MICROMASTER
Operating Instructions
Safety Instructions
Before installing and putting this equipment into operation, please read these safety instructions and warnings carefully and all the warning labels attached to the equipment. Make sure that the warning labels are kept in a legible condition and replace missing or damaged labels.
WARNING
This equipment contains dangerous voltages and controls dangerous rotating mechanical parts. Loss of life, severe personal injury or property damage can result if the instructions contained in this manual are not followed.
Only suitable qualified personnel should work on this equipment, and only after becoming familiar with all safety notices, installation, operation and maintenance procedures contained in this manual. The successful and safe operation of this equipment is dependent upon its proper handling, installation, operation and maintenance.
???MICROMASTERS operate at high voltages.
???Only
???If a Residual
???Machines with a three phase power supply, fitted with EMC filters, must not be connected to a supply via an ELCB (Earth Leakage
???The following terminals can carry dangerous voltages even if the inverter is inoperative:
-the power supply terminals L/L1, N/L2, L3.
-the motor terminals U, V, W.
???Only qualified personnel may connect, start the system up and repair faults. These personnel must be thoroughly acquainted with all the warnings and operating procedures contained in this manual.
???Certain parameter settings may cause the inverter to restart automatically after an input power failure.
???This equipment must not be used as an ???emergency stop??? mechanism(see EN 60204, 9.2.5.4)
???If motor thermal protection is required, then an external PTC must be used. (Refer to Section 2.3.5.)
???Lowering the fan tray on Frame Size C MICROMASTER exposes rotating parts. Power must be isolated prior to this operation.
CAUTION
???Children and the general public must be prevented from accessing or approaching the equipment!
???This equipment may only be used for the purpose specified by the manufacturer. Unauthorised modifications and the use of spare parts and accessories that are not sold or recommended by the manufacturer of the equipment can cause fires, electric shocks and injuries.
???Keep these operating instructions within easy reach and give them to all users!
European Low Voltage Directive
The MICROMASTER product range complies with the requirements of the Low Voltage Directive 73/23/EEC as amended by Directive 98/68/EEC. The units are certified for compliance with the following standards:
EN
EN
European Machinery Directive
The MICROMASTER inverter series does not fall under the scope of the Machinery Directive. However, the products have been fully evaluated for compliance with the essential Health & Safety requirements of the directive when used in a typical machine application. A Declaration of Incorporation is available on request.
European EMC Directive
When installed according to the recommendations described in this manual, the MICROMASTER fulfills all requirements of the EMC Directive as defined by the EMC Product Standard for Power Drive Systems
UL and CUL listed.
ISO 9001
Siemens plc operates a quality management system which complies with the requirements of ISO 9001.
26/09/97
1. OVERVIEW
The MICROMASTERS are a range of frequency inverters for controlling the speed of three phase AC motors. Various models are available, ranging from the compact 120 W single phase input MICROMASTER up to the 7.5 kW three phase input MICROMASTER.
The inverters are
Features:
state of the art IGBT technology for reliability and with selectable ultrasonic pulse frequency permits protection is provided by comprehensive protective
???Easy to install, program and commission.
???Closed loop control using a Proportional, Integral (PI) control loop function.
???High starting torque with automatic starting boost.
???Remote control capability via RS485 serial link using the USS protocol with the ability to control up to 31 inverters.
???A comprehensive range of parameters is provided to enable the inverters to be configured for use in almost any application.
???
???
???Factory default parameter settings
???Output frequency (and hence motor speed) can be controlled by one of five methods:
(1)Frequency setpoint using the keypad.
(2)High resolution analogue setpoint (voltage input).
(3)External potentiometer to control motor speed.
(4)Fixed frequencies via binary inputs.
(5)Serial interface.
???
???Integral RFI filter on single phase input inverters (MM12 - MM300).
???Acceleration/deceleration times with programmable smoothing.
???Fully programmable single relay output incorporated.
???External Options connector for optional
???Automatic recognition of 2, 4, 6 or
???Integral
???Fast Current Limit (FCL) for reliable
???Compact design and the ability to mount inverters side by side provides greater space saving.
?? Siemens plc 1997G85139-H1750-U049-B
2. INSTALLATION
2.1 Wiring Guidelines to Minimise the Effects of EMI
The inverters are designed to operate in an industrial environment where a high level of
(1)Ensure that all equipment in the cubicle is well earthed using short, thick earthing cable connected to a common star point or busbar. It is particularly important that any control equipment that is connected to the inverter (such as a PLC) is connected to the same earth or star point as the inverter via a short, thick link. Flat conductors (e.g. braids or metal brackets) are preferred as they have lower impedance at high frequencies.
The return earth from motors controlled by the inverters should be connected directly to the earth connection (PE) on the associated inverter.
(2)Wherever possible, use screened leads for connections to the control circuitry. Terminate the ends of the cable neatly, ensuring that unscreened wires are as short as possible. Use cable glands whenever possible.
(3)Separate the control cables from the power connections as much as possible, using separate trunking, etc. If control and power cables cross, arrange the cables so that they cross at 90?? if possible.
(4)Ensure that contactors in the cubicle are suppressed, either with
(5)Use screened or armoured cables for the motor connections and ground the screen at both ends via the cable glands.
(6)If the drive is to be operated in an
On no account must safety regulations be compromised when installing inverters!
MAINS POWER
CABLE
Connect to Mains and
PE terminals on Inverter
CONTROL
CABLE
EARTH STUD
FILTER UNIT
Note: There must be a good conductive bond between filter and metal panel.
EARTH STUD (under)
SCREENED
CABLE
When cable glands cannot be used, terminate screen to metal panel by removing cable sheath.
Figure 1: Example of an RFI Suppression Filter Installation
?? Siemens plc 1997G85139-H1750-U049-B
2.2 Mechanical Installation
WARNING
THIS EQUIPMENT MUST BE EARTHED.
To guarantee the safe operation of the equipment it must be installed and commissioned properly by qualified personnel in compliance with the warnings laid down in these operating instructions.
Take particular note of the general and regional installation and safety regulations regarding work on dangerous voltage installations (e.g. VDE), as well as the relevant regulations regarding the correct use of tools and personal protective gear.
The mains input and motor terminals can carry dangerous voltages even if the inverter is inoperative. Use insulated screwdrivers only on these terminal blocks.
Environmental Requirements
Hazard
Temperature
Altitude
Shock
Vibration
Radiation
Atmospheric
Pollution
Water
Overheating
Notes
Min. = 0??C
Max. = 50??C
If the Inverter is to be installed at an altitude > 1000 m, derating will be required.(Refer to DA 64 Catalogue).
Do not drop the inverter or expose to sudden shock.
Do not install the inverter in an area where it is likely to be exposed to constant vibration.
Do not install the inverter near sources of
Do not install the inverter in an environment which contains atmospheric pollutants such as dust, corrosive gases, etc.
Take care to site the inverter away from potential water hazards. e.g. Do not install the inverter beneath pipes that are subject to condensation.
Ensure that the inverter???s air vents are not obstructed.
Make sure that there is an adequate
1.Using the formula below, calculate the airflow required.
Note:
Typical dissipation (Watts) = 3% of inverter rating.
T = Allowable temperature rise within cabinet in ??C.
3.1 = Specific heat of air at sea level.
Ideal Installation
F
???
???
??? = 4.5 mm
Tightening Torque (with washers fitted)
2.5Nm Frame size A and B
3.0Nm Frame size C
??? = 4.8 mm (B) ??? = 5.6 mm (C)
Frame Sizes
(all measurements in mm)
Figure 2: Mechanical Installation Diagram
?? Siemens plc 1997G85139-H1750-U049-B
2.3 Electrical Installation
The electrical connectors on the MICROMASTER are shown in Figure 3. Connect the cables to the power and control terminal blocks in accordance with the information supplied in sections 2.3.1 - 2.3.4. Ensure that the leads are connected correctly and the equipment is properly earthed as shown in Figure 3.
CAUTION
The control, power supply and motor leads must be laid separately. They must not be fed through the same cable conduit/trunking.
Use screened cable for the control lead. Use Class 1 60/75oC copper wire only (for UL compliance). Tightening torque for the power (mains input and motor) terminals is 1.1 Nm.
To tighten up the power/motor terminal screws use a 4 - 5 mm
2.3.1 Power and Motor Connections - Frame Size A
Ensure that the power source supplies the correct voltage and is designed for the necessary current (see section 7). Ensure that the appropriate
Connect the power and motor connections as shown in Figure 3.
WARNING
Isolate the supply before making or changing connections.
Ensure that the motor is configured for the correct supply voltage. Single/three phase 230 V
MICROMASTERS must not be connected to a 400 V three phase supply.
When synchronous machines are connected or when coupling several motors in parallel, the inverter must be operated with voltage/frequency control characteristic (P077= 0 or 2).
Control
Terminals
PE L/L1 N/L2 L3
PE
L3
L2
L1
N
Mains Input
Terminals
U V W
Motor Terminals
SINGLE PHASE
THREE PHASE
2.3.2 Power and Motor Connections - Frame Size B
The terminal arrangement for frame size B is identical to frame size A (see Figure 3). However, before the wires can be connected to the terminal blocks, you must lower the terminal access panel and secure the cables to the gland plate.
Refer to Figures 3 and 4. Proceed as follows:
1.Insert the blade of a small screwdriver into slot A on the side of the inverter and press in the direction of the arrow. At the same time, apply finger pressure to clip B on the other side of the access panel and press in the direction of the arrow.
This will release the access panel, which will then swing down on its
2.Remove the gland plate by applying pressure to release clips C and D in the direction of the arrows.
3.Secure each cable to the correct hole in the gland plate, ensuring that the exposed wires are long enough to reach the terminal blocks.
4.Before refitting the gland plate, feed the control wires (if used) through hole 1 and the mains input and motor wires through hole 2. IT IS MOST IMPORTANT THAT THE MOTOR AND CONTROL WIRES ARE
KEPT APART.
5.Refit the gland plate. Ensure that the release clips snap into position.
6.Connect the wires to the terminal blocks as shown in Figure 3. (See section 2.3.4 for information about connecting the control wires.)
7.Close the terminal access panel.
A
B
E
CF
D
A & B: Terminal cover release tabs
C & D: Gland plate release tabs
G
E:Control cable input (16.2 mm diameter; accepts cables up to 10 mm diameter)
F:Mains cable input (22.8 mm diameter; accepts cables up to 14.5 mm diameter)
G:Motor cable input (22.8 mm diameter; accepts cables up to 14.5 mm diameter)
Figure 4: Power Connections Access Diagram - Frame Size B
2.3.3 Power and Motor Connections - Frame Size C
The terminal arrangement for frame size C is identical to frame size A (see Figure 3). However, before the wires can be connected to the terminal blocks, you must lower the fan housing and secure the cables to the gland plate.
Refer to Figure 5 and proceed as follows:
1.While supporting the fan housing with one hand, insert the blade of a screwdriver into slot A on the underside of the inverter and press upwards to release the securing tab. Lower the fan housing, allowing it to swing out to the right on its
2.Applying pressure to the gland plate release clips B and C in the direction of the arrows. Swing the plate out to the left on its
3.Secure each cable to the correct hole in the gland plate, ensuring that the exposed wires are long enough to reach the terminal blocks.
4.Connect the wires to the terminal blocks as shown in Figure 3. (See section 2.3.4 for information about connecting the control wires.) IT IS MOST IMPORTANT THAT THE MOTOR AND CONTROL WIRES
ARE KEPT APART.
5.Swing the gland plate back into the base of the inverter. Ensure that the release clips snap into position.
6.Swing the fan housing back into the base of the inverter.
D
E B
F A
C
A: Fan housing release tab
B & C: Gland plate release tabs
D:Control cable input (16.2 mm diameter; accepts cables up to 10 mm diameter)
E:Mains cable input (22.8 mm diameter; accepts cables up to 14.5 mm diameter)
F:Motor cable input (22.8 mm diameter; accepts cables up to 14.5 mm diameter)
Figure 5: Power Connections Access Diagram - Frame Size C
?? Siemens plc 1997G85139-H1750-U049-B
2.3.4 Control Connections
Transducer or other load
(+15 V, max. 50 mA)
Control Terminal Block
Figure 6: Control Connections
2.3.5 Motor Overload Protection
When operated below rated speed, the cooling effect of fans fitted to the motor shaft is reduced. Consequentially, most motors require
Note: To enable the trip function, set parameter P051, P052 or P053 =19.
8
MOTOR
PTC
7
1k??
Inverter Control
Terminals
9
Figure 7: Motor Overload PTC Connection
PE U, V, W
3. FRONT PANEL CONTROLS & BASIC OPERATION
3.1 Front Panel Controls
CAUTION
The digital frequency setpoint has been set at 5.00 Hz in the factory. This means that, it is not necessary to enter a frequency setpoint via the button or parameter P005 in order to test that the motor turns following a RUN command.
All settings must only be entered by qualified personnel, paying particular attention to the safety precautions and warnings.
The parameter settings required can be entered using the three parameterisation buttons (P, and ???) on the front panel of the inverter. The parameter numbers and values are indicated on the four digit LED display.
Jog
LED Display
P
Pressing this button while the inverter is stopped causes it to start and run at the preset jog frequency. The inverter stops as soon as the button is released. Pressing this button while the inverter is running has no effect. Disabled if P123 = 0.
Press to start the inverter. Disabled if P121 = 0.
Press to stop the inverter.
Displays frequency (default), parameter numbers or parameter values (when P is pressed) or fault codes.
Press to change the direction of rotation of the motor. REVERSE is indicated by a minus sign (values < 100) or a flashing decimal point (values > 100). Disabled if P122 = 0
Press to INCREASE frequency. Used to change parameter numbers or values to higher settings during the parameterisation procedure. Disabled if P124 = 0.
Press to DECREASE frequency. Used to change parameter numbers or values to lower settings during the parameterisation procedure. Disabled if P124 = 0.
Press to access parameters. Disabled if P051 - P053 = 14 when using digital inputs.
Figure 9: Front Panel
3.2 Basic Operation
Refer to section 5 for a full description of each parameter.
3.2.1 General
(1)The inverter does not have a main power switch and is live when the mains supply is connected. It waits, with the output disabled, until the RUN button is pressed or for the presence of a digital ON signal at terminal 5 (rotate right) or terminal 6 (rotate left) - see parameters P051 - P053.
(2)If output frequency is selected to be displayed (P001 = 0), the corresponding setpoint is displayed approximately every 1.5 seconds while the inverter is stopped.
(3)The inverter is programmed at the factory for standard applications on Siemens
P084
P083 P082 P085
Figure 10: Typical Motor Rating Plate Example
Note: Ensure that the inverter is configured correctly to the motor, i.e. in the above example delta terminal connection is for 220 V.
3.2.2 Initial Testing
(1)Check that all cables have been connected correctly (section 2) and that all relevant product and plant/location safety precautions have been complied with.
(2)Apply mains power to the inverter.
(3)Ensure that it is safe to start the motor. Press the RUN button on the inverter. The display will change to 5.0 and the motor shaft will begin to turn. It will take one second for the inverter to ramp up to 5 Hz.
(4)Press the STOP button. The display will change to 0.0 and the motor slow to a complete stop within one second.
?? Siemens plc 1997G85139-H1750-U049-B
3.2.3 Basic Operation - 10 Step Guide
The basic method of setting up the inverter for use is described below. This method uses a digital frequency setpoint and requires only the minimum number of parameters to be changed from their default settings. It assumes that a standard Siemens
Step /Action
1. Apply mains power to the inverter.
The display will alternate between the actual frequency (0.0 Hz) and the requested frequency setpoint (5.0 Hz default).
2. Press the parameterisation button.
3. Press the button until parameter P005 is displayed.
4. Press P to display the current frequency setpoint (5 Hz is the factory default setting).
5. Press the button to set the desired frequency setpoint (e.g. 35 Hz).
Button Display
P
P
6. Press P to lock the setting into memory.
7, Press the ??? button to return to P000.
8. Press P to exit the parameterisation procedure.
The display will alternate between the current frequency and the requested frequency setpoint.
9. Start the inverter by pressing the RUN button.
The motor shaft will start to turn and the display will show that the inverter is ramping up to the setpoint of 35 Hz.
Note
The setpoint will be achieved after 7 seconds (35 Hz/50 Hz x 10 s *). If required, the motor???s speed (i.e. frequency) can be varied directly by using the ??? buttons. (Set P011 to 001 to enable the new frequency setting to be retained in memory during periods when the inverter is not running.)
10. Switch the inverter off by pressing the STOP button.
The motor will slow down and come to a controlled stop (takes 7 s **).
*Default
**Default
P
P
4. OPERATING MODES
4.1 Digital Control
For a basic startup configuration using digital control, proceed as follows:
(1)Connect control terminal 5 to terminal 8 via a simple on/off switch. This sets up the motor for clockwise rotation (default).
(2)Apply mains power to the inverter. Set parameter P009 to 002 or 003 to enable all parameters to be adjusted.
(3)Check that parameter P006 is set to 000 to specify digital setpoint.
(4)Set parameter P007 to 000 to specify digital input (i.e. DIN1 (terminal 5) in this case) and disable the front panel controls.
(5)Set parameter P005 to the desired frequency setpoint.
(6)Set parameters P081 to P085 in accordance with the rating plate on the motor (see Figure 10).
Note: In many cases, when default factory parameters are used, the default stator resistance set in P089 will generally suit the default power rating set in P085. Should the inverter and motor ratings differ greatly, it is recommended that the stator resistance of the motor is measured and entered manually into P089. Continuous Boost (P078) and Starting Boost (P079) are dependent on the value of Stator Resistance - too high a value may cause overcurrent trips
(7)Set the external on/off switch to ON. The inverter will now drive the motor at the frequency set by P005.
4.2 Analogue Control
For a basic startup configuration using analogue voltage control, proceed as follows:
(1)Connect control terminal 5 to terminal 8 via a simple on/off switch. This sets up the motor for clockwise rotation (default).
(2)Connect a 4.7 k?? potentiometer to the control terminals as shown in Figure 6 or connect pin 2 (0V) to pin 4 and a 0 - 10 V signal between pin 2 (0V) and pin 3 (AIN+).
(3)Apply mains power to the inverter. Set parameter P009 to 002 or 003 to enable all parameters to be adjusted.
(4)Set parameter P006 to 001 to specify analogue setpoint.
(5)Set parameter P007 to 000 to specify digital input (i.e. DIN1 (terminal 5) in this case) and disable the front panel controls.
(6)Set parameters P021 and P022 to specify the minimum and maximum output frequency settings.
(7)Set parameters P081 to P085 in accordance with the rating plate on the motor (see Figure 10).
Note: In many cases, when default factory parameters are used, the default stator resistance set in P089 will generally suit the default power rating set in P085. Should the inverter and motor ratings differ greatly, it is recommended that the stator resistance of the motor is measured and entered manually into P089. Continuous Boost (P078) and Starting Boost (P079) are dependent on the value of Stator Resistance - too high a value may cause overcurrent trips
(8)Set the external on/off switch to ON. Turn the potentiometer (or adjust the analogue control voltage) until the desired frequency is displayed on the inverter.
?? Siemens plc 1997G85139-H1750-U049-B
4.3 Stopping the Motor
Stopping can be achieved in several ways:
???Cancelling the ON command or pressing the OFF button (O) on the front panel causes the inverter to ramp down at the selected ramp down rate (see P003).
???OFF2 - operation causes the motor to coast to a standstill (see parameters P051 to P053).
???OFF3 - operation causes rapid braking (see parameters P051 to P053).
???DC injection braking up to 250% causes a rapid stop (see P073).
4.4 If the Motor Does Not Start Up
If the display shows a fault code, refer to Section 6.
If the motor does not start up when the ON command has been given, check that the ON command is valid, check if a frequency setpoint has been entered in P005 and check that the motor specifications have been entered correctly under parameters P081 to P085.
If the inverter is configured for operation via the front panel (P007 = 001) and the motor does not start when the RUN button is pressed, check that P121 = 001 (RUN button enabled).
If the motor does not run after parameters have been changed accidentally, reset the inverter to the factory default parameter values by setting parameter P944 to 001 and then pressing P.
4.5 Local and Remote Control
The inverter can be controlled either locally (default), or remotely via a USS data line connected to the RS485
When local control is used, the inverter can only be controlled via the front panel or the control terminals. Control commands, setpoints or parameter changes received via the RS485 interface have no effect.
When operating via remote control the inverter will not accept control commands from the terminals.
Exception: OFF2 or OFF3 can be activated via parameters P051 to P053 (refer to parameters P051 to P053 in section 5).
Several inverters can be connected to an external control unit at the same time. The inverters can be addressed individually.
For further information, refer to the following documents (available from your local Siemens office):
4.6 Closed Loop Control
4.6.1 General Description
The MICROMASTER provides a PI control function for closed loop control (see Figure 11). PI control is ideal for temperature or pressure control, or other applications where the controlled variable changes slowly or where transient errors are not critical. This control loop is not suitable for use in systems where fast response times are required.
Note: The closed loop function is not designed for speed control, but can be used for this provided that fast response times are not required.
When closed loop PI control is enabled (P201 = 002), all setpoints are calibrated between zero and 100%, i.e. a setpoint of 50.0 = 50%. This allows general purpose control of any process variable that is actuated by motor speed and for which a suitable transducer is available.
Setpoint
P205
Figure 11: Closed Loop Control
4.6.2 Hardware Setup
Connect the outputs from the external feedback transducer to control terminals 3 and 4. This analogue input accepts a 0/2 - 10 V signal, has
15 V dc power for the feedback transducer can be supplied from terminals 8 and 9 on the control block.
4.6.3 Parameter Settings
Closed loop control cannot be used unless P201 is first set to 002. Most of the parameters associated with closed loop control are shown in Figure 11. Other parameters which are also associated with closed loop control are as follows:
P001 (value = 007)
P061 (value = 012 or 013)
P210
P220
Descriptions of all closed loop control parameters are provided in section 5. For further detailed information about PI operation refer to the Siemens DA 64 Catalogue.
?? Siemens plc 1997G85139-H1750-U049-B
5. SYSTEM PARAMETERS
Parameters can be changed and set using the
Note: If you press the or ??? button momentarily, the values change step by step. If you keep the buttons pressed for a longer time, the values scroll through rapidly.
Access to parameters is determined by the value set in P009. Check that the key parameters necessary for your application have been programmed.
Note: In the following parameter table:
????????? Indicates parameters that can be changed during operation.
?????? Indicates that the value of this factory setting depends on the rating of the inverter.
To increase the resolution to 0.01 when changing frequency parameters, instead of pressing P momentarily to return to the parameter display, keep the button pressed until the display changes to ???-
If parameters are changed accidentally, all parameters can be reset to their default values by setting parameter P944 to 1 and then pressing P.
5. SYSTEM PARAMETERS
English
Description / Notes
This displays the output selected in P001.
In the event of a fault, the relevant fault code (Fxxx) is displayed (see section 6). In the event of a warning the display flashes. If output frequency has been selected (P001 = 0) and the inverter is OFF, the display alternates between the selected frequency and the actual frequency.
Display selection:
0 = Output frequency (Hz)
1 = Frequency setpoint (i.e. speed at which inverter is set to run) (Hz)
2 = Motor current (A)
3=
4= Not used
5= Motor RPM
6= USS status (see section 8.2)
7= Closed loop control setpoint (% of full scale)
8= Output voltage
This is the time taken for the motor to accelerate from standstill to the maximum frequency as set in P013.
Setting the ramp up time too short can cause the inverter to trip (fault code F002 - overcurrent).
This is the time taken for the motor to decelerate from maximum frequency (P013) to standstill.
Setting the ramp down time too short can cause the inverter to trip (fault code F001 - overvoltage).
This is also the period for which DC injection braking is applied (see P073)
?? Siemens plc 1997G85139-H1750-U049-B
P004 ???
Used to smooth the acceleration/deceleration of the motor (useful in applications where it is important to avoid ???jerking???, e.g. conveyor systems, textiles, etc.).
Smoothing is only effective if the ramp up/down time exceeds 0.3 s.
Total acceleration time = 15 s
Note: The smoothing curve for deceleration is based on the ramp up gradient (P002) and is added to the ramp down time set by P003. Therefore, the ramp down time is affected by changes to P002.
P005 ???
P006
P007
Digital frequency setpoint (Hz)
Frequency setpoint source selection
Keypad control
0 - 400.00
[5.00]
0 - 2
[0]
0 - 1
[1]
Sets the frequency that the inverter will run at when operated in digital mode. Only effective if P006 set to ???0???.
Sets the control mode of the inverter.
0 = Digital. The inverter runs at the frequency set in P005. Alternatively, if P007 is set to zero, the frequency may be controlled by setting any two of binary inputs P051 - P053 to values of 11 and 12.
1 = Analogue. Control via analogue input signal.
2 = Fixed frequency or motor potentiometer. Fixed frequency is only selected if the value of at least one binary input (P051 - P053) = 6, 17 or 18.
Notes: (1) If P006 = 1 and the inverter is set up for remote control operation, the analogue inputs remain active.
(2)Motor potentiometer setpoints via digital inputs are stored when P011 = 1.
0 = Front panel buttons disabled (except STOP, and ???). Control is via digital inputs (see parameters P051 - P053). and ??? may still be used to control frequency provided that P124 = 1 and a digital input has not been selected to perform this function.
1 = Front panel buttons enabled (can be individually disabled depending on the setting of parameters P121 - P124).
Note: The digital inputs for RUN, REVERSE, JOG and increase/ decrease frequency are disabled.
P009 ???
Determines which parameters can be adjusted:
0 = Only parameters from P001 to P009 can be read/set. 1 = Parameters from P001 to P009 can be set and all other
parameters can only be read.
2 = All parameters can be read/set but P009 automatically resets to 0 when power is removed.
3 = All parameters can be read/set.
Parameter
P011
Description / Notes
0 = Disabled
1 = Enabled after
P012 ???
P013 ???
P014 ???
P015 ???
P016 ???
Allows the inverter to start onto a spinning motor.
Under normal circumstances the inverter runs the motor up from 0 Hz. However, if the motor is still spinning or is being driven by the load, it will undergo braking before running back up to the setpoint - this can cause an overcurrent trip. By using a flying restart, the inverter ???homes in??? on the motor's speed and runs it up from that speed to the setpoint.Note: If the motor has stopped or is rotating slowly, some ???rocking??? may occur as the inverter senses the direction of rotation prior to restarting.(See also P020)
0 = Normal restart
1 = Flying restart after power up, fault or OFF2 ( if P018 = 1).
2 = Flying restart every time (useful in circumstances where the motor can be driven by the load).
P017 ???
P018 ???
response to STOP commands and requests to reduce frequency. Note: P004 must be set to a value > 0.0 for this parameter to have
any effect.
WARNING: While waiting to
P019 ???
P020
P021 ???
?? Siemens plc 1997G85139-H1750-U049-B
P023 ???
P024 ???
Analogue input function
Analogue setpoint addition
0 - 2
[0]
0 - 2
[0]
0 = 0 V to 10 V
1 = 2 V to 10 V
2 = 2 V* to 10 V
* The inverter will come to a controlled stop if V < 1 V.
WARNING: The motor can automatically run without a potentiometer or voltage source connected between pins 3 and 4.
WARNING: With P023=2, the inverter will automatically start when V goes above 1 V. This equally applies to analogue and digital control (i.e. P006 = 0 or 1).
If the inverter is not in analogue mode (P006 = 0 or 2), setting this parameter to ???1??? causes the analogue input value to be added.
0 = No addition.
1 = Addition of the analogue setpoint (defined by P023) to the fixed frequency or the motor potentiometer frequency.
2 = Scaling of digital/fixed setpoint by analogue input (P023) in the range 0 - 100%.
Note: By selecting a combination of reversed negative fixed frequency settings and analogue setpoint addition, it is possible to configure the inverter for ???centre zero??? operation with a
P027 ???
P028 ???
P029 ???
P031 ???
P032 ???
Skip frequency 2 (Hz)
Skip frequency 3 (Hz)
Skip frequency 4 (Hz)
Jog frequency right (Hz)
Jog frequency left (Hz)
0 - 400.00
[0.00]
0 - 400.00
[0.00]
0 - 400.00
[0.00]
0 - 400.00
[5.00]
0 - 400.00
[5.00]
See P014.
See P014.
See P014.
Jogging is used to advance the motor by small amounts. It is controlled via the JOG button or with a
If jog right is enabled (DINn = 7), this parameter controls the frequency at which the inverter will run when the switch is closed. Unlike other setpoints, it can be set lower than the minimum frequency.
If jog left is enabled (DINn = 8), this parameter controls the frequency at which the inverter will run when the switch is closed. Unlike other setpoints, it can be set lower than the minimum frequency.
P041 ???
P042 ???
P043 ???
P044 ???
P045
??? Fixed setpoints not inverted. ??? Fixed setpoints inverted.
P046 ???
P047 ???
P048 ???
P050
Fixed frequency 5 (Hz)
Fixed frequency 6 (Hz)
Fixed frequency 7(Hz)
Inversion fixed setpoints for fixed frequencies 5 - 7
0 - 400.00
[25.00]
0 - 400.00
[30.00]
0 - 400.00
[35.00]
0 - 7
[0]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
Valid if P006 = 2 and P051 = P052 = P053 = 17.
Valid if P006 = 2 and P051 = P052 = P053 = 17.
Sets the direction of rotation for the fixed frequency:
??? Fixed setpoints not inverted. ??? Fixed setpoints inverted.
?? Siemens plc 1997G85139-H1750-U049-B
English
5. SYSTEM PARAMETERS
Description / Notes
*Only effective when P007 = 0.
**See section 4.3.
Binary Coded Fixed Frequency Mapping
(P051, P052, P053 = 17)
5. SYSTEM PARAMETERS
English
Description / Notes
This operates in the same manner as the external brake control (described in P063/P064), except that the relay is not activated.
0 = Normal stop mode
1 - 3 = Do not use
4 = Combination stop mode
Only effective if the relay output is set to control an external brake (P061 = 4). In this case when the inverter is switched on, it will run at the minimum frequency for the time set by this parameter before releasing the brake control relay and ramping up (see illustration in P064).
As P063, only effective if the relay output is set to control an external brake. This defines the period for which the inverter continues to run at the minimum frequency after ramping down and while the external brake is applied.
Notes: (1) Settings for P063 and P064 should be slightly longer
?? Siemens plc 1997G85139-H1750-U049-B
The DC brake can be activated using DIN1 - DIN3 (braking is active for as long as the DIN is high - see P051 - P053).
P074 ???
P076 ???
400V inverters require the continuous current rating reduced for operation below 5Hz, when operating at switching frequencies greater than 4kHz and with boost values greater than 100% (P078 + P079). These are typically as follows:
MM37/3- MM750/3 50%xP083 80%xP083
Operates continuously over the whole frequency range.
For many applications it is necessary to increase low frequency torque. This parameter sets the
P079 ???
P081
P082
P083
P084
P085
P089 ???
P091 ???
?? Siemens plc 1997G85139-H1750-U049-B
Sets the baud rate of the RS485 serial interface (USS protocol):
3= 1200 baud
4= 2400 baud
5= 4800 baud
6= 9600 baud
7= 19200 baud
Note: Some RS232 to RS485 converters are not capable of baud rates higher than 4800.
This is the maximum permissible period between two incoming data telegrams. This feature is used to turn off the inverter in the event of a communications failure.
Timing starts after a valid data telegram has been received and if a further data telegram is not received within the specified time period, the inverter will trip and display fault code F008.
Setting the value to zero switches off the control.
Setpoints are transmitted to the inverter via the serial link as percentages. The value entered in this parameter represents 100% (HSW = 4000H).
0 = Compatible with 0.1 Hz resolution
1 = Enable 0.01 Hz resolution
2 = HSW is not scaled but represents the actual frequency value to a resolution of 0.01 Hz (e.g. 5000 = 50 Hz).
0 = Option module not present
1 = PROFIBUS module (enables parameters relating to PROFIBUS)
This sets the inverter for European or USA supply and motor frequency:
0 = Europe (50 Hz)
1 = USA (60 Hz)
Note: After setting P101 = 1 the inverter must be
Note: If P101 = 1 then the rating is displayed in hp.
1 = Normal operation (FORWARD/REVERSE operation allowed)
P131
P132
P134
P135
P137
P140
P141
P142
P143
P201
P202 ???
P203 ???
P205 ???
P206 ???
P207 ???
P208
Frequency setpoint (Hz)
Motor current (A)
DC link voltage (V)
Motor RPM
Output voltage (V)
Most recent fault code
Most recent fault code
Most recent fault code
Most recent fault code
Closed loop mode
P gain (%)
I gain (%)
Sample interval (x 25 ms)
Transducer filtering
Integral capture range (%)
Transducer type
[0]1 = Not used.
2 = Closed loop control using analogue input for transducer feedback input.
0.0- 999.9 Proportional gain.
[1.0]
[0]1 - 255 = Low pass filtering applied to sensor.
0 - 100 Percentage error above which integral term is reset to zero. [100]
0 - 1 0 = An increase in motor speed causes an increase in sensor
[0]voltage/current output.
1= An increase in motor speed causes a decrease in sensor voltage/current output.
?? Siemens plc 1997G85139-H1750-U049-B
English
Parameter Function
5. SYSTEM PARAMETERS
0.0- 100.0 Read only. Value is a percentage of full scale of the selected input.
0 - 1 0 = Normal operation
[0]1 = Switch off inverter output at or below minimum frequency.
Specific to
Access only possible with P099 = 1
0 - 4 Sets the inverter for local control or remote control over the serial link:
[0]0 = Local control
1 = Remote control (and setting of parameter values)
2 = Local control (but remote control of frequency)
3 = Remote control (but local control of frequency)
4 = Local control (but remote read and write access to parameters and facility to reset trips)
Note: When operating the inverter via remote control (P910 = 1 or 3), the analogue input remains active when P006 = 1 and is added to the setpoint.
Specific to
0.00- 99.99 Contains the software version number and cannot be changed.
0 - 255 You can use this parameter to allocate a unique reference number to
[0]the inverter. It has no operational effect.
Specific to
Access only possible with P099 = 1
P947
P958
1 = Changes to parameter settings are retained during periods when power is removed.
WARNING: When using the serial link to update the parameter set held in EEPROM, care must be taken not to exceed the maximum number of write cycles to this EEPROM - this is approximately 50,000 write cycles. Exceeding this number of write cycles would result in corruption of the stored data and subsequent data loss. The number of read cycles are unlimited.
?? Siemens plc 1997G85139-H1750-U049-B
6. FAULT CODES
In the event of a failure, the inverter switches off and a fault code appears on the display. The last fault that occurred is stored in parameter P930. e.g. ???0003??? indicates that the last error was F003.
Fault Code
F001
F002
F003
F005
F008
F010
F011
F012
F013
F018
F030
F031
F033
F036
F074
F106
F112
F151 - F153
F188
F201
F212
Cause
Overvoltage
Overcurrent
Overload
Inverter overtemperature (internal PTC)
USS protocol timeout
Initialisation fault / Parameter loss *
Internal interface fault *
External trip (PTC)
Programme fault *
PROFIBUS link failure
Option module to link failure
PROFIBUS configuration error
PROFIBUS module watchdog trip
Motor overtemperature by I2t calculation
Parameter fault P006
Parameter fault P012/P013
Digital input parameter fault
Automatic calibration failure
P006 = 1 while P201 = 2
Parameter fault P211/P212
Corrective Action
Check whether supply voltage is within the limits indicated on the rating plate. Increase the ramp down time (P003).
Check whether the required braking power is within the specified limits.
Check whether the motor power corresponds to the inverter power. Check that the cable length limits have not been exceeded.
Check motor lead and motor for
Check whether the motor parameters (P081 - P086) correspond with the motor being used.
Check the stator resistance (P089). Increase the
Check whether the motor is obstructed or overloaded.
Check whether the motor is overloaded.
Increase the maximum motor frequency if a motor with high slip is used.
Check that the ambient temperature is not too high.
Check that the air inlet and outlet are not obstructed.
Check that the integral fan is working.
Check the serial interface.
Check the settings of the bus master and P091 - P093.
Check whether the timeout interval is too short (P093).
Check the entire parameter set. Set P009 to ???0000??? before power down.
Switch off power and switch on again.
Check if motor is overloaded.
Switch off power and switch on again.
Automatic
WARNING: The inverter may start at any time.
Check the integrity of the link.
Check the integrity of the link.
Check the PROFIBUS configuration.
Replace PROFIBUS module
Check that the motor current does not exceed the value set in P083.
Parameterise fixed frequency(ies) and/or motor potentiometer on the digital inputs.
Set parameter P012 < P013.
Check the settings of digital inputs P051 to P053.
Motor not connected to inverter - connect motor.
If the fault persists, set P088 = 0 and then enter the stator resistance of the motor into P089 manually.
Change parameter P006 and/or P201.
Set parameter P211 < P212.
* Ensure that the wiring guidelines described in section 2.1 have been complied with.
When the fault has been corrected the inverter can be reset. To do this press button P twice (once to display P000 and the second time to reset the fault), or erase the fault via a binary input (see parameters P051 - P053 in section 5) or via the serial interface.
Optional external Class A and Class B filters are available (see section 8.3).
Notes
a
Siemens 4
b
Assumes
c
MM300 and MM300/2 require an external choke (e.g.
?? Siemens plc 1997G85139-H1750-U049-B
Options / Accessories
8. SUPPLEMENTARY INFORMATIONEnglish
8. SUPPLEMENTARY INFORMATION
8.1 Application Example
Setup procedure for a simple application
This application is now to be modified as follows:
8.2 USS Status Codes
The following list gives the meaning of status codes displayed on the front panel of the inverter when the serial link is in use and parameter P001 is set to 006:
001 Message OK
002 Slave address received
100Invalid start character
101Timeout
102Checksum error
103Incorrect message length
104Parity fail
Notes
(1)The display flashes whenever a byte is received, thus giving a basic indication that a serial link connection is established.
(2)If ???100??? flashes on the display continuously, this usually indicates a bus termination fault.
?? Siemens plc 1997G85139-H1750-U049-B
8.3
All manufacturers / assemblers of electrical apparatus which performs a complete intrinsic function which is placed on the market as a single unit intended for the end user must comply with the EMC directive EEC/89/336 after January 1996. There are three routes by which the manufacturer/assembler can demonstrate compliance:
1.
This is a manufacturer???s declaration that the European standards applicable to the electrical environment for which the apparatus is intended have been met. Only standards which have been officially published in the Official Journal of the European Community can be cited in the manufacturer???s declaration.
2.Technical Construction File
A technical construction file can be prepared for the apparatus describing its EMC characteristics. This file must be approved by a ???Competent Body??? appointed by the appropriate European government organisation. This approach allows the use of standards which are still in preparation.
3.EC
This approach is only applicable to radio communication transmitting apparatus.
The MICROMASTER units do not have an intrinsic function until connected with other components (e.g. a motor). Therefore, the basic units are not allowed to be CE marked for compliance with the EMC directive. However, full details are provided below of the EMC performance characteristics of the products when they are installed in accordance with the wiring recommendations in section 2.1.
Three classes of EMC performance are available as detailed below. Note that these levels of performance are only achieved when using the default switching frequency (or less) and a maximum motor cable length of 25 m.
Class 1: General Industrial
Compliance with the EMC Product Standard for Power Drive Systems EN
* Limits not required inside a plant where no other consumers are connected to the same electricity supply transformer.
Class 2: Filtered Industrial
This level of performance will allow the manufacturer/assembler to
Immunity:
Supply Voltage Distortion
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations
IEC
IEC
Class 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assembler to
Note:
The MICROMASTERS are intended exclusively for professional applications. Therefore, they do not fall within the scope of the harmonics emissions specification EN
?? Siemens plc 1997G85139-H1750-U049-B
Compliance Table:
Model No.
MM12 - MM220
MM12/2 - MM300/2
MM12/2 - MM220/2 with external filter (see table) 1 phase input only
MM150/3 - MM750/3
MM150/3 - MM750/3 with external filter (see table)
EMC Class
Class 2
Class 1
Class 2*
Class 1
Class 2*
*If the installation of the inverter reduces the radio frequency field emissions (e.g. by installation in a steel enclosure), Class 3 limits will typically be met.
External Filters:
B
*Class B filters are for use with 1/3 AC 230V unfiltered units.
8.4Environmental Aspects
Transport and Storage
Protect the inverter against physical shocks and vibration during transport and storage. The unit must also be protected against water (rainfall) and excessive temperatures (see section 7).
The inverter???s packaging is
If the unit has been in storage
Dismantling and Disposal
The unit can be
The component parts can be
Documentation
This handbook is printed on
8.5 User???s Parameter Settings
Record your own parameter settings in the table below:
Herausgegeben vom
Bereich
Postfach 3269,
Siemens plc Sir William Siemens House Princess Road Manchester M20 8UR
?? Siemens plc 1997
Printed in EU