba International Corporation by writing to:
Toshiba International Corporation
13131 West Little York Road
Houston, Texas
Attn: UPS Product Manager.
For further information on Toshiba International Corporation???s products and services, please visit our website at www.tic.toshiba.com.
V
EMC Statements
FCC Part 15
NOTICE: Pursuant to section 15 of the FCC rules this product has been tested and complies with the conditions of a Class B digital device. The product has been established as offering sufficient protection against dangerous interference for installations in a residential area. Installation and use of the equipment should comply with the instructions provided in order to avoid interference due to the amount of radio frequency energy that is radiated and generated by the equipment.
TIC cannot assure that no interference will occur. Turn the unit on and off to help determine if the radio or television reception is found to be influenced by harmful interference from the equipment. If required, use one of the following measures to minimize the negative effects of interference:
???Place the receiving antenna in a separate location or orientation.
???Increase the distance between the receiver and the equipment.
???Ensure that your equipment and the receiver are on separate circuits.
???Contact a technician experienced with radio and TV or a dealer for further assistance.
This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations
VI
Declaration of Conformity Request
Units labeled with a CE mark comply with the following standards and directives: Harmonic Standards: EN
EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits.
93/68/EEC, Amending Directive 73/23/EEC.
89/336/EEC, Council Directive relating to electromagnetic compatibility. 92/31/EEC, Amending Directive 89/336/EEC relating to EMC.
The EC Declaration of Conformity is available upon request for products with a CE mark.
VII
General Safety Instructions
DO NOT attempt to install, operate, maintain or dispose of this equipment until you have read and understood all of the product safety information and directions that are contained in this instruction manual.
Safety Alert Symbol / Signal Words
The Safety Alert Symbol indicates that a potential personal injury hazard exists. The symbol is comprised of an equilateral triangle enclosing an exclamation mark.
Signal Words
Listed below are the signal words that are used throughout this manual followed by their descriptions and associated symbols. When the words DANGER, WARNING, and CAUTION are used in this manual they will be followed by important safety information that must be carefully adhered to.
1.Danger ??? The word DANGER in capital letters preceded by the safety alert symbol indicates that an imminently hazardous situation exists that, if not avoided, will result in death or serious injury to personnel.
DANGER
VIII
2.Warning ??? The word WARNING in capital letters preceded by the safety alert symbol indicates that a potentially hazardous situation exists that, if not avoided, could result in death or serious injury to personnel.
WARNING
3.Caution/Attention ??? The word CAUTION or ATTENTION in capital letters preceded by the safety alert symbol indicates that a potentially hazardous situation exists that, if not avoided, may result in minor or moderate injury.
CAUTION / ATTENTION
4.The word CAUTION without the safety alert symbol indicates a potentially hazardous situation exists which, if not avoided, may result in equipment and property damage.
CAUTION
IX
Special Symbols
Other warning symbols may appear in conjunction with the Danger, Warning, and Caution symbol and are used to specify special hazards. These warnings describe particular areas where special care and/or procedures are required in order to prevent serious injury and possible death.
1.ELECTRICAL HAZARD SYMBOL ??? Indicates a hazard that may cause injury from an electrical shock or burn. The symbol is comprised of an equilateral triangle enclosing a lightning bolt.
2.EXPLOSION HARZARD SYMBOL ??? Indicates a hazard that may cause injury from exploding parts. It is comprised of an equilateral triangle enclosing an explosion image.
X
Important Safety Instructions
This manual contains important instructions that should be followed during the installation, maintenance, and operation of the UPS and its batteries to assure safe and proper operation.
1.Turn off, lockout, and tagout all power sources before connecting the power wiring to the equipment or when performing maintenance.
2.Hardwire type UPS units are not equipped with an
3.The maximum ambient operating temperature is 104?? F (40?? C).
4.Battery servicing should be performed by a qualified Toshiba Representative only.
5.Unauthorized personnel should not service batteries.
6.Contact your nearest Toshiba authorized service center for battery replacement.
Qualified Personnel ONLY!
Qualified Personnel is one that has the skills and knowledge relating to the construction, installation, operation, and maintenance of the electrical equipment and has received safety training on the hazards involved (Refer to the latest edition of NFPA 70E for additional safety requirements).
Qualified Personnel shall:
1.Have read the entire operation manual.
2.Be trained and authorized to safely energize,
3.Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety practices.
4.Be trained in rendering first aid.
XI
5.Be knowledgeable of batteries and the required handling and maintenance precautions.
For further information on workplace safety visit www.osha.gov.
XII
Important Safety Instructions (cont'd)
WARNING
Misuse of this equipment could result in injury and equipment damage. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the misuse of this equipment.
CAUTION
Do not dispose of the batteries in a fire. The batteries may explode.
CAUTION
Do not open or mutilate the batteries. Released electrolyte is harmful to the eyes and skin and could also be toxic.
DANGER
A battery can present a risk of electrical shock and high short circuit current.
XIII
To be performed by Qualified Personnel only.
1.Verify that the UPS is off and that the power cord is disconnected from the power source.
2.Remove watches, rings or other metal objects.
3.Use tools with insulated handles to prevent inadvertent shorts.
4.Wear rubber gloves and boots.
5.Do not place tools or any metal parts on top of batteries.
6.Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source of ground.
Contact with any part of a grounded battery can result in electrical shock.
The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance.
XIV
Instructions Importantes Concernant
LA S??CURIT??
CONSERVER CES INSTRUCTIONS
Cette notice contient des instructions importantes concernant la s??curit??.
ATTENTION
Une battery peut pr??senter un risque de choc ??lectrique, de br??lure par transfert d' ??nergie.
ATTENTION
L' ??limination des batteries est r??glement??e. Consulter les codes locaux ?? cet effet.
XV
Inspection/Storage/Disposal
CAUTION
Inspection
Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the pallet. Refer to labels or documentation attached to packing material.
Uncrating
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping, keep all original crating and packing materials for return to the shipping agent. The warranty does not apply to damage incurred during shipping. Ensure that the rated capacity and the model number specified on the nameplate conform to the order specifications.
Storage
During periods of
Storage Preparation
1.Power up the UPS and allow it to operate with no load for 24 hours to fully charge the batteries.
2.Stop the unit.
3.Place the MCCB switch in the Off position.
Storing Conditions
???For best results, store the UPS in the original shipping container and place on a wood or metal pallet.
???Storage temperature ???
???The optimum storage temperature is 21?? C (70?? F). A higher ambient temperature will require recharging more frequently during storage.
Avoid the following storage locations:
XVI
???Locations that are subject to extreme temperature changes or high humidity.
???Locations that are subject to high levels of dust or metal particles.
???Locations that are subject to excessive vibration.
???Inclined floor surfaces.
Storage Maintenance
???If stored at an ambient temperature less than 20?? C (68?? F), recharge the batteries every 9 months.
???If stored at an ambient temperature of 20?? ??? 30?? C (68?? ??? 86?? F), recharge the batteries every 6 months.
???If stored at an ambient temperature of 30?? ??? 40?? C (86?? ??? 104?? F), recharge the batteries every 3 months.
Disposal
Please contact your local or state environmental agency for details on disposal of electrical components and packaging in your particular area.
It is illegal to dump
Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba
XVII
Installation Precautions
CAUTION
1.Install the unit in a
2.Install the unit in a stable, level and upright position that is free of excessive vibration.
3.Install the unit where the ambient temperature is within the range specified.
4.Do not install the UPS in areas that are subject to high humidity.
5.Do not install the UPS in areas that allow exposure to direct sunlight.
6.Do not install the UPS in areas that allow exposure to high levels of airborne dust, metal particles, or flammable gases.
7.Do not install the UPS in areas near sources of electrical noise. Ensuring a proper earth ground will reduce the effects of electrical noise and will reduce the potential for electrical shock.
8.Do not install the UPS in areas that would allow fluids or any foreign object to get inside the UPS.
9.The UPS generates and can radiate
10.The user should provide output
11.After ensuring that all power sources are turned off and isolated in accordance with established lockout/tagout procedures, connect the power source wiring of the correct voltage to the input terminals of the UPS.
XVIII
12.Connect the output terminals of the UPS to the load (refer to NEC Article 300 ??? Wiring Methods and Article 310 ??? Conductors For General Wiring). Size the branch circuit conductors in accordance with NEC Table 310.16.
Conductor Routing and Grounding
1.Use separate metal conduits for routing the input power, output power, and control circuits.
2.Follow the wire size and tightening torque specifications.
3.Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise.
4.A separate ground cable should be run inside the conduit with the input power, output power, and control circuits.
CAUTION
THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.
XIX
Operating Precautions
CAUTION
1.The UPS should not be powered up until the entire operation manual has been read.
2.The voltage of the input power source must be within the range of +10% to
3.The UPS should not be used with a load that has a rated input that is greater than the rated output of the UPS.
4.Do not use the UPS to provide power to motors that require high starting current or with motors that require a long starting time, such as vacuum cleaners and machine tools (over sizing the UPS for lock rotor current would be required).
5.Do not insert metal objects or combustible materials in the ventilation slots of the UPS.
6.Do not place, hang, or paste any objects on the exterior surfaces of the UPS.
7.The capacitors of the UPS maintain a residual charge for a while after turning the UPS off. The required discharge time for each UPS typeform is provided via a cabinet label and a CHARGE LED. Wait for at least the minimum time indicated on the label and ensure that the CHARGE LED has gone out before opening the door of the UPS once the UPS power has been turned off.
8.Do not attempt to disassemble, modify, or repair the UPS. Call your Toshiba sales representative for repair information.
9.Turn the power on only after attaching ALL of the covers.
10.Do Not remove any covers of the UPS when the power is on.
11.If the UPS should emit smoke or an unusual odor or sound, turn the power off immediately.
12.The heat sink and other components may become extremely hot to the touch.
XX
Allow the unit to cool before coming in contact with these items.
13.Warning signs should be placed on or near the load as a notification that the load is being powered by the UPS.
14.Additional warnings and notifications shall be posted at the equipment installation location as deemed required by Qualified Personnel.
WARNING
While operating in the inverter mode, placing the breaker in the OFF position will switch the UPS to the battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be in the bypass mode at the time that the breaker is placed in the OFF position for the UPS to shutdown power to the load.
CAUTION
After an Emergency Power Off (EPO), do not reset the breaker until the UPS has been fully discharged. The UPS could be damaged if the unit is not fully discharged before the breaker is reset.
XXI
1. Introduction
The information provided in this manual covers single phase 1000 ??? 1200 VA uninterruptible power systems. Included in this manual is information on the installation, operation, safety precautions, shipping, and storage of the equipment.
Installation must be carried out in accordance with this manual. Electrical installations must also follow local legislation and regulations. Only qualified personnel should install this equipment. Failure to comply with the warnings and precautions could prove to be fatal.
2. System Description
The purpose of the UPS is to protect sensitive systems from poor quality utility power, complete loss of power, or other associated problems. System types include computers, workstations, process control systems, telecommunications systems, sales terminals, or other critical instrumentation.
Electrical interference may occur causing problems in AC power. Interference may come from lightning, the power company, radio transmissions, or motors. Normal operation of sensitive electrical equipment requires protection against power outages, low or high voltage levels, frequency variations, differential and
In order to prevent power line problems from reaching critical systems and causing damage to software, hardware or causing equipment to malfunction, the UPS helps by maintaining a constant voltage, isolating critical load output, and cleaning the utility AC power.
1
2.1 General Description
As a double conversion
Other features of the UPS includes
???
???Programmable Load Shed Receptacle
???Intelligent Charger with Rapid Charge in only 3.5 hours to 90%
???Wide Input Voltage Window
???Wide Input Frequency Window for Complete Generator Compatibility
???Input Power Factor greater than 0.97
???Output Power Factor 0.70
???Multiple Languages LCD Display
???Free Run Mode - See detail explanation on page 4
???Diagnostic Tests - See detail explanation on page 4
???Optional Network Interface Card
???Optional Environmental Monitoring Device
In the event that a power failure lasts longer than the UPS backup time, the UPS will shut down. Upon power restoration, the UPS will restart automatically, which includes output power being restored to the load and the start of battery recharge.
See following figure for systemic applicable of the UPS system.
Figure 1. Block diagram
2
???An input filter reduces transients on the main supply.
???For maintaining full battery charge,
???DC power is converted to AC in the inverter and passes it on to the load.
???Power to the load is maintained from the battery during a power failure.
???The converter increases voltage for the inverter as required.
3
Free Run Mode
Free run mode is a mode of operation in which the output frequency does not match input frequency. The UPS operates in free run mode when the input frequency is outside of the selected input frequency range. When starting the UPS, the targeted frequency is 50 or 60 Hz ??0.25Hz Refer to section 4.3 Front Panel Settings to set up bypass availability while running in free run mode.
Diagnostic Tests
When the UPS is started, a diagnostic test is executed automatically that checks the electronics and battery, and reports any problems on the LCD display.
The advanced battery management system monitors the performance of the battery and will indicate if battery replacement is required. The battery management system tests the battery every 30 days of normal mode operation. A battery discharge test is performed and reports any problems on the LCD display.
Except during the first 24 hours after startup while the UPS is in charging mode, diagnostic tests can be performed manually from the front panel when required.
4
2.2 System Configuration
The UPS device and the internal backup battery make up the system. Depending on the site and load requirements of the installation, available options may be utilized to create a tailored solution.
Planning a UPS system should include the following considerations:
???The total demand of the protected system shall dictate the output power rating (VA). Allow a margin for future expansion or calculation inaccuracies from measuring power requirements.
???Backup time needed will determine the battery size needed. If the load is less than the UPS nominal power rating then the actual backup time will be longer.
???The following options are available:
???External Battery Cabinets, and
???Connectivity options (Remote Contact, SNMP/WEB card).
The following UPS models are available.
Additional External Battery Cabinets are available if more
5
3. Storage
Please adhere to the following instructions if the UPS is not installed when received:
???Store the equipment in its original packing and shipping carton.
???Store the unit in a temperature of 15?? C to 25?? C.
???Ensure that the equipment is fully protected from wet or damp areas and from
moist air.
In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6 months for at least 8 hours during storage.
6
3. Installation
3.2 Environment
To ensure safe and proper operation, ensure that the installation conforms to the following specifications.
Ensure that the installation location is consistent with the following:
???Avoid extreme temperature and humidity. Maximal battery life can be attained with a recommended temperature range of 15?? C to 25?? C.
???Protect the equipment from moisture.
???Space and ventilation requirements must be met. Ensure there is at least 100mm (4 inch) behind and 50mm (2 inch) on the sides of the UPS for ventilation.
???Ensure that the front of the UPS remain supply clear for user access.
The External Battery Cabinets must be installed next to or underneath the UPS.
7
Vertical and
Install the vertical and
8
Install the
Installation with bottom bracket.
Screw: M5*11, 4 PCS.
9
Stacked UPS Installation with accessories
Install the stacked unit as shown below.
Stack installation
10
Rear Panel Views
1000VA ??? 1200VA Tower Rear Panel
11
1000VA Rack mount (1U) Rear Panel
12
1000VA Rack mount (2U) Rear Panel
13
3.3 Connection to main supply and loads (1000 ??? 1200 VA)
???Ensure that the UPS is disconnected from the main supply and loads while connecting the External Battery Cabinets.
???Use the battery cable supplied with the External Battery Cabinet to connect the External Battery Cabinet to the UPS. If more than one battery cabinet is required, use the supplied cable.
???A familiarity with the UPS parameter settings is required if changing the Battery pack quantity as when using the External Battery Cabinets section 4.3 Front Panel Settings.
???Connect the input cable to the UPS and connect the other end to a grounded outlet. The batteries will charge automatically when connected to the main supply.
The UPS may be used immediately to power a load. However, the maximum battery
???If a Site Wiring Fault is displayed, rotate the connector (Schuko ??? electric
contact) (see section 5.6 Troubleshooting).
After charging the UPS connect the load to the UPS (see the example in Figure 2 Example of Installation of Plug & Play products.
???Do not connect any devices to the UPS that may cause overloading of the UPS or that draws
???See section 4 Computer and Alarm Connections if computer or alarm (rear panel) connections are used.
???The installation is now complete.
14
Figure 2 Example of Installation of Plug & Play products.
15
4.3 Front Panel Settings
Listed below are the default settings of the primary UPS parameters.
16
Complete the installation entirely before changing the default settings or connecting a load to the UPS.
17
4. Computer and Alarm Connections
At the rear of the UPS is an interface that allows direct communication with a computer system (see figure 2). There is a RS232 serial data interface, a USB data interface, and an emergency power off switch. The RS232 port and the USB interface cannot be used simultaneously.
In addition there is an optional interface slot that allows for the installation of communications cards. It may be used in parallel with either the RS232 or USB ports.
An SNMP/WEB card is available for the optional interface slot that allows for the RemotEye II to manage and monitor the system over a network or over the internet.
Only the communication cable provided with the UPS may be used to connect the UPS to a computer when using the RS232 port of the UPS. Ensure that the operating system of the computer supports RS232 communications.
Other advanced power protection solutions, such as SNMP, are available from your dealer.
The
Table 1 : RS232 Pin Out Signal
18
USB Port
Connecting the UPS to a computer using the USB port of the computer requires USB compliant hardware, PC operating system support, and a UPS driver. The RS232 serial port cannot be used when using the USB port. The USB cable is a standard cable and may be purchased separately.
EPO Port (emergency power off)
A
After an Emergency Power Off (EPO), do not reset the breaker until the UPS has been fully discharged. The UPS could be damaged if the unit is not fully discharged before the breaker is reset.
Network Transient Protector
The network transient protector, located on the back panel, has both IN and OUT RJ45 10 baseT jacks and will protect a single network connector. Connect the input connector to the jack labeled IN, and the output connector to the jack labeled OUT.
Load Segments
The sets of receptacles known as load segments, which provide organized shutdown and startup of the equipment. Less critical equipment can be turned off during power outages saving battery power for critical loads. The load group status can be viewed from the LCD display and can be changed if necessary.
19
5. User???s Guide to Operations
Normal ongoing UPS operation requires little or no user input. Startup and shutdown requirements of the user are discussed in this section.
5.2 UPS Startup and Shutdown
Starting the UPS
???Ensure that installation is correct and that the input power cable is connected to a properly grounded outlet.
???Start the UPS by pressing the On/Off button on the front panel.
???The UPS will start the inspection of internal functions, main synchronization, and inverter startup. A successful completion allows for output power via the outlets.
???During the startup inspection the LCD will display Ready On. The LED will light up when output power has started and the LCD display will show Line Mode.
???Switch on the load.
Shutting Down the UPS
???Shut off and disconnect the load.
???Press and hold the UPS On/Off button for five seconds. The alarm will sound and the UPS will shut down.
???The LCD will momentarily display UPS OFF.
Note: In emergency situations the EPO should be used.
5.3 Button Operation
1.??? ??? is the Load ON/OFF button.
(a)Press and hold the Load ON/OFF button for at least 3 seconds to turn on the UPS.
(b)While the UPS is operating, press and hold the Load ON/OFF button for at least 3 seconds to turn off the UPS.
20
2.??? ??? is the Enter button.
(a)Press and hold the Enter button for at least 2 seconds to read the parameter settings of the UPS. Press the Enter button again to read the next parameter.
(b)Ten seconds of inactivity will return the display to the original status.
3.??? ??? is the Function button.
(a)Press and hold the Function button for at least 2 seconds to access the selectable parameters. Press the Function button again to view the next parameter.
(b)Press the Enter button to view or change the displayed parameter.
(c)Ten seconds of inactivity will return the display to the original status.
5.4 Control Panel functions
The front panel is composed of five LED indicators, an LCD screen, and a speaker for audible alarms.
ON/ ??? is on when the UPS is turned on (green).
21
Status of the UPS, measurements, and alarms are all indicated on the LCD screen.
Figure 3 Control panel
Normal Display
The UPS status is shown in the normal display mode. The UPS Meters display and the Setting display may be accessed by pressing this button.
UPS Meters Display
Listed below are the parameters available for viewing from the UPS meters display. Press this button to scroll through the parameters.
22
UPS Configurations
1)Parameter settings may be viewed from the UPS Settings display.
2)To enter the configuration mode, press and hold the Function button for one second. The first configuration parameter will be shown on the LCD display.
3)Press the Function button again to scroll through the remaining parameters.
4)Press the Enter button to select a displayed parameter.
5)Press the Function button to scroll through the options for the selected parameter. Press the Enter button to select the setting.
6)If prompted to save the selection, press the Enter button to either confirm or save the selection. See the table on page 16 for a complete listing of the
7)If there is no user input for ten seconds, the UPS will exit the configuration mode and return to normal mode displaying Line mode.
23
UPS Manual Test
Manual UPS and Battery tests may be performed from the UPS configuration screen. Tests may be performed when the battery is not being charged.
To run the battery test scroll to the ???Manual Bat Test??? parameter press the Enter button twice.
**Note: In order for the UPS to operate normally, Manual Bypass should always be set to OFF because the load will not be protected by the unit when Manual Bypass is ON.
***Note: Turn off the UPS and keep the AC power on to use the Generator function. (go to normal mode for \Generator\OFF).
5.5 Interpreting UPS Messages
Troubleshooting procedures described here provide instructions to be used to isolate UPS malfunctions.
Start the troubleshooting procedure in the event of a control panel alarm.
Audible Alarms
???While operating on battery power (ON BAT LED is on) the UPS will beep once at
???While operating on battery power and the battery power is low (ON BAT LED is flashing) the UPS will beep twice at
???In the event of an internal fault with an active alarm (ALARM LED is on), the UPS will provide a constant audible alarm and display an error message on the LCD display.
???While operating in the Bypass mode (BYPASS LED is on) the UPS will not beep.
Silencing an Alarm
With the exception of a LOW BATTERY Alarm, pressing any of the front panel buttons will turn off the alarm. Select Silent Alarm Mode to disable all audible alarms.
24
5.6 Troubleshooting
25
6. Maintenance
With a minimal amount of maintenance you can expect years of satisfactory operation from the UPS unit. The most critical issues for the reliability of the UPS are environmental issues. Ensure that the temperature and humidity are always in accordance with the specifications and keep the area around the unit clean and dust free.
The typical battery lifetime is 4 years when operated at 25?? C.
Check the
26
7. Technical Specifications
7.2 Power Range
27
7.3 Power Range:1000 VA (19???
28
7.4 Power Range
29
7.5 Power Range 1000 VA (19???
30
Tower HV Model
31
Tower LV Model
32
8. Warranty Information
TOSHIBA INTERNATIONAL CORPORATION LIMITED WARRANTY POLICY
(48 contiguous U.S. States, Canada, Mexico)
(UNINTERRUPTIBLE POWER
TOSHIBA INTERNATIONAL CORPORATION (???TIC???) warrants that the 1000 Series Uninterruptible Power Supplies (???UPS???) and Uninterruptible Power Supply Battery (???BATTERY???) sold by TIC to the
Note 1: The warranty period begins from the shipment date. The shipment date is determined by the date on the TIC Bill of Lading.
Note 2: For the 1000 Series the warranty applies if the unit is sent and returned (paid for) by the user to/from the Toshiba International Corporation or a Toshiba International Corporation designated Authorized Service Center.
If any UPS, part of UPS, and/or BATTERY fails to conform or is defective then TIC, at this option, will repair or replace defective component(s).
33
LIMITATIONS AND EXCLUSIONS
This limited warranty shall not cover the UPS, UPS part, or BATTERY during their respective warranty periods, if the following storage, maintenance, installation, operating conditions are not met throughout the warranty periods (5 conditions below):
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA
INTERNATIONAL CORPORATION UPSREQUIRED OPERATING
CONDITIONS
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOT TOSHIBA
INTERNATIONAL CORPORATION UPS
INSTALLATION AND MAINTENANCE CONDITIONS
34
1.The Warranty does not cover damage or defects caused by misuse, improper application, wrong or inadequate electrical current/voltage/frequency, inadequate connections, inadequate water or drain services, user negligence, repair by non- Toshiba International Corporation designated personnel, accident during shipment, tampering, alterations, a change in UPS and/or BATTERY location or application, exposure to the elements, acts of God, theft, sabotage, installation contrary to TIC's recommendations or specifications (Published Operation Manuals), or if the serial numbers have been altered, defaced, or removed.
2.Repair or replacement of a defective UPS, UPS part, and/or BATTERY does not extend the respective original warranty period. All defective UPS, UPS parts, and/or BATTERIES shall be the property of TIC upon replacement.
3.The sales contract contains the entire obligation of Toshiba International Corporation and constitutes the sole and exclusive remedy of all purchasers and users of the UPS, UPS part, and/or BATTERY. TIC???s responsibility for UPS, UPS Parts, and/or BATTERY shall not exceed one times the net UPS and/or BATTERY purchase price.
35
Procedure for Defective Product Screening and Disposition
User must contact TIC via
the respective warranty period will warranty work be performed.
In the event of a defective BATTERY claim
Credit for Replacement Battery When Approved Warranty
36
MODIFICATIONS
No representative, salesperson, agent, distributor, or employee of TIC is authorized to modify any of the terms of the warranty, unless modifications are made in writing and signed by an authorized TIC officer.
37