SIMOTION
D410
Commissioning Manual
Valid for SIMOTION D410 DP and D410 PN
08/2008 Edition
Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
WARNING
This device may only be used for the applications described in the catalog or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance.
Trademarks
All names identified by ?? are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Preface
Contents of the commissioning manual
This manual is part of the SIMOTION D4xx documentation package, Edition 08/2008. This manual describes commissioning of the SIMOTION devices D410 DP and D410 PN.
Information blocks in this manual
The following information blocks describe the purpose and use of the commissioning manual.
???Description
This section provides information pertaining to the SIMOTION system and its integration into the information landscape.
???Commissioning (hardware)
This section describes how to start up the device and what you must take into account.
???Configuring SIMOTION D410
This section describes how to integrate SIMOTION D410 in a project and how to configure the interfaces.
???Commissioning (software)
This section describes how to configure a plant and how to test the drives and axes you configured.
???Maintenance and service
This section describes how to replace a module, how to run updates, and how to modify settings.
???Diagnostics data
This section provides information about diagnostic possibilities and LED states.
???Appendices with factual information for reference (for example, Standards and Approvals, and ESD)
???Index for locating information.
SIMOTION Documentation
An overview of the SIMOTION documentation can be found in a separate list of references.
This documentation is included as electronic documentation with the supplied SIMOTION
SCOUT.
Preface
The SIMOTION documentation consists of 9 documentation packages containing approximately 80 SIMOTION documents and documents on related systems (e.g. SINAMICS).
The following documentation packages are available for SIMOTION V4.1 SP2:
???SIMOTION Engineering System
???SIMOTION System and Function Descriptions
???SIMOTION Diagnostics
???SIMOTION Programming
???SIMOTION Programming - References
???SIMOTION C
???SIMOTION P350
???SIMOTION D4xx
???SIMOTION Supplementary Documentation
Hotline and Internet addresses
Technical support
If you have any technical questions, please contact our hotline:
Preface
Note
http://www.siemens.com/automation/service&support
Calls are subject to charge, e.g. 0.14 ???/min. on the German landline network. Tariffs of other phone companies may differ.
Questions about this documentation
If you have any questions (suggestions, corrections) regarding this documentation, please fax or
Siemens Internet address
The latest information about SIMOTION products, product support, and FAQs can be found on the Internet at:
???General information:
???http://www.siemens.de/simotion (German)
???http://www.siemens.com/simotion (international)
???Product support:
???http://support.automation.siemens.com/WW/view/en/10805436
Additional support
We also offer introductory courses to help you familiarize yourself with SIMOTION.
Please contact your regional training center or our main training center at
Nuremberg, phone +49 (911) 895 3202.
Information about training courses on offer can be found at:
www.sitrain.com
Preface
Disposal and recycling
SIMOTION D410 is an environmentally friendly product! It includes the following features:
???In spite of its excellent resistance to fire, the
???Identification of plastic materials in accordance with DIN 54840
???Less material used because the unit is smaller and with fewer components thanks to integration in ASICs
SIMOTION D410 can be recycled because it is made with
For
http://www.ad.siemens.com/partner
Further information / FAQs
You can find further information on this manual under the following FAQs:
http://support.automation.siemens.com/WW/view/de/27585482
The following resources are also available:
???SIMOTION - Utilities & Applications CD: This CD is supplied together with the SIMOTION SCOUT and, along with FAQs, also contains free utilities (e.g. calculation tools, optimization tools, etc.) and application examples
???The latest FAQs for SIMOTION can be found at: http://support.automation.siemens.com/WW/view/de/10805436
???SIMOTION SCOUT online help
???Additional documentation: see SIMOTION references
Table of contents
Table of contents
1.1System overview
Overview
In SIMOTION D, the SIMOTION functionality is integrated directly in the
SIMOTION D410 is a module drive system for single axes, which solves demanding drive tasks for a very wide range of industrial applications. SIMOTION D410 supplements D425, D435 and D445, the three power levels for
SIMOTION D is an integral part of the Totally Integrated Automation (TIA) concept. TIA features standardized data management, configuration and communication over all products and systems. Thus, an extensive toolbox of automation modules is also available for SIMOTION D410.
Application
Combining a power module with SIMOTION D410 forms a compact single drive for machine and plant engineering.
Applications include:
???Machine concepts with central drive (e.g., pressing, printing and packaging machines, . .
.)
???Modular machine concepts where the machine modules broken down to single axes
???Single drives with high accuracy, stability and concentricity requirements (compared with standard drives) in machine and industrial plant engineering
???Single drives for transport tasks (conveying, raising, lowering)
???Single drives with integrated PLC functionality and expanded motion control functionality such as output cam or cams
???Drives without power recovery (wire drawing, extruding)
???Drive connections with high availability requirements (incoming supply failure may not cause all axes to fail)
Product variants
SIMOTION D410 comes in two variants:
???SIMOTION D410 DP with PROFIBUS DP interface.
???SIMOTION D410 PN with PROFINET interface.
Description
1.1 System overview
System integration
SIMOTION provides an optimized system platform for automation and drive solutions where the main focus is on motion control applications and technology tasks.
The SIMOTION system is made up of three components:
???SIMOTION SCOUT Engineering System
???Runtime Software
???Hardware platforms
The innovative SIMOTION concept involves integrating pure automation and motion functions, which have been traditionally isolated in the past.
Figure
SIMOTION can be used with all machines with motion control tasks. The focus is on a simple and flexible solution to a wide variety of motion control tasks. In order to achieve this in the best way possible, a new system approach has been introduced:
the fusion of motion control with two other control functions, which are found in most machines: PLC and technology functions.
This approach enables motion control of axes and machines with only one system. The same applies to technology functions, such as pressure control of a hydraulic axis. A seamless switch can be made from
Description 1.1 System overview
Combining the three control functions of motion control, PLC and technology functions has the following benefits:
???Lower engineering expenditure and higher machine performance.
???Interfaces between individual components requiring rapid response are no longer needed.
???Simple, standardized and transparent programming and diagnostics for the complete machine.
Description
1.2 System components
1.2System components
Overview
SIMOTION D410 communicates with the components of the automation landscape via the following interfaces:
???PROFIBUS DP (SIMOTION D410 DP only)
???PROFINET (SIMOTION D410 PN only)
???
???Power Module Interface
???SIMOTION D features a SINAMICS Integrated drive element. Communication with the SINAMICS Integrated (node 3) is via PROFIBUS mechanisms (DP integrated).
The most important system components and their functions are listed in the following table.
Description 1.2 System components
PROFIBUS DP
SIMOTION D410 DP can communicate via PROFIBUS DP interface to the following components:
Note
Note that only one real axis can be used on a SIMOTION D410.
Description
1.2 System components
Note
Please note that not all modules for the I/O systems listed above are enabled for SIMOTION. Moreover,
A list of all I/O modules that can currently be used with SIMOTION is available under the following link:
http://support.automation.siemens.com/WW/view/de/11886029
In addition to the I/O modules enabled for SIMOTION, all certified standard slaves can, in principle, be connected to SIMOTION if they support the following:
???Cyclic data traffic
???Acyclic data traffic
???Isochronous data traffic
These modules are integrated via the GSD file from the device manufacturer.
Note
Please note that in individual cases further boundary conditions must be fulfilled in order to integrate a standard slave into SIMOTION. For example, "driver modules" in the form of function blocks are required for some modules, which enable integration or make it especially easy.
For modules enabled for SIMOTION (e.g.,
Description 1.2 System components
PROFINET
SIMOTION D410 PN can communicate via PROFINET interface to the following components:
Note
Note that only one real axis can be used on a SIMOTION D410.
Note
A list of all I/O modules that can currently be used with SIMOTION is available at the following link:
http://support.automation.siemens.com/WW/view/de/11886029
Description
1.2 System components
SIMOTION D410 can communicate via
Note
Note that SIMOTION D410 does not support the CX32 expansion!
Description 1.3 SIMOTION D410 DP display
1.3SIMOTION D410 DP display
View
The following figure shows SIMOTION D410 DP with the interfaces and front elements.
;
6HULDOLQWHUIDFHQRIXQFWLRQ
; 352),%86
0VFUHZRQVKLHOG FRQQHFWLRQ
; (OHFWURQLFVSRZHUVXSSO\
&RPSDFW)ODVKbFDUG
; (3WHUPLQDOVWHPSHUDWXUH VHQVRUFRQQHFWLRQ
3RZHU0RGXOH,QWHUIDFH30,)
; (QFRGHULQWHUIDFH+7/77/66,
; '5,9(&/L4LQWHUIDFH
6LGHQDPHSODWH
7770 0HDVXULQJVRFNHWV
/('GLVSOD\V
7\SHSODWH
%23LQWHUIDFH QRIXQFWLRQ
5(6(7EXWWRQ
0RGHVHOHFWRUVZLWFK ',3VZLWFK
Figure
Note
The label underneath the mode selector lists the switch settings for the operating states of the SIMOTION D410.
Description
1.3 SIMOTION D410 DP display
Interfaces
The SIMOTION D410 DP interfaces are described in the following tables.
Description 1.3 SIMOTION D410 DP display
Nameplates
The following figure shows you all the information included on the nameplates located on the side of the unit.
0RGXOHGHVLJQDWLRQ
2UGHUQXPEHU
6HULDOQXPEHU
+:YHUVLRQ
Figure
Description
1.3 SIMOTION D410 DP display
The following nameplate includes the SIMOTION D410 DP barcode numbers and is located on the front side of the module.
%DUFRGH0/)%1R$8$$$$
3$8$$$$
%DUFRGH
6DFK1U$(
Figure
Note
The contents of the individual nameplate fields on the current module may differ from those described in this Manual (e.g., updated product status, space for approvals and identifications, etc.).
Description 1.4 SIMOTION D410 PN display
1.4SIMOTION D410 PN display
View
The following figure shows SIMOTION D410 PN with the interfaces and front elements.
;
'LJLWDOLQSXWVRXWSXWV
Figure
Description
1.4 SIMOTION D410 PN display
Interfaces
The SIMOTION D410 PN interfaces are described in the following tables.
Description 1.4 SIMOTION D410 PN display
Nameplates
The following figure shows you all the information included on the nameplates located on the side of the unit.
0RGXOHGHVLJQDWLRQ
2UGHUQXPEHU
6HULDOQXPEHU
+:YHUVLRQ
Figure
Description
1.4 SIMOTION D410 PN display
The following nameplate includes the MAC address of the PROFINET interface (ports X200 and X201) and is located on the front side of the module.
$8$%$$ $(
;;;;;;
%DUFRGH0$&DGGUHVV
Figure
Note
The contents of the individual nameplate fields on the current module may differ from those described in this Manual (e.g., updated product status, space for approvals and identifications, etc.).
Description 1.5 The CompactFlash card
1.5The CompactFlash card
CompactFlash card
The following figure shows you all the information included on the nameplate of the
CompactFlash card (CF card).
3RLQWHUWRVKRZSOXJLQGLUHFWLRQ
RIWKH&)FDUG
Figure
For versions V4.1 SP1 HF6 and higher,
Example with Z option for a combined SIMOTION IT license + 2 TControl licenses:
Z=J00+T02
A maximum of 7 different Z options are printed on the type plate of the CF card. When there are more than 7 different Z options, the text "Z = see delivery order" is printed on the CF card in place of the Z option.
Description
1.6 Licensing
Available Z options / licenses for SIMOTION D CF cards
The following Z options are available for SIMOTION D410:
TControl temperature control:
???Txx ??? TControl license and number (e.g. T03 = 3 TControl licenses)
SIMOTION IT:
???D00 ??? IT DIAG license
???X00 ??? OPC
???J00 ??? Combined license for SIMOTION IT, comprises SIMOTION IT Virtual Machine for Java applications, SIMOTION IT DIAG and SIMOTION IT OPC
Safety functions:
???Fxx - License for SINAMICS Safety Integrated Extended Functions (e.g., F01 = 1 license for safety functions)
1.6Licensing
SIMOTION D410 licensing
SIMOTION D410 is a modular drive system for
Licenses are required for runtime functions such as SIMOTION IT DIAG. These can be pre- installed on a CompactFlash card (CF card) or ordered separately.
Additional references
For more information about license management, see the SIMOTION SCOUT Configuring Manual. General information about licensing can be found in the Motion Control SIMOTION, SINAMICS S120 catalog and motors for production machines catalog, PM21 2008.
Description 1.7 Safety information
1.7Safety information
Observe the following safety information when working with SIMOTION D410 and its components!
CAUTION
The CompactFlash card may only be unplugged and plugged in when SIMOTION D410 is switched off (zero current)!
CAUTION
The 50 mm clearances above and below the components must be observed. The ventilation openings may not be covered by connecting cables.
2.1Prerequisites for commissioning
Prerequisites
Prerequisites for commissioning the SIMOTION D410:
???You have completed installation and the wiring of your system with SIMOTION D410.
???A programming device / PC is available.
Connecting a programming device / PC to SIMOTION D410
You can interconnect the programming device / PC:
???With the PROFIBUS interface of SIMOTION D410 DP (X21 connector) using a connecting cable.
Information pertaining to cable lengths for PROFIBUS DP is available in the
SIMOTION D410 Manual.
???With the PROFINET interface of SIMOTION D410 PN (X200 or X201 connector) using a twisted pair cable.
Information pertaining to PROFINET communication is available in chapter "Configuring PROFINET".
System requirements
System requirements for hardware commissioning:
???The programming device must be equipped with a PROFIBUS or Ethernet adapter.
???The programming device / PC must be interconnected with SIMOTION D410 DP (connector X21) for online communication on PROFIBUS DP.
???The programming device / PC must be interconnected with SIMOTION D410 PN (connector X200 and 201) for online communication on PROFINET.
???You need a CF adapter on the programming device / PC to write to the Compact Flash Card (for example, a SIMOTION firmware update).
Commissioning (hardware)
2.2 Inserting the Compact Flash card
2.2Inserting the Compact Flash card
Properties of the CF card
The CF card is mandatory for operation of SIMOTION D410. The SIMOTION kernel and the drive control software (SINAMICS firmware) are installed on the CF card.
The CompactFlash card must be inserted when you start up SIMOTION D410 in order to load the SIMOTION kernel.
Note
The Compact Flash Card may only be removed and inserted while SIMOTION D410 is in de- energized state!
Procedure
Insert the CompactFlash Card as follows:
1.The insertion direction of the CompactFlash Card is identified by an arrow on the card and a matching arrow on the slot. Align the arrows when inserting the CompactFlash Card.
2.Gently push the CompactFlash Card into the card slot of SIMOTION D410 until it engages. The properly inserted card does not protrude from the SIMOTION D410 housing.
Figure
Commissioning (hardware) 2.3 Switching on the power supply
2.3Switching on the power supply
Checking the system
Check the system installation and wiring once again before you switch it on. Observe the
???Have you observed all ESD measures when handling the components?
???Are all connectors properly inserted and interlocked / screwed on?
???Are all components grounded and all shields terminated?
???Have you made allowances for sufficient load capacity of the central power supply?
Switching on the external power supply
Power is supplied to the SIMOTION D410 using an external power supply unit, for example, using SITOP power supplies (in special circumstances, the SIMOTION D410 can also be supplied using the PM340 Power Module, see SIMOTION D410 Manual).
Switch on the power supply after having checked off all items of the checklist.
CAUTION
It is imperative to prevent the external 24 VDC power supply to SIMOTION D410 from being interrupted for a duration longer than 3 ms. Operation of SIMOTION D410 is stopped on expiration of these 3 ms and can only be recovered by cycling power Off > On.
Additional information is available in chapter "User memory concept".
Startup of SIMOTION D410
The startup of SIMOTION D410 is initiated after the power supply is activated:
1.The RDY LED is lit and the red RUN/STOP LED briefly lights up at the beginning of the startup sequence. These LEDs can be used to monitor the startup sequence. Any errors are displayed.
2.Startup of the SIMOTION kernel.
3.All
Note
Startup of SIMOTION D410 is completed as soon as its RDY LED is lit in green color and the RUN/STOP LED is lit in yellow or green color.
The SIMOTION D410 is ready for configuring after successful completion of the startup.
Commissioning (hardware) 2.4 RESET button
2.4RESET button
Arrangement
The RESET button is located behind the blanking plate on the SIMOTION D410.
Performing a reset operation
A reset causes the entire system to be reset and requires the system to be
Commissioning (hardware)
2.5 User memory concept
2.5User memory concept
2.5.1SIMOTION D410 memory model
The following figure provides an overview of the SIMOTION D410 memory model.
Figure
The next chapters provide information pertaining to user memories and to the sequences of specific user actions.
See also
Commissioning (hardware) 2.5 User memory concept
2.5.2Properties of the user memories
Properties of
More information
IP and DP parameters in
The IP and DP parameters are loaded from configuration data on the CompactFlash Card during startup for use by the SIMOTION device. The SIMOTION D410 can use the addresses defined in these data to go online. The IP and DP parameters on the CompactFlash Card are also written to
Commissioning (hardware)
2.5 User memory concept
Volatile data
Definition of the properties of volatile data:
???Volatile data resides in the RAM area of SIMOTION D410.
???The download data of SIMOTION SCOUT is written to this memory.
???These data is lost after the SIMOTION D410 is shut down.
???Contents of the "volatile data" area:
???SIMOTION kernel
???Technology packages (TP)
???User data (programs, configuration data, parameters)
Figure
You can find additional information about memory management in SIMOTION in the
SIMOTION Basic Functions Function Manual.
Commissioning (hardware) 2.5 User memory concept
CompactFlash Card
The CompactFlash Card contains the following data:
???SIMOTION kernel
???Technology packages (TP)
???User data (units, configuration data, parameters, task configuration)
???IP parameters (IP address, subnet mask, router address)
???DP parameters (PROFIBUS DP address, baud rate)
2.5.3Operator actions and their impact on user memory
The next section describes the user actions identified in the "SIMOTION D410 memory model" by arrows and their impact on user memory.
Download SIMOTION SCOUT
The "Download" command transfers the following data from the Engineering System to the "volatile data" area:
???User data (units, configuration data, parameters, task configuration)
???Technology packages
The IP and DP parameters are furthermore saved to the
Copy RAM to ROM
The "Copy RAM to ROM" command is used on the ES to save the following data to the CompactFlash Card:
???Technology packages and user data (units, configuration data, parameters, task configuration) of the "volatile data" area
???Actual values are copied to the "volatile data" area, depending on the settings in
SIMOTION SCOUT
Note
The "Copy RAM to ROM" command does not save the actual values of the retain variables to the CompactFlash Card:
Commissioning (hardware)
2.5 User memory concept
Startup of SIMOTION D410
The SIMOTION kernel is loaded from the CompactFlash Card to the "volatile data" area during the startup of SIMOTION D410.
Volatile data is lost if you shut down the SIMOTION D410 module after the download. Data loaded from the CompactFlash Card at the next restart:
???The technology packages and user data to the "volatile data" area
???IP and DP parameters to the
Backup of
The "_savePersistentMemoryData" system function is used to save the contents of non- volatile data to the CompactFlash Card. This backup prevents the retain variables and the absolute encoder position from being lost if a component is replaced.
The backup copy is saved to the "PMEMORY.XML" backup file in the "USER/SIMOTION" folder. On system side it is always ensured that a consistent overall image of the
NOTICE
An absolute encoder overflow after "_savePersistentMemoryData" was executed indicates that the restored
Commissioning (hardware) 2.5 User memory concept
Startup and
The table below describes the startup situations which may develop in terms of the non- volatile data and how to handle such situations.
Diagnostics of
Users can determine the status of
The following message events are entered once in the diagnostics buffer when they occur:
Commissioning (hardware)
2.5 User memory concept
Refer to the SIMOTION SCOUT Configuration Manual for information about how to read out the contents of the diagnostic buffer.
System variable "persistentMemoryPowerMonitoring.persistentDataState" indicates the status of
See also
3.1Software requirements
SIMOTION SCOUT Engineering System
The SIMOTION SCOUT Engineering System must be installed on your programming device / PC in order to commission the SIMOTION D410. Observe the information on the current
"SIMOTION SCOUT" CD.
For information on how to install SIMOTION SCOUT on your programming device / PC, refer to the SIMOTION SCOUT Configuration Manual.
3.2Inserting SIMOTION D410 into a project
Creating a project and configuring the programming device / PC interface
Proceed as follows in order to create a project in SIMOTION SCOUT and to insert a
SIMOTION D410:
1.Select the "Project > New..." menu.
2.Enter a name for your project in the "New Project" dialog box and confirm your entry with "OK".
A new folder is generated in the Project Navigator and assigned the name of the project.
3.
4.The "Properties" dialog box of the (PROFIBUS or PROFINET) interface opens where you set up the connection to the programming device / PC according to the module characteristics.
Configuring SIMOTION D410
3.2 Inserting SIMOTION D410 into a project
Communication with the programming device / PC via PROFIBUS (only for D410 DP)
1.Select the PROFIBUS interface from the "Properties - PROFIBUS/MPI" dialog box and confirm your selection with "OK".
2.The connection to the programming device / PC is activated automatically and HW Config opens.
Note
The active state setting of the connection to the programming device / PC is only visualized in NetPro!
Interconnection with the programming device / PC on PROFINET (only for D410 DN)
The "Properties - Ethernet Interface" dialog box is open.
Figure
Program the following parameters in the "Properties - Ethernet Interface" dialog box:
1.Click "New".
The "New Subnet Industrial Ethernet" dialog box opens. Rename the new subnet, or accept the default name by clicking "OK".
2.Select the new Ethernet subnet which is now displayed in the "Properties - Ethernet Interface" dialog box.
3.Define your addresses in the "IP address" and "Subnet mask" fields of the "Properties - Ethernet Interface" dialog box. Change to the "Network node" field and define whether you are going to use a router and, if yes, enter the router address. Confirm with "OK".
4.Select the PROFINET interface from the "Properties" dialog box and confirm your selection with "OK".
5.The connection to the programming device / PC is activated automatically and HW Config opens.
Configuring SIMOTION D410 3.2 Inserting SIMOTION D410 into a project
Note
The active state setting of the connection to the programming device / PC is only visualized in NetPro!
Representation in HW Config
SIMOTION D410 is represented in HW Config.
Figure
Configuring SIMOTION D410
3.3 Configuring the PROFIBUS DP interface (only D410 DP)
3.3Configuring the PROFIBUS DP interface (only D410 DP)
3.3.1General information about PROFIBUS DP communication
Definition of PROFIBUS DP
PROFIBUS DP is an international, open field bus standard specified in the European field bus Standard EN 50170 Part 2. PROFIBUS DP is optimized for
Components communicating on PROFIBUS DP are classified as master and slave components.
???Master (active bus node)
Components representing a bus master determine the data traffic on the bus and are therefore also referred to as active bus nodes.
???Slaves (passive bus nodes)
These devices may only receive, acknowledge and return messages to the master if requested by the master.
Examples: SINAMICS drives, I/O modules
Note
If a SIMOTION D410 DP is operated as a passive PROFIBUS
Additional references
You will find additional information about PROFIBUS DP in the SIMOTION Communication System Manual.
Configuring SIMOTION D410
3.3Configuring the PROFIBUS DP interface (only D410 DP)
3.3.2Assignment of the PROFIBUS addresses in HW Config
Assigning PROFIBUS addresses
Assign a PROFIBUS address to all devices before you start networking these in order to enable intercommunication.
Note
All PROFIBUS addresses you assign must be unique on the PROFIBUS subnet.
Information pertaining to the rules of communication on the PROFIBUS subnet is available in the SIMOTION D410 Manual.
Define the PROFIBUS address separately for each device on your programming device / PC in HW Config. Certain PROFIBUS DP slaves are equipped with an address switch.
Note
The PROFIBUS addresses set at the devices using these switches must correspond with the address settings in HW Config.
Recommendation for PROFIBUS addresses
Reserve PROFIBUS address "0" for a service programming device and "1" for a service HMI device which are connected to the subnet as required.
Recommended PROFIBUS address setting for SIMOTION D410 in case of replacement or service:
Reserve address "2" for a SIMOTION D410. This prevents redundancy of the addresses after SIMOTION D410 is installed in the subnet with default settings (for example, when replacing a SIMOTION D410). Assign addresses higher than "2" to any additional devices on the subnet.
Configuring SIMOTION D410
3.3 Configuring the PROFIBUS DP interface (only D410 DP)
3.3.3Operating SIMOTION D410 on PROFIBUS DP.
PROFIBUS DP interface (X21)
SIMOTION D410 provides an interface for connecting to PROFIBUS DP. The interface supports transmission rates up to 12 Mbit/s.
The PROFIBUS DP interface can be operated as:
???DP slave, isochronous
???DP master, isochronous
???DP slave, not isochronous
???DP master, not isochronous
Both PROFIBUS DP interfaces are set by default for operation as master at address 2 at a transmission rate of 1.5 Mbit/s. The PROFIBUS DP network is automatically detected and generated for this setting.
However, you can select other settings. Such
HW Config and NetPro.
3.3.4Creating a new PROFIBUS DP subnet
The SIMOTION D410 device is networked using SIMOTION SCOUT. Set up your user- specific bus parameters for the PROFIBUS interface when you configure the network.
Note
The actions outlined below only need to be taken if you have not selected an interface when integrating SIMOTION D410 into the project (cf. chapter "Integrating SIMOTION D410 into a project").
Next, interconnect the programming device / PC using NetPro with the device, see the chapter "Configuring the programming device / PC interface".
1.
2.
3.Click "Properties" in the "General" tab to open the "PROFIBUS interface DP/MPI" dialog box.
4.Click "New" to open the "Properties - New PROFIBUS Subnet" dialog box.
5.Name the new subnet, and then enter its properties in the "Network settings" tab, for example, the transmission rate.
6.Click "OK" to accept the settings.
The new subnet is now displayed in the "Properties - PROFIBUS interface DP/MPI" dialog box and is ready for being interconnected with the PROFIBUS DP interface.
7.Save and compile the changes.
The PROFIBUS subnet you created is displayed as a graphic object in HW Config.
Configuring SIMOTION D410
3.3Configuring the PROFIBUS DP interface (only D410 DP)
3.3.5Setting the DP cycle and system cycle clocks
All system clocks for SIMOTION D410 DP are based on the DP cycle of SINAMICS Integrated, which must be set in HW Config.
Table
The PROFIBUS DP interface of the SIMOTION D410 DP supports operation at a DP cycle time ??? 1 ms, at a resolution of 0.125 ms. SINAMICS Integrated always runs in isochronous mode. The cyclic tasks of SIMOTION are therefore always in synchronism with SINAMICS Integrated.
The set DP cycle of SINAMICS Integrated is displayed as "Bus cycle" in the "System Clocks - D410..." dialog box in SIMOTION SCOUT. Select the SIMOTION D410 DP in the project tree, and then select the "Set system clocks" option in the "Target system" > "Expert" menu.
The table below shows the ratios you can set for the system clocks of SIMOTION D410 DP based on the DP cycle.
The minimum configurable length of the servo cycle is 1 ms. In conjunction with technology objects, a minimum servo cycle of 2 ms is recommended.
If you programmed the PROFIBUS DP interface for operation in isochronous master mode, you must synchronize its DP cycle with the DP cycle of SINAMICS Integrated in HW Config.
The timebase for the system clocks is generated internally if the DP interface is operated in isochronous or
The PROFIBUS DP interface can also be operated in isochronous slave mode. In this constellation system clocks are based on the clock signals received at the slave interface. A substitute clock of a duration equivalent to the configured clock is generated internally if the isochronous slave interface has not received a clock signal.
The clock settings are included in the project download to SIMOTION D410 DP and are adjusted according to specification.
At a PROFIBUS DP interface operated in isochronous slave mode you can also step down the clock ratio for synchronization with SINAMICS Integrated. This reduction of the clock ratio at the isochronous slave interface for synchronization with SINAMICS Integrated allows the operation of a DP cycle at the slave interface which is equivalent to an integer multiple SINAMICS Integrated. You set up this reduction by configuring the SINAMICS Integrated and DP interface cycles in HW Config. The rule is checked in HW Config.
Configuring SIMOTION D410
3.3 Configuring the PROFIBUS DP interface (only D410 DP)
3.3.6Rules for SIMOTION D410 DP
Rules for synchronizing the system clocks
You must conform to the following rules when setting the DP cycle and SINAMICS clocks:
1.The DP cycle must be an integer multiple of the current controller cycle. Error A01902 (2) is reported in the drive if this rule is violated.
2.The master application cycle (T mapc), which corresponds to the servo cycle, must be an integer multiple of the speed controller cycle. Error A01902 (7) is reported in the drive if this rule is violated. The
If the master application cycle = 1, this means that the DP cycle is also an integer multiple of the speed controller cycle.
3.The DP cycle must be an integer multiple of the basic cycles r0110[x]
Note
In addition to the rules mentioned, also observe the rules outlined below. These rules apply both to SIMOTION D410 DP and to SIMOTION D410 PN!
An overview of errors reported in SINAMICS Integrated is provided in the SINAMICS S Parameter Manual
Configuring SIMOTION D410 3.3 Configuring the PROFIBUS DP interface (only D410 DP)
Rules for SIMOTION D410 DP
The general rule for SIMOTION D410 specifies that the DP cycle (D410 DP) forms the basic clock of the cycle system. All cycles longer than this basic clock must be an integer multiple of the basic clock.
This rule also applies to SINAMICS cycles, if one of the successive cycles is longer than the basic clock:
???Speed controller p115[1]
???Flow controller p115[2]
???Setpoint channel p115[3]
???Position controller p115[4]
???Positioning p115[5]
???Technology controller (p0115[6])
???Onboard I/O p0799
???Terminal module I/O p4099
The corresponding cycle must be an integer multiple of the basic clock.
If any change to the DP cycle violates this rule you must also change the SINAMICS cycles. In order to change the cycles in the Expert list of SIMOTION SCOUT, select the "Control_Unit" from "SINAMICS_Integrated" in the Project Navigator, and then open the "Expert List" by selecting the "Expert" command from the shortcut menu.
Example: A default value of 4 ms is set at the SINAMICS setpoint channel. If setting a DP cycle of 3 ms you must set an integer multiple value as required at the setpoint channel, for example, 3 ms or 6 ms.
Configuring SIMOTION D410
3.4 Configuring PROFINET (only for D410 PN)
3.4Configuring PROFINET (only for D410 PN)
3.4.1General information about PROFINET communication
Overview
PROFINET is an open
The PROFINET interface supports operation of SIMOTION D410 PN as IO controller and/or as intelligent device.
PROFINET distinguishes between the controller and its assigned devices. Controller and devices form a PROFINET IO system, comparable to a
SIMOTION D410 PN supports the following PROFINET communication methods:
???RT
???IRT
With IRT, a distinction is made between IRT with high flexibility and IRT with high performance.
Additional references
Additional information pertaining to PROFINET communication is available in the SIMOTION Communication System Manual.
Configuring SIMOTION D410 3.4 Configuring PROFINET (only for D410 PN)
3.4.2Operating SIMOTION D410 PN on PROFINET
PROFINET interfaces (X200, X201)
SIMOTION D410 PN provides a
A port has two integrated LEDs, a green LED and an orange LED. The following LED states can occur:
Properties of PROFINET on SIMOTION D410 PN
SIMOTION D410 PN on PROFINET supports the following properties
???PROFINET specifies operation at 100 Mbit/s.
???The minimum send cycle is 0.5 ms, and the maximum is 4 ms.
???The setting accuracy for the send cycle is 125 ??s.
The use of cycle reduction is possible for the D410. Detailed information concerning cycle reduction is available in the SIMOTION SCOUT Communication System Manual.
Configuring SIMOTION D410
3.4 Configuring PROFINET (only for D410 PN)
Initializing SIMOTION D410
SIMOTION D410 must be assigned an IP address and a device name in order to enable downloading of the project. This is performed online on the SIMOTION device using the so- called "node initialization". To perform the node initialization, the programming device / PC must be connected with the SIMOTION D410 PN. SIMOTION SCOUT must be open.
1.Click the "Reachable nodes" button on the SIMOTION SCOUT toolbar. The newly opened "Reachable nodes" window shows the SIMOTION D410 device as "bus node" with the address 0.0.0.0 and a name.
2.Select the "Bus node" entry and open the "Edit Ethernet node..." function in the context menu. The "Edit Ethernet Node" dialog box opens.
3.Enter a name in the "Device name" field.
4.Click the "Assign name" button and confirm the displayed message with "OK."
5.Enter an appropriate IP address for the Ethernet subnet in the "IP address" field.
6.Enter an appropriate subnet mask for the Ethernet subnet in the "Subnet mask" field.
7.If required, enter the data for a network gateway.
8.Click "Assign IP Configuration". The entered data is assigned to the SIMOTION device.
9.Confirm the displayed message with "OK".
10.Click the "Close" button to close the "Edit Ethernet Node" window.
11.Click the "Update" button in the "Reachable Nodes" window. The SIMOTION D410 device is now displayed as "Geraet_01" with the type designation of the device and the assigned IP address.
12.Click the "Close" button to close the "Reachable Nodes" window.
Configuring SIMOTION D410 3.4 Configuring PROFINET (only for D410 PN)
Reading the IP address
To fetch the IP address, the SIMOTION SCOUT must be in online mode.
The IP address of SIMOTION D410 PN can be viewed in SIMOTION SCOUT as follows:
1.Establish an online connection to the SIMOTION D410.
2.
3.Select the "Target device > Device Diagnostics" command from the shortcut menu. The address is displayed as follows, for example:
Figure
Note
The MAC address is available on the rating plate on the front panel of the module.
Changing the IP address, device name, network gateway
Set the IP address, the subnet mask and, if necessary, the data for a gateway (router address) in order to enable communication over PROFINET with SIMOTION D410.
If you want to change the properties in the PROFINET subnet, you can change them using the "Reachable nodes" function in SIMOTION SCOUT or in the HW Config.
The "Reachable nodes" function with SIMOTION SCOUT is described in the "SIMOTION D410 initialization" section.
To configure and transfer the properties in HW Config, proceed as follows:
1.Open your project in SIMOTION SCOUT.
2.Open HW Config.
3.Click "Properties". The "Properties - Ethernet Interface" dialog box opens.
4.Click "New". The "New Subnet Industrial Ethernet" dialog box opens. Rename the new subnet, or accept the default name by clicking "OK".
5.Select the new Ethernet subnet which is now displayed in the "Properties - Ethernet Interface" dialog box.
Configuring SIMOTION D410
3.4Configuring PROFINET (only for D410 PN)
6.Define your addresses in the "IP address" and "Subnet mask" fields of the "Properties - Ethernet Interface" dialog box. Change to the "Network node" field and define whether you are going to use a router and, if yes, enter the router address. Confirm with "OK".
7.Close the "Properties" dialog by clicking "OK".
8.Save and compile the modified hardware configuration.
9.Download the new hardware configuration on PROFINET to your SIMOTION D410.
3.4.3Setting the send cycles and system clocks
Prerequisite
If, for the PROFINET interface, IRT (high performance) is not configured as the RT class, but no data is being transferred (no
Setting the DP cycle in HW Config
Set the DP cycle of SINAMICS Integrated in HW Config.
Table
SINAMICS Integrated always operates in isochronous mode. The cyclic tasks of SIMOTION are therefore always in synchronism with SINAMICS Integrated.
Configuring SIMOTION D410 3.4 Configuring PROFINET (only for D410 PN)
Setting the send cycle in HW Config
The PROFINET send cycle always forms the basis of the SIMOTION cycles if RT class IRT is set and data is in actual fact transferred. Set the send cycle in the "Domain Management" dialog box of HW Config. Open this dialog by selecting the "Edit" > "PROFINET IO" > "Domain Management ..." command in HW Config.
The set PROFINET send cycle is displayed in SIMOTION SCOUT as "Bus cycle" in the "System Clocks - D410..." dialog box. Select the SIMOTION D410 PN in the project tree, and then select the "Set system clocks" option in the "Target system" > "Expert" menu.
The PROFINET interface supports send cycle times within the range 0.5 ms < send cycle < 4 ms. The maximum configurable resolution is 0.125 ms.
The table below shows which ratios you can set for the system clocks of SIMOTION D410 PN based on the DP cycle of SINAMICS Integrated or on the PROFINET send cycle.
The minimum configurable length of the servo cycle is 1 ms. In conjunction with technology objects, a minimum servo cycle of 2 ms is recommended.
Configuring SIMOTION D410
3.4 Configuring PROFINET (only for D410 PN)
3.4.4Rules for SIMOTION D410 PN
Rules for using the PROFINET send cycle
If the PROFINET send cycle is the basis for the cycles, ensure that the DP cycle of the SINAMICS Integrated and the servo cycle are equal.
The timebase for the system clocks are generated internally if the PROFINET interface is not operated with RT class IRT with high performance or IRT with high performance is set, but no data is being transferred. This also applies if the PROFINET interface is operated as synchronization master with RT class IRT with high performance and data is being transferred. The SIMOTION device does not have to synchronize itself with an external cycle.
The basis for system clocks is derived from the clock signals received at the PROFINET interface if this interface is operated as synchronization slave with RT class IRT with high performance. The SIMOTION device does not have to synchronize itself with this external clock.
A substitute clock of a duration equivalent to the configured clock is generated internally if the PROFINET interface has not received a clock signal.
The clock settings are included in the project download to the SIMOTION device and are adjusted according to specification.
Configuring SIMOTION D410 3.4 Configuring PROFINET (only for D410 PN)
Rules for SIMOTION D410 PN
The general rule for SIMOTION D410 specifies that the send cycle (D410 PN) forms the basic clock of the cycle system. All cycles longer than this basic clock must be an integer multiple of the basic clock.
This rule also applies to SINAMICS cycles, if one of the successive cycles is longer than the basic clock:
???Speed controller p115[1]
???Flow controller p115[2]
???Setpoint channel p115[3]
???Position controller p115[4]
???Positioning p115[5]
???Technology controller (p0115[6])
???Onboard I/O p0799
???Terminal module I/O p4099
The corresponding cycle must be an integer multiple of the basic clock.
If any change to the send cycle violates this rule you must also change the SINAMICS cycles. In order to change the cycles in the Expert list of SIMOTION SCOUT, select the "Control_Unit" from "SINAMICS_Integrated" in the Project Navigator, and then open the "Expert List" by selecting the "Expert" command from the shortcut menu.
Example: A default value of 4 ms is set at the SINAMICS setpoint channel. If setting a DP cycle of 3 ms you must set an integer multiple value as required at the setpoint channel, for example, 3 ms or 6 ms.
Note
An overview of errors reported in SINAMICS Integrated is provided in the SINAMICS S Parameter Manual
4.1Overview of commissioning
Prerequisites
Prerequisites for commissioning the SIMOTION D410:
???The system has been connected and wired.
???The SIMOTION D410 is switched on and started up (STOP state).
???SIMOTION SCOUT (with integrated STARTER) has been installed and started on the programming device / PC.
???Communication between the SIMOTION D410 and the programming device / PC is configured.
???You have created a project and installed a SIMOTION D410 in the project.
NOTICE
For the SIMOTION D410, a reset of the drive must not be set using the expert list of the control unit in the p972 parameter (drive unit reset). This causes SIMOTION D410 malfunction, the RDY, RUN/STOP and SF/BF LEDs glow red. In this fault situation, the SIMOTION D410 must be switched off and on again.
Commissioning steps
This chapter describes the steps in configuring the plant and testing the configured stand- alone drive and axis. The steps in commissioning are listed below in the order as recommended:
1.Configuring SINAMICS Integrated
The integrated drive SINAMICS Integrated can be configured in offline or online mode:
???Offline configuration
All components and their order number must be known for the offline configuration.
???Online configuration
The configuration in online mode allows you to upload all information of the connected
Commissioning (software)
4.2Configuring the system in offline mode
2.Creating an axis
3.Using the digital I/O
4.Optionally, use TMx, DMC20 or other encoders
5.Testing the configured drive
6.Testing the configured axis
Observe the corresponding references.
4.2Configuring the system in offline mode
4.2.1Overview
Prerequisites for offline configuration
???All components and their order number must be known for the offline configuration.
???You created a project in SIMOTION SCOUT and added a SIMOTION D410 to the project.
???You configured the communication between the programming device / PC and SIMOTION D410.
Procedure
Steps involved in offline configuring:
???Calling the Drive Wizard
???Configuring the components
???Aligning the HW Config
???Downloading the project to SIMOTION D410
Note
You can configure all available terminal modules such as TM15 in the course of the offline configuration, for example.
Commissioning (software) 4.2 Configuring the system in offline mode
4.2.2Accessing the drive wizard
Integrated drive
SIMOTION D410 features an integrated SINAMICS S120 drive (control unit) which is automatically included when you insert the SIMOTION D410 in the Project Navigator. The integrated drive must be operated in equidistant, isochronous mode using PROFIdrive- compliant message frame types.
The integrated drive and its associated modules (SINAMICS S120 motor modules, for example) are configured using the Drive Wizard of the integrated STARTER in SIMOTION
SCOUT.
Note
Observe all necessary safety information and wiring rules in the corresponding current SINAMICS S120 documentation.
Procedure
Select the "SINAMICS_Integrated" > "Configure drive unit" drive element in the Project Navigator to open the Drive Wizard.
You can configure the following components:
???Power unit (e.g. SINAMICS S120 PM340 power module)
???Motor
???Encoder
Commissioning (software)
4.2 Configuring the system in offline mode
4.2.3Configuring the components
Procedure
1.Enter a drive name in the "Drive Properties" dialog box and select the drive type (servo or vector).
Figure
2.You can select the function modules and the control mode in the
Figure
Commissioning (software) 4.2 Configuring the system in offline mode
3.Select your motor module by order number from the list shown in the "Power Unit" dialog box.
Figure
4.Select in the "Power unit supplementary data" dialog the component added to the power unit.
The selection of the component depends on the construction type.
???D410 DP with D410 PN: The SIMOTION D410 snapped directly onto the PM340 power module
???CUA31 or CUA32: The CUA3x snapped directly onto the PM340. The D410 is mounted individually on a mounting plate. The D410 is connected with the CUA3x using a
Commissioning (software)
4.2 Configuring the system in offline mode
Figure
5. Select the motor and possibly the motor type in the next dialog box.
Figure
6. Select a motor holding brake (if installed).
Commissioning (software) 4.2 Configuring the system in offline mode
Figure
7.Select the encoder order number in the "Encoder selection by motor order number" if using a motor that is not equipped with a
Figure
8.In the following dialog, select the PROFIBUS message frame.
The following message frames can be used, for example, in conjunction with SINAMICS S120 drives:
???SIEMENS message frame 105,
Commissioning (software)
4.2Configuring the system in offline mode
???SIEMENS message frame 106,
Advantages of DSC (compared to a position controller in the control unit):
???Higher Kv (position controller gain) possible
???Larger bandwidth and consequently higher dynamic response
???Shorter response times for disturbance characteristic
The DSC dynamic drive control can be used for the SIEMENS message frame 105, PSD- 10/10 and SIEMENS message frame 106,
Detailed information for the various message frame types is contained in the Motion Control, Electrical/Hydraulic Axis Technology Object, External Encoder function manual.
Figure
A "Summary" dialog box opens with a listing of all settings after you completed all settings in the Drive Wizard. You can now choose to activate your settings by clicking "Finish", or to return to the component configuration for further editing.
Commissioning (software) 4.2 Configuring the system in offline mode
Figure
The configured drive is displayed in the Project Navigator. An overview of your configured SINAMICS components is available in the "SINAMICS_Integrated" > "Topology" dialog.
Commissioning (software)
4.2 Configuring the system in offline mode
4.2.4Aligning HW Config
After having completed the configuration of all SINAMICS components, align the data with
HW Config.
Proceed as follows:
1.Open the "Configuration" entry in the "SINAMICS_Integrated" tree in the Project Navigator. The "SINAMICS_Integrated - Configuration" dialog box opens with a list of configured drive objects.
The question marks in the I/O address fields indicate that you have not yet defined the I/O addresses of the drive objects.
Figure
Note
Drive objects without address must be positioned at the end of the list, for otherwise it is not possible to align HW Config ("Align with HW Config"). To move the order of a drive object without address, select the associated drive object and move it downwards using the arrow key.
2.Click "Align with HW Config" in order to assign addresses to the configured components. The addresses are written to HW Config.
Commissioning (software) 4.2 Configuring the system in offline mode
Figure
Note
Repeat the HW Config alignment if the message frames for SINAMICS Integrated were changed. The addresses are not updated automatically.
4.2.5Downloading the project to SIMOTION D410
Procedure for downloading a project into the target system
1.Save and compile the project.
2.Go online to SIMOTION D410.
3.Select the "Download project to target system" command to download the project to SIMOTION D410. The connection to SINAMICS Integrated is activated automatically.
The drive has been assigned parameters and commissioned. You can now test the drive using the drive control panel.
Note
Online access to SINAMICS Integrated is not possible if HW Config is not loaded at the time you initially connect to the target system.
Download the data to HW Config in order to enable online access to SINAMICS Integrated.
Commissioning (software)
4.2 Configuring the system in offline mode
Procedure for downloading a created project to the CF card
You can use a card reader to also write the entire project to the CF Card in offline mode. In the SIMOTION SCOUT, you can call the "Download to the file system" function in the context menu of the SIMOTION device.
1.Save and compile the project.
2.Switch off the SIMOTION D410.
3.Remove the CF card and insert it in a card adapter. The card adapter must be connected with a programming device / PC.
4.Select in the SCOUT project the SIMOTION D410 device that you want to download to the CF card.
5.Click "Download to the file system" in the context menu. A dialog box opens.
6.Click the "Select target" button in the "Download to the file system" dialog box.
7.Select the target drive.
8.Confirm your entries with "OK". The data will be written to the CF card.
9.Remove the CF card and insert it in the D410 slot.
10.Switch on the D410. The D410 starts with the downloaded project.
Note
The initial startup from the CompactFlash Card you configured in offline mode takes longer.
The firmware of the SINAMICS component is updated automatically if any higher firmware version is found on the CF card. Observe any messages and alarms in the details window of the SIMOTION SCOUT after a firmware update. After having updated the firmware of a SINAMICS component, go offline and then switch off the power supply of the upgraded component (Power Off/On).
Commissioning (software) 4.3 Configuring the system in online mode
4.3Configuring the system in online mode
4.3.1Overview
Introduction
You can configure the plant in online mode after having completed its wiring. You can upload the data of SINAMICS components connected via
Note
Components without
Prerequisites for online configuration
???You created a project in SIMOTION SCOUT and added a SIMOTION D410 to the project.
???You configured the communication between the the programming device / PC and SIMOTION D410.
Procedure
Steps involved in offline configuring:
???Establishing the online connection
???Starting automatic configuration
???Configuring SINAMICS components
???Aligning HW Config
???Downloading the project to SIMOTION D410
Commissioning (software)
4.3 Configuring the system in online mode
4.3.2Establishing the online connection
The procedure for an initial commissioning follows.
To perform an online configuration, you must establish an online connection to the SIMOTION D410. In this case, no connection can yet be established to SINAMICS Integrated. An appropriate message is output. Once the hardware configuration has been loaded into the target device, an online connection to the SINAMICS Integrated is established automatically. Proceed as follows:
1.Save and compile the project.
2.Establish an online connection.
3.Select the SIMOTION D410 device in the Project Navigator.
Note
Ensure that you use the "Download to the target device" function rather than "Download to the target system". An automatic commissioning is no longer possible after "Download to the target system". If "Download to the target system" has been used, "Restore factory settings" must be performed on the drive element in order to start an automatic commissioning afterwards.
4.Use the "Download to the target device" function to download the SIMOTION D410 device into the target device. The connection to SINAMICS Integrated is activated automatically.
You can now run the automatic configuration at SINAMICS Integrated. For details, see Section Starting automatic configuration (Page 75).
Additional references
Further information about establishing an online connection to the programming device / PC is contained in the following documentation:
???SIMOTION SCOUT Configuration Manual
???SIMOTION SCOUT Online Help
???In FAQ on the "Utilities & Applications" CD
Commissioning (software) 4.3 Configuring the system in online mode
4.3.3Starting automatic configuration
Prerequisites
???You activated the online connection to SINAMICS Integrated.
???You have not yet configured any drive objects.
???The default settings of SINAMICS Integrated were activated.
Procedure
1.Open the "Automatic Configuration" dialog box by selecting the "SINAMICS_Integrated > Automatic configuration" command in the Project Navigator.
Figure
2.Click "Start automatic configuration".
The "Drive Object Type" dialog box opens.
Figure
Commissioning (software)
4.3Configuring the system in online mode
3.Select either a servo or a vector drive object.
4.Click "Close" to complete automatic configuration.
The configuration data is uploaded (Upload to PG) automatically as soon as automatic commissioning is completed.
Note
If the firmware of the SINAMICS components differs from the firmware on the CF card, the firmware of the SINAMICS components will be upgraded automatically.
5.Click "Close" to exit automatic configuration.
Figure
6.Perform the "Copy RAM to ROM ..." function on the D410 and on SINAMICS Integrated. This saves the project on the CF card and does not need to be reloaded after a switch-
Note
After having updated the firmware of a SINAMICS component, go offline and then switch off the power supply of the upgraded component (Power Off/On).
Result
The
Commissioning (software) 4.3 Configuring the system in online mode
Figure
You must then define the axis message frame and possibly edit the SINAMICS components (e.g. components without
See also
Editing SINAMICS components (Page 77)
4.3.4Editing SINAMICS components
Prerequisites
???You have uploaded all connected
???You shut down the connection to the target system (offline mode).
Commissioning (software)
4.3 Configuring the system in online mode
Procedure
Now go ahead and adapt your components to suit the application.
Run the wizards for all
This procedure corresponds with the description in chapter "Configuring the system in offline mode".
Note
If only the message frame type needs to be selected for the edit, you can also set this in the "Configuration" screen form of the drive element. A HW Config match is then required.
Configuring the system in offline mode (Page 62)
4.3.5Aligning HW Config
See also
Aligning HW Config (Page 70)
4.3.6Download the project to SIMOTION D410
After having aligned HW Config, download the configuration to SINAMICS Integrated.
1.Save and compile the project.
2.Go online to SIMOTION D410.
3.Select the "Download project to target system" command to download the project to SIMOTION D410. The connection to SINAMICS Integrated is activated automatically.
Drive programming and commissioning is completed. You can now test the drive using the drive control panel.
Commissioning (software)
4.4 Creating an axis
4.4Creating an axis
Overview
The SIMOTION SCOUT Engineering System can be used to insert axes in your project.
1.Start a session of the Axis Wizard in order to configure the axes and interconnect these with the SINAMICS Integrated drive.
2.Insert your user programs into the project.
3.Compile the project and download it to SIMOTION D410.
Note
Note that only one real axis can be used on a SIMOTION D410.
Creating an axis using the Axis Wizard
Axes are integrated as technology objects (TOs) in SIMOTION. Create the axis with corresponding settings under the SIMOTION D410 and then interconnect it with SINAMICS Integrated.
How to insert an axis:
1.
Figure
2.Name the axis TO in the "Insert Axis" dialog box, select the technology and save and confirm your entries with "OK".
3.Continue the Axis Configuration Wizard and enter your system settings until the "Drive Assignment" dialog box opens.
4.Click "Align SINAMICS devices..." to open the "Device Alignment" dialog box.
Commissioning (software)
4.4Creating an axis
5.Select the drive to be aligned (SINAMICS Integrated) in this dialog box and then click "Align".
The addresses are assigned to the configured components and entered in HW Config.
Note
This device alignment is only necessary if not already done in the course of drive commissioning. This shows that no interconnectable drive of the SINAMICS Integrated type is displayed.
Figure
6.Select a drive unit in the "Drive Assignment" dialog box. Normally only a SINAMICS Integrated drive will be offered. Exception: A D410 has been configured, for example, with a hydraulic axis. You have already defined the message frame type in the previous steps and so only need to accept it. To do this, click the "Accept data from the drive" button to transfer the SINAMICS Integrated values in the axis wizards.
7.Select the encoder from the "Encoder Assignment" dialog box and then adapt its properties. Click the "Accept data from the drive" button to transfer the SINAMICS Integrated values in the axis wizards.
Note
For motors with
8.Complete the Axis Wizard session.
The configured axis is displayed in the Project Navigator. After having downloaded it to the target system, you can test the axis using the axis or drive control panel.
Commissioning (software) 4.5 Integrating additional encoders (optional)
4.5Integrating additional encoders (optional)
4.5.1General information
SIMOTION D410 provides the option of integrating and configuring further encoders in addition to the motor encoder.
The following encoders are supported for operation with SIMOTION D410:
???Encoders with
???Encoders connected to SIMOTION D410 using the onboard encoder interface (X23)
???Encoders connected to SIMOTION D410 using an SMx module
???Encoders connected using PROFIBUS or PROFINET
Prerequisite
SIMOTION D410 features a
Configuring two encoders
The second encoder can be used at SIMOTION D410, for example, as:
???Machine encoder (second encoder)
???External encoder.
The external encoder can be used, for example, to measure an actual position value directly on a geared motor. If operating with a second encoder as machine encoder you can work with encoder changeover.
Configuring tasks
Encoders connected using PROFIBUS or PROFINET are configured only for SIMOTION.
Encoders connected using SMx,
Configure this additional encoder on drive side (SINAMICS Integrated) and in SIMOTION:
1.Configure the encoder interface on the drive side (second encoder)
2.Configuring a second encoder for a TO axis in SIMOTION
3.Configuring an external encoder in SIMOTION
These steps in configuring are described in the next section.
Commissioning (software)
4.5 Integrating additional encoders (optional)
4.5.2Configure the encoder interface on the drive side
Prerequisite
You configured the drive with an encoder in the Drive Wizard.
Procedure
1.Open the "Configuration" entry of your drive by selecting the "SINAMICS_Integrated" > Drives" command in the Project Navigator. The "Configuration" dialog box opens.
2.Click "Configure DDS..." to open the Drive Wizard.
3.Step the Drive Wizard forward until the "SINAMICS_Integrated - Encoders" dialog box opens.
4.Select the "Encoder 2" option in this dialog. The dialog box displays a list of available encoders.
5.Select for "encoder evaluation":
???SMx for the encoder connection using
???D410 DP (or D410 PN) for the encoder connection using the onboard encoder interface
Figure
6. Select the connected encoder and confirm with "Continue".
Commissioning (software) 4.5 Integrating additional encoders (optional)
7.In the "Configuration - SINAMICS Integrated - PROFIBUS (drive) Process Data Exchange" dialog box, select a message frame that supports the transmission of two encoder values (e.g. SIEMENS message frame 106,
8.Click "Continue" to complete the Drive Wizard.
9.Click "Transfer to HW Config" in the "SINAMICS_Integrated - Configuration" dialog box in order to align HW Config.
The drive is configured for operation with two encoders.
4.5.3Configuring a second encoder for a TO axis in SIMOTION
Requirements
???You have configured a drive with two encoders as specified in Section Configure the encoder interface on the drive side (Page 82).
???The set message frame supports the transmission of two encoder values.
???The configuration of the PROFIBUS message frames has been matched with HW Config.
Procedure
1.In the Project Navigator, open the Axis Wizard of the axis.
2.In the "Drive Assignment" dialog box, select the same message that you have already used to configure the second encoder on the SINAMICS Integrated or in the "SINAMICS Integrated > Configuration" screen form (e.g. SIEMENS message frame 106, PSD- 11/15).
3.Complete the Axis Wizard session.
You have configured a second encoder for an axis TO in SIMOTION. The set message frame type now allows you to use the value of a second encoder.
Commissioning (software)
4.5 Integrating additional encoders (optional)
4.5.4Configuring external encoders in SIMOTION
Prerequisite
Encoder using PROFIBUS/PROFINET
You have used HW Config to configure an encoder on the PROFIBUS or PROFINET. Two different possibilities are available for the encoder connection:
???Encoder interconnection using a PROFIdrive message frame (encoder with message frame type 81)
???Encoder interface as a direct value in the I/O area
Detailed information is contained in the "SIMOTION TO Axis, Electric/Hydraulic, External Encoder" Function Manual
Encoder on the drive
You configured a drive with two encoders, and then an electric axis with the PROFIBUS message frame to be used.
Procedure
1.Open the wizard for configuring an external encoder by selecting the "External Encoders" > "Insert external encoder" folder in the Project Navigator.
2.Assign a name in the "Inserting an external encoder" screen form and, if required, enter the author and version.
3.Execute the wizard for the encoder configuration and enter the appropriate values in the screen forms.
The external encoder is now configured and uses the second value which is transferred by means of the selected PROFIBUS message frame.
Additional references
Detailed information for the external encoder is contained in the SIMOTION SCOUT TO Axis, Electric/Hydraulic, External Encoder Function Manual.
Commissioning (software) 4.6 Using
4.6Using
4.6.1Onboard I/Os and terminal modules configuration overview
Using SINAMICS I/Os by SIMOTION
Digital inputs/outputs (I/Os) assigned to SINAMICS can be used completely or partially by SIMOTION. Examples here are the use of terminal modules (TMs) or onboard I/Os of the D410. To allow the I/Os to be used by SIMOTION, the input and output data must be transferred using message frames. This message frame configuration is used to represent the I/Os in the logical address space of SIMOTION and so can be used by a SIMOTION application. The BICO interconnections on the drive specify which I/Os are represented on the message frame.
These BICO interconnections can be:
???Freely defined (free message frame configuration; message frame extension).
???Permanently defined (standard message frames, e.g. message frame 39x; axis message frames). . .)
???Configuration dependent (TM15/TM17 High Feature).
The access to the message frame for SIMOTION D410 is made using I/O variables or input/output addresses. Depending how the I/Os are to be used, various configuration possibilities are appropriate:
Commissioning (software)
4.6 Using
Note
The module hardware for TM15 and TM15 DI/DO is identical. The differentiation is made only with the addition of the component in the Project Navigator of the SIMOTION SCOUT using "Inserting input/output component".
Further information about the TM15 and TM17 High Feature is contained in the TM15 and TM17 High Feature Commissioning Manual.
Note
The "free message frame configuration using BICO" and the "message frame extension" allow you to use inputs/outputs
For message frame 39x, however, all onboard terminals are interconnected automatically to message frame 39x using BICO interconnections and so available only for SIMOTION. The following is true:
???All onboard I/Os configured as digital output for the drive are only available for SIMOTION, i.e. they can no longer be used by SINAMICS.
???Digital inputs can be used by SIMOTION and SINAMICS.
Commissioning (software) 4.6 Using
4.6.2Use of message frame 39x
The following section describes the configuration of the onboard I/Os of a SIMOTION D410. The configuration of the onboard I/Os of a CU310 connected to a SIMOTION controller is performed similarly. With the exception of the
Functionality of the 390, 391 and 392 message frames
The onboard I/Os of the D410 assigned to SINAMICS can be used by SIMOTION with the 39x message frames. This functionality is available as of SIMOTION V4.1, SP1. If a message frame 39x is set, however, all the onboard I/Os are interconnected automatically to this message frame 39x using BICO interconnections and so available for SIMOTION. All onboard I/Os of a control unit parameterized as digital output, e.g. D410s are available only for SIMOTION. Digital inputs can be used by both SIMOTION and SINAMICS.
In addition to the use of the onboard I/Os, the 39x message frame permits the use of:
???
???"Global" measuring inputs
???The control and status word of the control unit (CU_STW, CU_ZSW)
Depending on the selected 39x message frame, various functionalities can be used with
SIMOTION D.
Because the same terminals are used, the maximum
The configuration of local measuring inputs does not require the configuration of message frame 39x.
Message frame 39x configuration
The following requirements must be satisfied:
???A SCOUT project has been created
???The D410 has been created
???A SINAMICS Integrated drive has been configured
Commissioning (software)
4.6 Using
Proceed as follows:
1.In the Project Navigator,
2.Select the message frame type (SIEMENS message frame 390, 391 or 392) for the control unit.
3.Click the "Transfer to HW Config" button to transfer the message frame data to hardware configuration.
A message frame 39x is configured for the D410 control unit. The address area of the message frame is displayed in "SINAMICS_Integrated ??? Configuration" dialog. The 39x message frame configuration automatically makes the BICO interconnections for the DI and DI/DO which are then available for SIMOTION.
Figure
Commissioning (software) 4.6 Using
Use of the onboard I/O by SIMOTION
For DI/DO channels, the terminal status of the output can be fetched back using the input (DI).
The 390 message frame transfers in PSD1 the control and status word of the control unit and in PSD2 the status of the onboard inputs/outputs.
For the 391 and 392 message frames, additional control and status information for the global measuring inputs is transferred. The content of these PSD3 to PSD15 is used exclusively by the measuring input technology object.
To allow access by the I/Os to the individual PSDs, I/O variables must be created in SIMOTION. For this purpose, the input/output addresses displayed in the "PROFIBUS message frame" tab in the "SINAMICS Integrated - Configuration" dialog box are required.
The following figure shows an example of I/Os created in SCOUT: In this example, the start address of the 390 message frame for the input and output data is each 276.
Figure
Commissioning (software)
4.6 Using
Configuring DI/DO as input or output
When a DI/DO is to be used as digital input or digital output, interconnection screen forms can be used for configuring.
Proceed as follows:
1.
2.Click the "Bidirectional digital inputs/outputs" tab.
3.In this tab, configure the required inputs or outputs.
Figure
The configuration can also be set
Note
When the 39x message frames are used, a HW Config must always be performed after changes have been made to onboard
Commissioning (software) 4.6 Using
4.6.3Free message frame configuring with P915/P916 (only TM15/TM17 High Feature)
The TM15 and TM17 High Feature terminal modules are connected to the control unit using the
The structure and the length of the message frame depends on the configured properties of the inputs and outputs. The I/O channels can be parameterized as digital input, digital output, input for measuring input or output for output cam.
The automatic interconnection of the message frame means the functionality of the modules can only be used by SIMOTION and is controlled from the SIMOTION user program using input/output addresses or I/O variables. A
Additional references
Additional information about this topic is available in the following documents:
???To configure TM15 and TM17 High Feature, refer to the TM15 and TM17 High Feature Commissioning Manual.
???To configure output cams and measuring inputs, refer to the SIMOTION Motion Control Output Cams and Measuring Inputs Function Manual.
???For the I/O processing with TM15 and TM17 High Feature (timing, classification in the task system), refer to the SIMOTION SCOUT Basic Functions Function Manual.
Commissioning (software)
4.6 Using
4.6.4Configuring free message frames by means of BICO
Overview
For the "free message frame configuring using BICO", dedicated message frames for the data transmission are assigned to the associated drive objects (e.g. terminal modules). Message frame type: Free message frame configuring using BICO (only slaves)
To allow SIMOTION to access the SINAMICS drive signals, e.g. I/Os, they must be interconnected to the SINAMICS using BICO to the message frame. The "free message frame configuring using" is a preferred solution when I/Os are to be divided
Free message frame configuring using the TM31 as example
The example describes the interconnection of a signal to the TM31 connected to a
SIMOTION D410.
Steps in configuring
???Configure a
???Interconnect the message frame for TM31
???Create I/O variables in SIMOTION SCOUT
Prerequisite
You have already created a project and configured a drive.
Commissioning (software) 4.6 Using
Configuring
1.
2.Enter a name for the module to be inserted and confirm your entry with OK.
3.
"Free message frame configuration with BICO" (message frame 999) is set for the inserted TM31. Insert the number of PSDs (Process Status Data) for I/O data. Observe the maximum possible number of PSDs for the various drive objects (see previous table). An TM31, for example, supports five PSDs in both the send and the receive direction.
4.Enter the value 5 in the "Length" column in the "Input data" or "Output data" fields.
Figure
5.Click "Transfer to HW Config" in order to transfer the data to HW Config and to read the address space of the I/O data.
Commissioning (software)
4.6 Using
Note
Before the matching, all drive objects without input/output addresses
The icons in the status column show the following information:
The message frame is configured differently in HW Config. You must match with HW Config.
You use a predefined standard message frame or free BICO interconnection.
You use a changed standard message frame that you have extended with additional data.
You use a message frame for which one of the two message frame lengths is too long. The drive object cannot process this entry.
Figure
You can now transfer data from TM31 to SIMOTION (PROFIBUS send direction) or receive data from there (PROFIBUS receive direction).
Commissioning (software) 4.6 Using
Interconnecting the message frame for TM31
The next section describes how you can transfer signals from TM31 to SIMOTION (PROFIBUS send direction).
Note
To perform interconnections in online mode, you must:
???Prior to the interconnection, download the message frame configuration into the target device. Function: Download the CPU / drive device to the target unit.
???After the interconnection, download the settings from the target device into the programming device / PC. Function: Download the CPU / drive unit to the programming device.
1.
2.Click "Binector/connector converter" in the "PROFIBUS send direction" tab. The "Binector/connector converter" tab opens
3.Select the source for status word 1 by clicking the "Source status word 1" field and then select the corresponding PSD, in this example, TM31
Figure
4.Click the button leading the "Source status word 1" field. The PSD bits are now displayed.
5.Click in a field and select the default signal, for example, bit 0.
This bit can be used, for example, to transmit the status at digital input DI 0 to
SIMOTION.
Commissioning (software)
4.6 Using
Figure
6. Interconnect all signals you need.
How to transfer a signal from SIMOTION to TM31 (PROFIBUS receive direction):
1.
2.Click "Binector/connector converter" in the "PROFIBUS receive direction" tab. The "Connector/binector converter" tab opens
3.Interconnect all required signals. Proceed as defined in the description of the "PROFIBUS send direction".
Creating an I/O variable in SIMOTION
Create the I/O variables in SIMOTION SCOUT in order to access the signals of TM31. You require the input or output addresses for the TM31 message frame in the "PROFIBUS Message Frame" dialog box. This allows you to assign the variable either as a complete word, a byte or a single bit.
1.In the Project Navigator,
2.Enter a name for the I/O variable.
3.Enter an I/O address, e.g.
PI277.0 - This accesses PSD1, bit 0 of the configured message frame. PI276.0 - This accesses PSD1, bit 8 of the configured message frame. SIMOTION can now access the signal.
The PROFIdrive profile specifies that the process status data (PSD) is defined as a
Commissioning (software) 4.6 Using
4.6.5Expanding a message frame
The message frame extension extends existing standard message frames (e.g. axis message frames) with additional process status data (PSD). These additional PSDs are then interconnected using BICO (e.g. to an actual speed value or to the status of a digital input).
A message frame extension is then the preferred variant when I/Os are to be distributed between SIMOTION and SINAMICS and, for example, an axis view is preferred (drive- related I/O should be appended to each axis message frame).
Proceed as follows:
1.Insert a drive using the Drive Wizard and select PROFIBUS (drive), e.g. "standard message frame 103", for process data exchange.
2.
The tab contains the default length of I/O data for the drive you inserted. As the addresses of I/O data have not yet been transferred to HW Config the default entry "???" is set.
3.Select the row of the object of which you want to expand the message frame.
Figure
4.Click "Add line" and select the "Message frame expansion" option in the menu shown.
A new line which contains the message frame expansion is inserted below the current line.
5.Enter the "length" for the number of PSDs by which the message frame is to be extended in the Input data and Output data columns.
Commissioning (software)
4.6 Using
Note
Before the matching, all drive objects without input/output addresses
The icons in the status column show the following information:
The message frame is configured differently in HW Config. You must match with HW Config.
You use a predefined standard message frame or free BICO interconnection.
You use a changed standard message frame that you have extended with additional data.
You use a message frame for which one of the two message frame lengths is too long. The drive object cannot process this entry.
6.Click "Transfer to HW Config" in order to transfer the changes to HW Config.
The red check mark at the line indicates that a modified standard protocol is being used. The I/O address data is entered after its transfer to HW Config.
7.Change to the configured drive and
8.Deactivate the "Hide inactive interconnections" option to display all PSDs of the message frame.
The send and receive data (at least 16 entries) will be displayed. The first PSDs are assigned the standard message frame by default and cannot be changed.
9.Interconnect the PSDs (at the end of the PSD list) that you have added with the required signals by means of BICO.
Commissioning (software) 4.6 Using
Figure
Note
A warning message is not output if you interconnect more PSDs than were set in the additional PSDs. Note that a SERVO drive object supports a maximum of 16 PSD setpoints and 19 PSD actual values. Each VECTOR drive object supports a maximum of 32 PSD setpoints.
Commissioning (software)
4.6 Using
4.6.6Using
Using
Output cams are defined as being the
The integrated digital outputs of the SIMOTION D can be used as cam output or as high- speed output with write access to the user program. In order to be able to use the high- speed outputs, one of the 39x message frames must be created.
Note
If I/O data is transferred using bus message frames, the update of the I/O data is subject to the set bus cycle. This means an I/O using a 39x message frame can change its status just once in each bus cycle of the PROFIBUS Integrated.
For SIMOTION D onboard outputs, the outputs are controlled using direct write accesses to the hardware (i.e. bypassing the message frame). This means:
???Write accesses to digital outputs act with a particularly short delay time because the write access is independent of the bus cycle.
???A more accurate output of the cam output is possible
For fast write accesses from the user program, the resulting delay time has the following form:
???User program delay time
???
H
If you use the output as
For additional information, see the SIMOTION Motion Control Output Cams and Measuring Outputs Function Manual.
If you use the output as
For information about message frame configuring, see Use of message frame 39x (Page 87).
4.6.7Using probe inputs on D410
Configuration of probe inputs
Measuring inputs are used for fast, accurate measurement of actual positions. This is achieved with hardware support (for example, the measuring input on the assigned drive unit). Digital inputs for standard peripherals, e.g. distributed SIMATIC ET 200 peripheral system, cannot generally be used as probe inputs.
For SIMOTION, the TO probe input technology object controls the probe input functionality. SIMOTION differentiates between two classes of the probe inputs; these classes have different properties that are configured differently.
Local and global measuring inputs
Depending on the used hardware platform, the following local and global measuring inputs are available for the measuring tasks:
???Local measuring inputs are
???Global measuring inputs can be freely assigned to the axes and add an internal timestamp to the measurement result for more precise determination of the axis positions.
Commissioning (software)
4.6 Using
A maximum of three probe inputs can be configured onboard on the D410.
Commissioning (software) 4.6 Using
Configuring of local measuring inputs on the D410
Local measuring inputs are always permanently assigned to an axis (drive). They are configured separately for each drive. The drive and the probe input must always be located on the same control unit. The measuring results are transferred using the axis message frame in accordance with the PROFIdrive profile. Message frame 39x does not need to be configured for local measuring inputs.
The settings for the use of the local measuring inputs must be made in the expert list.
Because a maximum of three encoders can be assigned to a drive, the index [1..2] specifies whether the measurement applies to 1, 2 or 3.
The following must be taken into account:
???Only two Measuring Input TOs can be configured per Axis TO or External Encoder TO.
???Only one Measuring Input TO can be active on an Axis TO or External Encoder TO.
Table
Detailed information is contained in the SIMOTION Motion Control Output Cams and Measuring Outputs Function Manual.
Commissioning (software)
4.6 Using
Configuring of global measuring inputs on the D410
Global measuring inputs can be freely assigned to the axes (drives) and add an internal timestamp to the measurement result for more precise determination of the axis positions. The drive and the probe input do not need to be located on the same control unit. The measuring results are not transferred using the axis message frame, but using the 391/392 axis message frame.
In addition to the settings of the parameters, message frame 391 (max. two measuring inputs) or message frame 392 (max. three measuring inputs) must be set for the control unit. The p680 parameter is used to define a terminal as global probe inputs. Message frame 391 can be used to assign the p680[0..1] parameter; message frame 392 can be used to assign the p680[0..2] parameter. The parameter used to set the required terminal is not relevant. The assignment of the measuring input to an axis is made using the logical hardware address and the bit number of the digital input to be used as measuring input (see also Section Use of message frame 39x (Page 87)).
The p490 parameter of the control unit can be used to invert a measuring input.
Note
The p684, and r685 to r688 parameters of the control unit have no relevance for SIMOTION.
Note
When the 39x message frames are used, a HW Config must always be performed after changes have been made to onboard
Commissioning (software) 4.6 Using
Table
Detailed information is contained in the SIMOTION Motion Control Output Cams and Measuring Outputs Function Manual.
4.6.8Outputs of cam outputs and probe inputs on TM15/TM17 High Feature
Quantity framework for TM15/TM17 High Feature
The TM15/TM17 High Feature Terminal Modules can be used to extend the number of outputs for cam outputs and probe inputs that can be installed.
???TM15, maximum 24 outputs for cam outputs / probe inputs
???TM17 High Feature, maximum 16 outputs for cam outputs / probe inputs
Additional references
Detailed information for the configuration is contained in the following documents
???SIMOTION Output Cams and Measuring Inputs Function Manual
???TM15/TM17 High Feature Terminal Modules Commissioning Manual
Commissioning (software)
4.7 Creating and programming TM41
4.7Creating and programming TM41
4.7.1Overview
The TM41 terminal module can be used to expand the number of digital I/O and of analog inputs within a drive system. TM41 also returns TTL signals which emulate an incremental encoder, for example, for a master control system.
The emulated encoder signal has the signal characteristic of an incremental TTL encoder (A track, B track, R track). The resolution of the encoder signal can be specified in the configuration.
Configuring the TM41 involves the following steps:
???Configuring TM41 at SINAMICS Integrated
???Configuring TM41 using the Axis Wizard.
Note
The digital I/Os can be interconnected similar to those of TM31.
The TM41 encoder interface (incremental encoder representation) can
???Be interconnected with an encoder signal of the control unit using parameterization, e.g. sin/cos incremental encoder. For detailed information, consult the SINAMICS manuals.
???From the SIMOTION viewpoint, can be accessed as axis. This allows you to return the axis position (a master value) as encoder signal to a second controller, for example. Detailed information is contained in the SIMOTION D4x5 Commissioning and Hardware Installation Manual.
The second application case can only be used with SIMOTION D410 with restrictions, because the TM41 is configured as a real axis. Because SIMOTION D410 supports just one real axis, no additional real axis can be configured.
4.7.2Configuring TM41 at SINAMICS Integrated
TM41 can be configured after you completed the configuration of SINAMICS Integrated. Proceed as follows:
1.
2.Select TM41 from the "Control type" field of the "Insert input/output component" dialog box and assign a unique name to the module.
3.Confirm your entry with "OK".
The TM41 is inserted in the Project Navigator by the name you entered.
Commissioning (software)
4.8 Creating a DMC20
4.8Creating a DMC20
4.8.1DMC20 hub properties
The DMC20
???Direct measuring systems
???Terminal modules
???Reduction of the network hierarchy levels A star topology has the following advantages:
???The components can operate as end node of your segment.
???Line communication is not affected.
Application examples
Encoder expansion and
???An encoder expansion involves integration of direct measuring systems. These are installed in the control cabinet directly at the machine. Several encoders can be connected to the same hub.
Note: SIMOTION D410 has just one
???Hot plugging is the option for changing motor components while in operation. These components are connected to a star topology using a
Additional references
Information pertaining to the DMC20
Commissioning (software)
4.8 Creating a DMC20
4.8.2Creating a
The hub is not wired when you insert the DMC20 and is represented in the topology tree in the component storage. The hub has to be wired manually. Proceed as follows:
1.
2.Select the "Insert new object" >
3.
The hub is saved to the component storage of the topology tree.
4.
The components connected to the hub are displayed in the topology tree.
The hub you inserted is displayed as icon at the "Topology" entry in the Project Navigator. All components connected to a hub are also displayed in the course of automatic configuration.
Commissioning (software)
4.9Testing the configured drive using the drive control panel
4.9Testing the configured drive using the drive control panel
You can test a configured drive using the drive control panel where you can define a speed value by setting a scaling factor. The drive control panel should only be used for commissioning.
Prerequisites
???The project has been downloaded to the target system.
???SIMOTION SCOUT is in online mode.
???The drive is not in use by a current project in RUN mode.
WARNING
Make sure that the drive test does not pose any risk to persons.
Testing the drive using the drive control panel
1.Change to the configured drive in the Project Navigator and open the drive control panel by selecting "Commissioning" > "Control panel". The drive control panel opens in the detail view.
Figure
2.In order to view the control range and axis diagnostics data, click "Show/hide control" and Show/hide axis diagnostics".
3.Click "Assume control priority". The "Assume Control Priority" dialog box opens.
Commissioning (software)
4.9 Testing the configured drive using the drive control panel
Figure
4.Read the notes and confirm these with "Accept".
5.Activate the "Enables" checkbox to enable the drive. All enables are now set with the exception of ON/OFF1.
6.Enter your setpoint in the input field and shift the scaling to 0% as safety setting.
Figure
7.Click the "Drive On" button. The "Enable is set" LED lights up in green color. The drive starts moving as you move the slider towards the right side. The current motor speed is displayed in "Actual".
8.Click "Drive Off" to stop the drive after you completed the test.
9.Deactivate the enable signal and click "Give up control priority" to deactivate controlling at the programming device / PC.
Commissioning (software)
4.10Testing the configured axis using the axis control panel
4.10Testing the configured axis using the axis control panel
Axis control panel
The axis control panel is used exclusively for testing axes.
You can use the axis control panel for the following tasks, for example:
???Testing all system components before the axis movement is controlled by a program
???Testing as to whether you can move the axis using the axis control panel if a fault is detected
???Moving the axes for tuning purposes (controller tuning)
???Executing active homing
???Setting and resetting the axis enable signal
???Testing a connected axis
Prerequisites
Prerequisites for testing:
???The project has been downloaded to the target system.
???SIMOTION SCOUT is in online mode.
Axis test
1.Open the "AXES" folder in the Project Navigator and click the "Control panel" entry below the axis (for example, Axis_1).
The axis control panel is displayed.
Figure
2.In order to view the control range and axis diagnostics data, click "Show/hide control" and "Show/hide axis diagnostics".
Commissioning (software)
4.10Testing the configured axis using the axis control panel
3.Click "Assume control priority".
Confirm the next message with "Yes" in order to set the controller to STOPU state.
Note
You must assume control priority in order to move the axis using the programming device / PC. You can always stop the axis by pressing the SPACEBAR.
4.The "Assume Control Priority" dialog box opens.
Figure
5.Read the notes and confirm these with "Accept".
6.To enable the axis, click "Set/reset enables". Confirm the "Set Axis Enable" dialog box with "OK".
7.Enable jog mode by clicking
8.Enter a velocity.
9.Click "OK" to confirm the displayed "Set Axis Enable" window.
10.Click the "Jog" button. The axis moves as long as you keep the left mouse button pressed. You can monitor the traversing motion at the velocity and position entries.
11.Click "Set/reset enables" to remove the enable. Confirm the "Reset Axis Enable" dialog box with "OK".
12.Click "Give up control priority" to deactivate axis control at the programming device / PC. You can no longer control the axis at the programming device / PC if this state is set.
Commissioning (software) 4.11 Downloading and saving user data
4.11Downloading and saving user data
Overview
It is advisable to backup all user data (programs, configuration data, parameters) to the CompactFlash Card after having completed commissioning of SIMOTION D410.
Downloading user data
Use the "Target system > Download > Download to the target system" command to transfer the following data from the SIMOTION SCOUT Engineering System (ES) to the
???Configuration data
???Programs
???Parameterization
???Technology packages
The hardware configuration of SIMOTION D410 and the retain variables are also saved to the "nonvolatile data" area.
Note
Using the menu:
???"Target system > Download > Download to the target system" downloads the complete project data to the target system.
???"Target system > Download > To the target system" downloads only the data of the selected device / drive element to the target system.
All contents of the "volatile data" area are lost after you shut down SIMOTION D410!
Additional references
For more information about the SIMOTION SCOUT Engineering System, consult the SIMOTION SCOUT Configuration Manual.
Commissioning (software) 4.12 Deleting data
Saving user data
The "Copy RAM to ROM" function is used in SIMOTION SCOUT to save the following data from RAM to the CompactFlash card:
???The technology data / user data from the "volatile data" area
???Baud rate, PROFIBUS DP addresses, IP address, subnet mask and router address, including the retain variables with their initial values from the
Note
The "Copy RAM to ROM" command cannot be used to save the actual value of retain variables to the CompactFlash Card.
Execute the "Copy RAM to ROM" function separately for SINAMICS Integrated. This requires that the drive element has been selected in the Project Navigator.
See also
Properties of the user memories (Page 36)
4.12Deleting data
4.12.1Overview of data deletion
You can define the scope of data to be deleted from SIMOTION D410 memory described in the "user memory concept". That is, you can choose to delete all data or only specific parts.
You have the following options of deleting data from SIMOTION D410:
???Resetting the memory of SIMOTION D410
???Deleting user data from the CompactFlash Card
???Restoring the default settings of SINAMICS Integrated
???Restoring the default settings of SIMOTION D410
Commissioning (software)
4.12 Deleting data
4.12.2Resetting the memory of SIMOTION D410
Introduction
A memory reset deletes all data from RAM on the SIMOTION D410 and
Reset the memory on SIMOTION D410 if
???You want to undo changes made to user data (programs, configuration data, parameter assignments) which you have not backed up by means of the "Copy RAM to ROM" command.
???The RUN/STOP LED is flashing (slow flashing) to indicate that SIMOTION D410 is requesting a memory reset.
???
You can reset memory either in offline mode using the DIL switch of SIMOTION D410, or in online mode using SIMOTION SCOUT.
Data deleted by memory reset
The following data is deleted during a memory reset:
???User data (units, configuration data, parameters, task configuration)
???Technology packages
???Retain TO (absolute encoder adjustment)
???Retain variables
Retain variables in the interface or implementation section of a UNIT are declared with
VAR_GLOBAL RETAIN
Note
As a memory reset deletes all absolute encoder data the encoder must be
Commissioning (software) 4.12 Deleting data
Data retained during memory reset
The following data is retained during memory reset:
???TCP/IP and DP parameters
???Diagnostics buffer
???Data that was saved with the _savePersistentMemoryData, _saveUnitDataSet, _exportUnitDataSet and RAMtoROM commands and with the "Copy RAM to ROM" function.
The data contents of a backup file generated by executing _savePersistentMemoryData (PMEMORY.XML/PMEMORY.BAK) is written back to
???Licenses
The technology packages and user data (configuration data, programs, parameter assignments) you previously backed up to a CompactFlash Card by means of the "Copy RAM to ROM" command are transferred to the
Memory reset by means of SIMOTION SCOUT
You can only reset memory using SIMOTION SCOUT if SIMOTION D410 is operating in online mode.
1.Select SIMOTION D410 from the Project Navigator of SIMOTION SCOUT.
2.Select the "Target device > Control system mode" command from the shortcut menu in order to open the "D410: System Mode" dialog box.
3.Select the STOP mode.
4.Next, select the MRES mode to reset the memory.
Memory reset using the mode selector switch
The mode selector switch function is implemented in SIMOTION D410 by means of a DIL switch (DIL =
Information pertaining to to the switch positions and corresponding modes of operation is available in the SIMOTION D410 Manual.
You can only reset memory using the mode selector switch if SIMOTION D410 is operating in offline mode.
Commissioning (software)
4.12 Deleting data
How to reset the memory:
1. Set the MRES mode on the DIL switch (see the picture below).
6FKDOWHUVWHOOXQJ 21
6FKDOWHUVWHOOXQJ 2))
Figure
The STOP LED begins to flash.
2.Set DIL switch 1 to ON (STOP mode) after the STOP LED is lit in yellow color.
3.Return the DIL switch to MRES mode within three seconds. The memory is now being reset.
4.Wait for SIMOTION D410 to complete its restart. Set DIL switch 1, 2 and 3 to ON (RUN mode).
The STOP LED lights after SIMOTION D410 has completed its memory reset.
Note
Memory reset is cancelled if you do not return the DIL switch to MRES as specified within three seconds. Repeat the procedure in this case.
4.12.3Deleting user data from the CompactFlash Card
Overview
You can delete the user data using SIMOTION SCOUT. SIMOTION D410 must be operating in online mode. This deletes the following data:
???User data from the "volatile data" area
???
???User data on the CompactFlash Card (user folders), including the SINAMICS configuration data
You can still go online to SIMOTION D410 at your programming device / PC. All licenses on the CompactFlash Card are retained.
Commissioning (software) 4.12 Deleting data
Deleting user data
1.Open the project you want to edit in SIMOTION SCOUT.
2.Go online to SIMOTION D410.
3.Select SIMOTION D410 in the Project Navigator, and then select the "Delete user data on card" option from the "Target system" menu.
4.Confirm the "Delete user data from card" message with "OK".
The user data are deleted. SINAMICS Integrated goes into offline mode.
4.12.4Restoring the default settings of SINAMICS Integrated
Prerequisite
You must be online to SINAMICS Integrated in order to restore its default settings.
Restoring the default settings
1.
2.Select the "Target device > Restore default settings" command from the shortcut menu. This restores the delivery state of SINAMICS Integrated.
4.12.5Restoring the default settings of SIMOTION D410
Overview
SIMOTION D410 is supplied with default parameters such as the transmission rate or PROFIBUS addresses. You can restore the default settings using the DIL switch. This deletes the following data:
???
???The backup copy of
???User data in the "volatile data" area and on the CompactFlash Card
???The communication configuration (IP and DP parameters)
All licenses on the CompactFlash Card are retained.
Commissioning (software)
4.13 System shutdown
Restoring the default settings using the DIL switch
1.The power supply is shut down.
2.Set the MRES mode on the DIL switch of SIMOTION D410 (see the picture below).
6FKDOWHUVWHOOXQJ 21
6FKDOWHUVWHOOXQJ 2))
Figure
3.Restart the power supply.
The buffered SRAM and user data are deleted. The default settings are loaded. SIMOTION D140 remains in STOP mode.
4.Change to the required mode by setting the DIL switch.
Note
The default communications parameters are now restored. You must
4.13System shutdown
All axes and system components must be in safe state before you shut down the system. You can set up this safe state by providing a separate motion task, for example.
You can shut down the power supply after the system has reached a standstill state.
Note
You must observe the safety notices for SINAMICS components, which you can find in the corresponding SINAMICS manuals.
5.1Replacing modules
5.1.1Removing and replacing the SIMOTION D410
Overview
You must replace the entire SIMOTION D410 module.
WARNING
Always shut down the load power supply before you replace the SIMOTION D410 module. You shut down power using the On/Off switch of the PS power supply module, for example.
Note that power modules with FSB performance rating or higher still carry a residual intermediate voltage after shutdown. Wait 10 minutes before you remove any screws.
You can replace a SIMOTION D410 DP with a SIMOTION D410 PN module and vice versa. Replace the device in HW Config
Replacing a SIMOTION D410 DP with a SIMOTION D410 PN module and vice versa
Note
The following procedure describes how you replace a SIMOTION D410 DP with a SIMOTION D410 PN of the same firmware version (and vice versa). The procedure for performing a software and firmware upgrade is described in Section Performing a software and firmware update (Page 126).
Proceed as follows:
1.
2.In the hardware catalog, open the appropriate folder structure: e.g. Drive Based\SIMOTION D410\6AU1
Maintenance and service 5.1 Replacing modules
Note
DO NOT delete the module in Slot 2 when replacing it!
Figure
3.
The module is replaced.
4.Save and compile the hardware configuration in order to activate the changes.
5.Close HW Config.
The configuration data for your SIMOTION device is immediately activated in the SIMOTION SCOUT project and the entire project saved. This includes activation of all changes made to the project, for example, to the axis configuration.
6.Select "SINAMICS Integrated" in the Project Navigator.
7.Open the context menu and click "Target device > Device version". A window opens in which you can change the appropriate version.
8.Select the version of the replaced D410.
Maintenance and service 5.1 Replacing modules
9.Click the "Change version" button and confirm the displayed message. The version of SINAMICS Integrated is changed.
10.Shut down the power supply.
11.Replace the module as described in "Replacing defective modules". 12.Restart the power supply.
Replacing defective modules
How to remove the SIMOTION D410 module:
1.Shut down the power supply.
2.Remove the CompactFlash Card from the card slot.
3.Remove the connections for the power supply.
4.Disconnect the
5.Disconnect the digital I/O connectors at interface X121.
6.Disconnect the plug of any encoder connected to the X23 encoder interface.
7.Remove the SIMOTION D410 module from the power module or from the mounting panel, depending on the type of assembly (see the "Installation" chapter in the
SIMOTION D410 Manual).
How to install the new SIMOTION D410 module:
Note
Observe the information in the SIMOTION D410 Manual, when installing, wiring and connecting the SIMOTION D410 module.
1.Mount the new SIMOTION D410 onto the power module, or onto the mounting panel (see the "Installation" chapter in the SIMOTION D410 Manual).
2.Connect all previously removed connectors.
3.Terminate the load voltage supply cables at the terminal block.
4.Rewire the shielding of all cables.
5.Insert the original CompactFlash Card into the card slot of the new SIMOTION D410.
6.Restart the power supply. The new SIMOTION D410 is immediately ready for operation.
Maintenance and service 5.1 Replacing modules
5.1.2Replacing
Replacing components
Automatic upgrading/downgrading
As of SINAMICS firmware version 2.5, the
An upgrade/downgrade operation in progress is indicated on the components by a 0.5 Hz
A successfully completed firmware upgrade/downgrade is indicated on the components by flashing at a frequency of 2 Hz and on the SIMOTION D410 by the yellow flashing of the RDY LED at 2 Hz. After the upgrade/downgrade is completed, the power must be cycled off and back on (POWER OFF/ON). The upgrade/downgrade function can be deactivated using the p7826 parameter in the expert list.
Additional references
Additional information is available in the SINAMICS S120 Commissioning Manual.
Maintenance and service 5.2 Replacing the fan
5.2Replacing the fan
Prerequisite
Replace the fan if a fault message is output by the temperature monitoring function as a result of fan failure. The fan must be replaced if the fan is defective or the maximum operating hours counter is attained.
The fan can be ordered as spare part, see "Spare parts and accessories" in the
SIMOTION D410 Manual.
CAUTION
The fan of the SIMOTION D410 module may only be replaced by qualified technical personnel and strictly in accordance with ESD guidelines!
Replacing the fan
How to replace the fan:
1.Unlock all
2.Remove the plastic enclosure.
3.You can now remove and replace the fan from the front without any additional tools.
4.Set the parameter of the p251 operating hours counter to "0". The parameter can only be changed in online mode.
Note
The parameter of the operating hours counter can only be set to "0". Any other values will be rejected. Restoring factory settings does not affect this parameter.
Maintenance and service
5.3 Performing a software and firmware update
5.3Performing a software and firmware update
Upgrading SIMOTION D410
The actions described in this section also apply to downgrading to an older version.
Various possibilities are available to perform a software and firmware update for SIMOTION D410:
???Upgrade the supplied upgrade data using the CF card adapter
???Upgrade using
???Upgrade using the SCOUT "Start update devices tool" function
The first method is described in the following section. The two other methods are described in the SIMOTION SCOUT Configuration Manual, in the Upgrading SIMOTION Devices Function Manual and in the online help.
Note
A firmware update using
Upgrade the supplied upgrade data using the CF card adapter
Prerequisite
The current firmware for the SIMOTION devices is contained on the SIMOTION SCOUT CDs (e.g. the d4xx.zip file for the SIMOTION D4xx firmware is located in the \3_D4xx\Firmware\... directory). Upgrading the SIMOTION D410 automatically updates the firmware of all connected SINAMICS components.
Note
Observe the readme files and upgrade instructions included in the delivery of new SIMOTION versions.
Use only CF cards released for SIMOTION D410 and which have an appropriate correct boot loader version.
You can obtain the compatibility relationships from the "software products" compatibility list on the SIMOTION SCOUT
NOTICE
The upgrade operation deletes all project data and parameters from the CompactFlash Card!
Maintenance and service 5.3 Performing a software and firmware update
Note
Retain data can be backed up with SIMOTION SCOUT; see SIMOTION SCOUT Configuration Manual or Online Help. See also Section User memory concept (Page 35).
Procedure
The following procedure describes how to perform the upgrade:
1.Switch off the power supply to the D410.
2.Remove the CompactFlash Card from SIMOTION D410 and insert it into the CompactFlash Card adaptor of your PC.
3.Open Windows Explorer. The CompactFlash Card must be visible as removable data volume Windows Explorer under an arbitrary drive letter.
4.If generating a backup copy of your data on the CompactFlash card (_saveunitdataset) using your own application: Save the "...\USER\SIMOTION\USER_DIR\UPP\UNITDS" folder to the CompactFlash Card using the Card Reader tool and Windows Explorer on the PC / programming device.
5.Delete all the data from the CompactFlash Card.
6.Unpack the file delivered to you on the CompactFlash Card. Always maintain the file structure when setting up the unpacking tool.
7.Copy the folder saved in step 4 back to the appropriate folder structure on the CF card.
8.Remove the CompactFlash Card from the CompactFlash Card adaptor of your programming device / PC.
9.Insert the CF card into the D410.
10.Switch on power to the D410. The new firmware is loaded from the CompactFlash Card to the SIMOTION D410 module.
Note
The license key is stored in the "KEYS" directory on the CF card. For the initial startup of the SIMOTION device, as of Kernel Version V4.1, the license key is saved in the boot sector of the CF card. The license key in the boot sector cannot be deleted by an operation action. The license key remains saved even by formatting the CF card or rewriting the boot loader.
If the license key is no longer present on the card, for example, as the result of deleting the "KEYS" directory, it will be written again during the startup of the SIMOTION device from the boot sector into the "KEYS" directory. The license key can be changed at any time, for example, by relicensing. At the next startup, the license key will be saved again in the boot sector.
Maintenance and service
5.3 Performing a software and firmware update
Updating the firmware of the SINAMICS components
How to update the firmware:
1.Select the SINAMICS component in the Project Navigator, for example, SINAMICS Integrated.
2.
The "SINAMICS Integrated - Configuration" dialog box opens and displays a list of all available drive objects.
3.Click "Version Overview" to open the list of connected SINAMICS components.
4.Establish the online connection and select the devices whose firmware you wish to update.
The list displays the current firmware version of the devices.
5.Click "Firmware update" to download the new firmware to the devices. Select all components whose firmware is to be updated.
6.Switch the power supply to the updated components off and on after you have performed the firmware update. The device is now ready for operation.
Note
For a firmware update, the SINAMICS components must be installed appropriately. The firmware cannot be updated if the components are not programmed.
You can also update the firmware by means of the Expert list. Refer to the SINAMICS S120 Commissioning Manual for a description of this procedure.
Upgrading a project
In order to allow the further use of existing projects you must take the following steps when upgrading the software:
1.Replace the module in HW Config
2.Upgrade the technology packages
3.Upgrade the libraries
Replace the module in HW Config
See Removing and replacing the SIMOTION D410 (Page 121)
Maintenance and service 5.3 Performing a software and firmware update
Upgrading technology packages
When modules are replaced or project data is imported, the versions of the technology packages (TP) assigned to the individual technology objects (TO) are not automatically upgraded to a version valid for the SIMOTION device. This upgrade requires a separate step.
To adapt the technology package version of the new SIMOTION device:
1.Select the desired SIMOTION device in the Project Navigator.
2.Choose "Select Technology Packages" from the context menu.
Note
If the last step you performed was to replace the SIMOTION device, the "Technology Packages from Another Version" dialog box appears. Confirm this with "OK" to delete the existing links to the technology packages, thus enabling new technology packages to be assigned. The "Select Technology Packages" dialog box will now appear.
The "Select Technology Packages" window opens.
1.Activate the checkbox for the technology packages.
The technology packages must have the same version as the kernel. Consequently, in SIMOTION SCOUT, the same version as the kernel is automatically assigned to each technology package.
2.If technology objects for your project indicating an incorrect version appear under "Incorrect version", click "Update". The "Update Technology Packages" dialog box opens. Otherwise, continue with step 8.
3.Confirm with "OK". A message appears.
4.Confirm the message with "OK".
5.If the update is successful, a message appears. Confirm with "OK".
6.Confirm the "Select Technology Packages" dialog window with "OK". The TP upgrade is complete.
Maintenance and service
5.3 Performing a software and firmware update
Upgrading the library
An upgrade of the libraries you are using is required if the version of the SIMOTION device or TOs in your existing project has changed.
1.Open the LIBRARY directory in the Project Navigator.
2.Select a library,
3.Select the "TPs/TOs" tab in the "Properties" window.
4.Select the SIMOTION device and the technology packages for which the library is to be valid.
5.Close the dialog box with "OK".
Note
Please also observe the notes on
Download the project to the target system
1.Click "Connect with target system" to go online to the target system.
2.Execute the "Download to target system" command, and then select "Copy RAM to ROM" to download the updated offline project to the target device.
3.For the automatic subsequent configuring in the SINAMICS Integrated drive, you must now perform "Download to programming device".
4.Save the project.
Maintenance and service 5.4 SIMOTION CompactFlash Card
5.4SIMOTION CompactFlash Card
5.4.1Replacing the CompactFlash Card
Prerequisite
Note
Always power down the unit before you insert or remove the CompactFlash Card!
The RDY LED on the SIMOTION D410 flashes in green color as long as any application is accessing the CompactFlash Card (see the chapter "Fault and status displays").
Procedure
How to replace the CompactFlash Card:
1.Shut down the power supply.
2.Remove the CompactFlash Card from the card slot of SIMOTION D410.
3.Hold the card between your thumb and finger on the gripping cavity and then pull it out.
4.Insert the new CompactFlash Card into the card slot. Push it in all the way with slight pressure until it engages. The insertion direction of the CompactFlash Card is identified by an arrow on the card and a matching arrow on the slot.
The properly inserted card does not protrude from the SIMOTION D410 housing.
5.Restart the power supply.
5.4.2Writing and deleting data on CompactFlash Cards
Overview
You have the following options of writing data to a CompactFlash Card:
???Saving technology and user data to the CompactFlash Card
The programming device / PC must be online to SIMOTION D410 in order to execute this function.
???Saving data from the programming device / PC to the CompactFlash Card. This function requires a CompactFlash Card adapter.
Note
CompactFlash Card are always shipped in formatted state.
Maintenance and service
5.4 SIMOTION CompactFlash Card
Saving technology and user data to the CompactFlash Card
The CompactFlash Card can be used as storage volume for technology and user data (programs, configuration data and parameters) from the "volatile data" area. Proceed as follows:
1.Go online to SIMOTION D410 on your programming device / PC (see the chapter "Creating a project").
2.Select the "Copy RAM to ROM" command in SIMOTION SCOUT to write the data to your CompactFlash Card.
Writing data to a CompactFlash Card on your programming programming device / PC
A CompactFlash Card adapter must be installed on the programming device / PC and can be used to write data to the CompactFlash Card. Always save your project data to CompactFlash Card using the programming device / PC before you update the SIMOTION firmware, for example.
Note
Do not use any of the onboard tools in Windows to modify or delete files which were written to the CompactFlash Card using the "Copy RAM to ROM" function in SIMOTION SCOUT. Such actions may irrevocably destroy your project.
5.4.3Formatting the CompactFlash Card
You can format a faulty CompactFlash Card, for example. Proceed as follows:
1.Insert the CompactFlash Card into a CompactFlash Card adapter which is connected to your programming device / PC.
2.Format the CompactFlash Card in Windows (FAT file system). The CompactFlash Card is formatted.
Maintenance and service 5.4 SIMOTION CompactFlash Card
5.4.4Bootloader on the CompactFlash card
Writing a bootloader
A bootloader may need to be written in the following situations:
???When a new bootloader is required for the used SIMOTION D410 firmware version.
???When a new bootloader is required for the used SIMOTION D410 hardware version.
???When the bootloader is defective.
The bootloader version can be fetched using the SIMOTION SCOUT device diagnosis. If this is not possible because of the following reason, this can be caused by an incorrect bootloader version. In this case, replace the bootloader version with the current version.
???The SIMOTION D410 does not startup, the RDY LED flashes red at 0.5 Hz and the RUN/STOP LED lights red or all LEDs remain off.
Use the "Options > Write boot sector..." function to write the bootloader version in the SIMOTION SCOUT to the CF card.
Detailed information for the CF card, bootloader version, SIMOTION D410 hardware and SIMOTION firmware version compatibility relationships is contained in the software compatibility list. This list is available both in the supplied documentation of the SIMOTION SCOUT CD at \1_Important\German\Kompatibilit??t\ . . . and also in the Internet at "http://support.automation.siemens.com/WW/view/de/18857317"
6.1Diagnostics by means of LED displays
Overview
The status LEDs display the operating modes or fault states of SIMOTION D410.
Legend of the LED states
Diagnostics data
6.1 Diagnostics by means of LED displays
LED displays
The following table provides an overview of all relevant LED display combinations. Each LED can be lit in yellow, red, or green color. The color which corresponds with the LED signal state is also defined.
Diagnostics data 6.1 Diagnostics by means of LED displays
1) Priority of the displays: The displays always visualize the state which is assigned the numerically lowest priority level. The error of the next highest priority class is displayed after the cause of the previous signal state was eliminated.
The LED "OUT > 5V" display is controlled only by the encoder evaluation for the integrated X23 encoder interface in SINAMICS Integrated. The table below lists the display states and their meaning.
Diagnostics data
6.2 Extended diagnostic capabilities
6.2Extended diagnostic capabilities
SIMOTION Task Profiler application
The SIMOTION Task Profiler is a dedicated application installed parallel to SIMOTION SCOUT during the SIMOTION SCOUT setup. The Task Profiler can be called in online mode from the device diagnosis in SIMOTION SCOUT or the Windows application. In cases of malfunction or errors, the Task Trace data can be written in a directory or on the CF card. This data can then be processed using the Task Trace Viewer.
For further information, see the SIMOTION Task Trace Function Manual.
Diagnostic functions with the DIP switch
The following diagnostic functions are possible using the specified switch settings on the DIP switch of the D410:
???Downgrading a SIMOTION device - switch 6
You can use this function to undo a SIMOTION devices update.
Place switch 6 of the DIP switch on the D410 to ON (0000010), and switch the D410 off and on.
The "Start devices update tool" function is described in the Upgrading SIMOTION Devices Function Manual.
???Writing diagnostic data to the CF card - switch 7
This diagnostic data can provide important information after a D410 malfunction (crash). If this function has been performed, diagnostic data is written to the CF card. This data can then be sent in a suitable form, e.g. compressed as *.zip file, to the Technical Support for evaluation.
Proceed as follows:
1.To do this, set the DIP switch 7 to ON.
2.Shutdown the D410.
3.Switch on the D410. The data will be written to the CF card. Wait until the D410 has completed its start.
4.Shutdown the D410 and remove the CF card.
5.A DIAG folder is created in the \USER\SIMOTION\HMI\SYSLOG directory. This folder contains the diagnostic data.
6.Transfer the diagnostic data for processing to the Technical Support.
Standards and approvals
A.1 General rules
IEC 1131
A
The SIMOTION programmable controller meets the requirements and criteria of the
Standard IEC 1131, Section 2.
CE marking
Our products meet the general and
89/336/EEC "Electromagnetic Compatibility" (EMC guideline) The EC declaration of conformity is contained in this manual.
EMC Directive
SIMOTION products are designed for industrial use.
UL certification
Recognized component mark for United States and the Canada Underwriters Laboratories (UL) according to Standard UL 508, File 16 4110.
Declaration of conformity
The current Declaration of Conformity is on the Internet at
http://support.automation.siemens.com/WW/view/de/15257461
Standards and approvals
A.2 Safety of electronic controllers
A.2 Safety of electronic controllers
Introduction
The following remarks relate to fundamental criteria and apply irrespective of the type of controller and the manufacturer.
Reliability
Comprehensive and
These include
???The selection of
???
???Systematic and computerized inspection of all supplied components
???Burning in of all LSI circuits (e.g. processors, memories, etc.)
???Measures to prevent static discharge when handling MOS circuits
???Visual checks during various stages of manufacture
???Continuous heat testing at higher ambient temperatures for several days
???Computerized final inspection
???Statistical analysis of all returned goods so that corrective measures can be initiated immediately
???Monitoring of the primary controller components using online tests
These measures are considered to be basic measures for safety engineering. They avoid or control the majority of faults that may occur.
Risk
A higher degree of safety standard applies to all applications and situations where there is a risk of material damage or injury to persons if there is a failure. Special regulations specific to the system apply to such applications. These must be taken into account for configuration of the controller (e.g. VDE 0116 for furnaces).
For electronic controllers with safety responsibility, the measures required for preventing or controlling faults depend on the hazard inherent in the plant. In this respect, the basic measures listed above are no longer adequate once the hazard exceeds a certain potential. Additional measures (e.g. double redundancy, tests, checksums, etc.) for the controller must implemented and certified (DIN VDE 0801).
Standards and approvals
A.2 Safety of electronic controllers
Division into
Nearly all systems contain parts that perform
Important note
Even if an extremely high level of conceptual safety has been achieved in the design of an electronic controller - e.g. through implementation of a
DANGER
Electrical, magnetic and electromagnetic fields (EMF) that occur during operation can pose a danger to persons who are present in the direct vicinity of the product - especially persons with pacemakers, implants, or similar devices.
The relevant directives and standards must be observed by the machine/plant operators and persons present in the vicinity of the product. These are, for example, EMF Directive 2004/40/EEC and standards EN
These state that a hazard analysis must be drawn up for every workplace, from which measures for reducing dangers and their impact on persons are derived and applied, and exposure and danger zones are defined and observed.
The safety information in the Storage, Transport, Installation, Commissioning, Operation, Maintenance, Disassembly and Disposal sections must also be taken into account.
Standards and approvals
A.3 Electromagnetic Compatibility
A.3 Electromagnetic Compatibility
Definition
Electromagnetic compatibility (EMC) is the ability of an electrical device to function sufficiently in its electromagnetic environment without interfering with this environment.
The SIMOTION D410 control meets the requirements of the EU directive on EMC and the EMC law of the European single market 89/339/EEC.
Relevant standards regarding electromagnetic compatibility
The following EMC standards are met if the EMC installation guideline (order number
ESD guidelines
B.1 ESD definition
What does ESD mean?
B
All electronic modules are equipped with highly integrated modules or components. Because of the technology used, these electronic components are very sensitive to overvoltages and thus to discharge of static electricity.
The acronym ESD has become the established designation for such Electrostatic Sensitive Devices. The ESD designation is used internationally to refer to electrostatic sensitive devices.
Electrostatic sensitive devices are identified by the following symbol:
Figure
CAUTION
Electrostatic sensitive devices can be irreparably damaged by voltages that are far lower than anything a person can perceive. These voltages occur if you touch a component or the electrical connection of a module without having previously discharged any static from your body. Any damage that occurs to a module as a result of overvoltage is generally not recognized immediately and only comes to light after the equipment has been operating for some time.
B.2 Electrostatic charging of individuals
Any person who is not conductively connected to the electrical potential of the environment can accumulate an electrostatic charge.
ESD guidelines
B.3 Basic measures for protection against discharge of static electricity
This figure indicates the maximum electrostatic charges that can accumulate on an operator when he comes into contact with the indicated materials. These values comply with the specifications in IEC
Figure
B.3 Basic measures for protection against discharge of static electricity
Ensure sufficient grounding
When working with electrostatic sensitive devices, make sure that the you, your workstation, and the packaging are properly grounded. This prevents the accumulation of static electricity.
Avoid direct contact
You should only touch ESD components if unavoidable (for example, during maintenance work). When you touch modules, make sure that you do not touch either the pins on the modules or the printed conductors. If you follow these instructions, electrostatic discharge cannot reach or damage sensitive components.
If you have to take measurements on a module, make sure that you first discharge any static that may have accumulated in your body. To do this, touch a grounded metal object. Only use grounded measuring instruments.
Appendix
C.1 List of abbreviations
C
Appendix
C.1 List of abbreviations
Index
A
Abbreviations, 146
Applications, 11
Automatic D410 downgrading, 124
Automatic D410 upgrading, 124
Axis
Creating with Axis Wizard, 79
Testing, 111
B
Boot sector
License key, 127
Bootloader, 133
Reading, 133
Writing, 133
C
CE
Type plate, 27 Commissioning steps, 61 Compact Flash Card
Inserting, 32 CompactFlash card, 27
Licenses, 27 Type plate, 27 View, 27
CompactFlash Card, 38
Formatting, 132
Replacing, 131 Saving user data, 132 Writing, 131
Writing data using the programming device / PC, 132
Configuration
Global measuring inputs on D410, 101 Local measuring inputs on D410, 101 Measuring inputs on D410, 101
Configuring
D410
Commissioning Manual, 08/2008 Edition
DI/DOs on D410, 90
Configuring encoders, 81
Configuring the internal encoder, 82
D
D410
Automatic downgrading, 124 Automatic upgrading, 124 Diagnostic functions, 138 Downgrading, 126
I/Os, 85
LED status on the PROFINET port, 53 Message frame extension, 97 Onboard I/Os, 85
RESET button, 34 Upgrading, 126
Upgrading the firmware, 126 D410 configuration
Message frame 39x, 87 D410 device version, 121
Upgrading, 121 D410 devices update
Downgrading, 138 D410 diagnosis
Diagnostic functions, 138 LED display, 136
Switch 6, 138
Switch 7, 138
D410 downgrading, 126 Devices update, 138
D410 LEDs, 135
D410 LEDs display, 135 Diagnostics data, 136
D410 LEDs state, 135
D410 message frame configuration Message frame 39x, 87
D410 onboard I/Os Digital outputs, 100
D410 operating state, 135 LEDs, 135
D410 PN Initialization, 54 IP Address, 54
LED display on the PROFINET port, 53
147
Index
LED status on the port, 53 Node initialization, 54 PROFINET interface, 53 Reading the IP address, 55 Renaming a device, 54
D410 PN PROFINET port LED display, 53
D410 project
Downloading to the file system, 72 Downloading to the target system, 71
D410 quantity framework
D410 upgrading, 126 Declaration of conformity, 139 Device names
Changing on the D410 PN, 55 Configuring on the D410 PN, 55
Diagnostics buffer entries, 40 DMC20
Creating, 108
Properties, 107 DP cycle
PROFIBUS, 49
PROFINET, 56 Drive control panel, 109 Drive Wizard
E
EMC guidelines, 139 Encoder, 84
over PROFIBUS, 84 Via PROFINET, 84
ESD guideline, 143 Expanding a message frame
D410, 97 External encoders
Configuring in SIMOTION, 84
F
Fan, 125
Operating hours counter, 125 Replacing the fan, 125
Fan operating hours counter, 125
Fetching the IP address of the D410 PN, 55 Firmware update
Starting manually, 128
Free message frame configuring on D410
BICO, 92
Interconnection, 91, 92
Message frame 999, 92
P915/P916, 91
G
Gateway for D410 PN, 55
Global measuring inputs on D410, 101 Parameters, 104
Guideline ESD, 143
H
D410, 100
HW Config alignment, 70
I
I/Os of the D410, 85 IEC 1131, 139 Initialization
D410 PN, 54 Integrated drive
SINAMICS S120, 63 Interfaces
PROFIBUS DP interface, 48 IP Address
Changing on the D410 PN, 55 Configuring on the D410 PN, 55
L
Libraries Upgrading, 130
License key, 127 Licenses
Runtime, 27
Local measuring inputs on D410, 101 Parameters, 103
M
Measuring inputs on D410
Comparison of local and global measuring inputs, 101
Index
Using SIMOTION SCOUT, 116 Using the mode selector switch, 116
Message frame 391 on D410, 87 Message frame 392 on D410, 87 Message frame 39x on D410, 87
PSD1, 89
PSD2, 89
Message frame configuration for D410, 87 Message frame configuring on D410, 91 Message frame extension
D410, 97
Message frames on D410 39x, 87
N
Nameplates
SIMOTION D410 DP, 21
SIMOTION D410 PN, 25
Deleting user data, 117
O
Offline configuration, 62 Onboard I/Os of the D410, 85 Onboard I/Os on the D410, 101
Probe inputs, 101 Online configuration, 73
Overview of the use of the I/Os on the D410, 85
P
Possible applications, 11
Probe inputs on D410, 101
Process status data, 92
PROFIBUS addresses
Assign, 47
PROFIBUS DP
Configuring, 46
Creating a new subnet, 48
Definition, 46
DP cycle, 49
PROFIBUS DP interface, 48
PROFINET
Configuring, 52
D410 PN interfaces, 53
DP cycle, 56
Programming device / PC
Activate the online connection, 74 Project
Creating, 43
Download to the target system, 130 Upgrading, 128
PSD, 92
Maximum number, 92
R
References, 3
Replacing the D410 module
DP with PN and vice versa, 121 In HW Config, 121 Installing/removing the module, 123
Replacing the module
Reset D410, 34
Restoring the default settings SIMOTION D410, 118 SINAMICS Integrated, 118
Rules
PROFINET send cycle, 58 SIMOTION D410 DP, 51 SIMOTION D410 PN, 59 System clocks, 50
Runtime licenses, 27
S
Safety of electronic controllers, 140 SIMOTION D410
Product variants, 11 System
Shutdown, 119 System cycle clock DP cycle, 49, 56 IPO cycle, 49, 56
System function _savePersistentMemoryData, 39
System integration, 12
T
Technology package
Upgrading, 129
Terminal Module TM41, 106
Configuring, 106
Testing the drive, 109
Index