Use & Care Guide
Model No.
153.332620 40 Gallon Tall
153.332640 50 Gallon Tall
Kenmore Elite??
Gas Water Heater
For potable water heating only.
Not suitable for space heating.
Not for use in mobile homes.
INSTALLER: Affix these instructions to or near the water heater.
OWNER: Retain these instructions for future reference.
FOR YOUR SAFETY: An odorant is added to the gas used by this water heater.
ADVERTENCIA
Si no puede leer o entender el ingl??s y necesita el manual de instrucciones en espa??ol, puede solicitarlo al
TRATE DE INSTALAR U OPERAR ESTE CALENTADOR DE AGUA SI NO ENTIENDE LAS INSTRUCCIONES. No hacer caso de esta advertencia podr??a originar lesiones graves o mortales.
P/N
Sears Brands Management Corporation,
Hoffman Estates, IL 60179 U.S.A.
www. kenmore.com
www.sears.com
1
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater.
Many
This is the safety alert symbol. It is used to alert you to potential personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage.
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and how to avoid the risk of injury.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances. WARNING: This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This appliance can cause
IMPORTANT DEFINITIONS
???Quali???ed Technician: A quali???ed technician must have ability equivalent to a licensed tradesman in the ???elds of plumbing, air supply, venting, and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas ???red water heaters. The quali???ed technician must also be familiar with the design features and use of ???ammable vapor ignition resistant water heaters, and have a thorough understanding of this instruction manual.
???Service Agency: A service agency also must have ability equivalent to a licensed tradesman in the ???elds of plumbing, air supply, venting and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas ???red water heaters. The service agency must also have a thorough understanding of this instruction manual, and be able to perform repairs strictly in accordance with the service guidelines provided by the manufacturer.
???Gas Supplier: The natural gas or propane utility or service who supplies gas for utilization by the gas burning appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including the natural gas meter or propane storage tank of a building. Many gas suppliers also offer service and inspection of appliances within the building.
SAFETY PRECAUTIONS
Read and follow water heater warnings and instructions.
?? Sears Brands Management Corporation
2
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell Natural or LP gas.
Do not expose water heater control to excessive gas pressure.
Use only gas shown on rating plate.
Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended period of
Read instruction manual before installing, using or servicing water heater.
Breathing Hazard - Carbon Monoxide Gas
Install vent system in accordance with codes.
Do not operate water heater if flood damaged
Heater should not be installed for High Altitude operation above 10,100 feet (3,078 m).
Do not operate if soot buildup.
Do not obstruct water heater air intake with insulating jacket.
Do not place chemical vapor emitting products near water heater.
Gas and carbon monoxide detectors are available.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
Improper installation and use may result in property damage.
Do not operate water heater if flood damaged.
Install in location with drainage.
Fill tank with water before operation. Be alert for thermal expansion.
Refer to instruction manual for installation and service.
3
4
5
PRODUCT WARRANTY
12 - YEAR LIMITED WARRANTY ON WATER HEATER
For twelve years from the date of purchase, if this water heater is installed and operated in a
1.Supply free water heater parts for those that are defective in material or workmanship.
2.Supply a free water heater for one that develops a leak.
For the second through twelfth year from the purchase date, you must pay the labor cost for installation of parts or water heater.
For commercial, institutional, industrial or residential use by two or more families, the above limited warranty is only for two years. During the second year you must pay the labor cost for parts or water heater installation.
If governmental regulations prohibit Sears from furnishing a comparable model replacement water heater under this warranty, Sears will furnish a new water heater of comparable output as permitted by such governmental regulations; however, the Owner will be charged for the additional cost associated with the changes made to comply with such governmental regulations.
Replacements furnished under this warranty do not carry a new warranty; and are only covered by the unexpired portion of the original warranty.
1 - YEAR EXCLUSIVE KENMORE LABOR WARRANTY
For the ???rst year from the date of purchase, Sears will, free of charge, supply and install new water heater parts for defective ones or a new water heater for one that develops a leak.
WARRANTY SERVICE
To obtain warranty service, call
This warranty applies only while this product is in use in the United States.
This warranty gives you speci???c legal rights, and you may also have other rights which vary from state to state.
SEARS BRANDS MANAGEMENT CORPORATION, Hoffman Estates, IL 60179
The price of your water heater does not include a free checkup service call. On water heater installations arranged by Sears, Sears
warrants the installation.
A charge will be made on service calls due to poor or incomplete installation. These include:
Master Protection Agreements
Congratulations on making a smart purchase. Your new Kenmore?? product is designed and manufactured for years of dependable operation. But like all products, it may require preventive maintenance or repair from time to time. That???s when having a Master Protection Agreement can save you money and aggravation.
The Master Protection Agreement also helps extend the life of your new product. Here???s what the Agreement* includes:
???Parts and labor needed to help keep products operating properly under normal use, not just defects. Our coverage goes well beyond the product warranty. No deductibles, no functional failure excluded from coverage??? real protection.
???Expert service by a force of more than 10,000 authorized Sears service technicians, which means someone you can trust will be working on your product.
???Unlimited service calls and nationwide service, as often as you want us, whenever you want us.
???
???Product replacement if your covered product can???t be fixed.
???Annual Preventive Maintenance Check at your request ??? no extra charge.
???Fast help by phone ??? we call it Rapid Resolution ??? phone support from a Sears representative on all products. Think of us as a ???talking owner???s manual.???
???Power surge protection against electrical damage due to power fluctuations.
???$250 Food Loss Protection annually for any food spoilage
???Rental reimbursement if repair of your covered product takes longer than promised.
???10% discount off the regular price of any
Once you purchase the Agreement, a simple phone call is all that it takes for you to schedule service. You can call anytime day or night, or schedule a service appointment online.
The Master Protection Agreement is a risk free purchase. If you cancel for any reason during the product warranty period, we will provide a full refund. Or, a prorated refund anytime after the product warranty period expires. Purchase your Master Protection Agreement today!
Some limitations and exclusions apply. For prices and additional information in the U.S.A. call
* Coverage in Canada varies on some items. For full details, call Sears Canada at
Sears Installation Service
For Sears professional installation of home appliances, garage door openers, water heaters, and other major home items, in the U.S.A. or Canada call
6
CUSTOMER RESPONSIBILITIES
Thank You for purchasing a Kenmore water heater. Properly installed and maintained, it should give you years of trouble free service. If you should decide that you want the new water heater professionally installed by Sears call
Abbreviations Found In This Instruction Manual:
???CSA - Canadian Standards Association
???ANSI - American National Standards Institute
???NFPA - National Fire Protection Association
???ASME - American Society of Mechanical Engineers
???GAMA - Gas Appliance Manufacturers Association
Important Information About This Water Heater:
This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a ???ammable vapor ignition incident. New technology used in meeting these standards makes this product more sensitive to installation errors or improper installation environments. Please review the Installation Checklist section and make any required installation upgrades or changes.
This manual contains instructions for the installation, operation, and maintenance of the
BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER
HEATER.
???The installation must conform with these instructions and the local code authority having jurisdiction. In the absence of local codes, installations shall comply with the following:
In the United States: The National Fuel Gas Code ANSI Z223.1/ NFPA 54. This publication is available from the Canadian Standards Association, 8501 East Pleasant Valley Rd, Cleveland Ohio 44131, or The National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
???If after reading this manual you have any questions or do not understand any portion of the instructions, call the Sears Service Center.
???Carefully plan the place where you are going to put the water heater. Correct combustion, vent action, and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and ???res. See Figure 1.
???Examine the location to ensure the water heater complies with the Installation Instructions section in this manual.
???For California installation, this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California???s Of???ce of the State Architect, 1102 Q Street, Suite 5100, Sacramento, CA 95811. Instructions can also be downloaded to your computer at www.dsa.dgs.ca.gov/Pubs.
???Massachusetts Code requires this water heater to be installed in accordance with Massachusetts
???Complies with 40 Ng/J NOx requirements of Texas and most California AQM Districts.
WARNING
Excessive Weight Hazard
Use two or more people to move and install the water heater. Failure to do so can result in injury (including back injury).
IMPORTANT: Do not remove any permanent instructions, labels, or the data label from either the outside of the water heater or on the inside of water heater panels.
???Remove exterior packaging and place installation components aside.
???Inspect all parts for damage prior to installation and
???Completely read all instructions before attempting to assemble and install this product.
???After installation, dispose of/recycle all packaging materials.
7
PRODUCT SPECIFICATIONS
8
MATERIALS AND BASIC TOOLS NEEDED
MATERIALS NEEDED
To simplify the installation Sears has available the installation parts shown below. You may or may not need all of these materials, depending on your type of installation.
EXPANSION TANKS FOR
THERMAL EXPANSION
CONDITIONS AVAILABLE
IN 2 GALLONS (7.6 LITERS) AND
5 GALLONS (18.9 LITERS)
CAPACITY THROUGH
LOCAL SEARS STORE
OR SERVICE CENTER.
WAT E R H E AT E R I N S TA L L AT I O N K I T
WITH FLEXIBLE CONNECTORS FOR 3/4??? (19.05 mm) COPPER PLUMBING AND FLEXIBLE
GAS CONNECTOR WITH FITTINGS.
METAL DRAIN PANS AVAILABLE IN 20??? (508 mm) DIAMETER
FOR WATER HEATERS HAVING A DIAMETER 18??? (457 mm) OR LESS, 24??? (610mm) DIAMETER
FOR WATER HEATERS HAVING A DIAMETER 22??? (559 mm) OR LESS AND AVAILABLE IN 28??? (711 mm)
DIAMETER FOR WATER HEATERS HAVING A DIAMETER 26??? (660 mm)
OR LESS.
BASIC TOOLS
You may or may not need all these tools, depending on your type of installation. These tools can be purchased at your local Sears Store.
ADDITIONAL TOOLS NEEDED
WHEN SWEAT SOLDERING
???Pipe Wrenches (2) 14??? (356 mm)
???Screwdriver
???Tin Snips
???6??? (1.82 m) Tape or Folding Ruler
???Garden Hose
???Drill
???Pipe Dope or Te???on Tape
PHILLIPS SCREWDRIVER
ROLL OF TEFLON
TAPE (USE ONLY ON
WATER CONNECTIONS)
DRILL
TIN SNIPS
PIPE DOPE
(SQUEEZE TUBE)
USE FOR WATER AND GAS
CONNECTIONS
9
TYPICAL INSTALLATION
GET TO KNOW YOUR WATER HEATER - GAS MODELS
*INSTALL IN ACCORDANCE
WITH LOCAL CODES.
*DRIP LEG AS REQUIRED
BY LOCAL CODES.
* ALL PIPING MATERIALS
TO BE SUPPLIED BY
CUSTOMERS.
(S) GAS CONTROL VALVE/THERMOSTAT
TO VENT TERMINATION
ON ROOF
Y
K
IMPORTANT: DO NOT USE AN EXTENSION CORD TO CONNECT
THE WATER HEATER TO AN ELECTRICAL OUTLET.
FIGURE 1.
10
IMPORTANT INFORMATION ABOUT THIS WATER HEATER
This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor ignition incident. The new technology used in meeting these standards makes this product more sensitive to installation errors. Please review the following checklist and make any required installation upgrades or changes.
Questions? Contact Sears at
Installation Checklist
Water Heater Location
Water heater location is important and can affect system performance. Please check the following:
???
???
Installation area free of corrosive elements and flammable materials.
Centrally located with the water piping system (For new installations). Located as close to the gas piping, vent pipe system and 120VAC outlet as possible.
???
???
Located indoors and in a vertical position. Protected from freezing temperatures.
Proper clearances from combustible surfaces maintained and not installed directly on a carpeted floor.
???
???
Provisions made to protect the area from water damage. Metal drain pan installed and piped to an adequate drain.
Sufficient room to service the water heater. See Clearances and Accessibility section of this manual.
???
???
Water heater not located near an air moving device.
Is the installed environment dirty (excessive amounts of lint, dirt, dust, etc.)? If so, the air intake chamber louvers located on the side of the water heater will need to be cleaned periodically. Refer to the maintenance section of your water heater???s manual for information on cleaning the ???Air Intake Chamber Screen???.
Combustion Air Supply and Ventilation
Check for sufficient combustion air supply. Insufficient air for the combustion of gas will result in a inferior burner flame ???yellow- lazy???, thereby allowing smoking and carbon formation (sooting) to build up in the combustion chamber.
Is the water heater installed in a closet or other small, enclosed space? If so:
???Are there openings for
???Are the openings of sufficient size? Remember, if there are other
Fresh air not taken from areas that contain negative pressure producing devices such as exhaust fans, dryers, fireplaces, etc.
???Is there a furnace/air handler in the same room space as the water heater? If so, has a return air duct system been attached that exits the room? If so, check for leaks on the air duct system. If no air duct system is present, correct immediately by contacting a local Heating, Ventilation, Air- Conditioning & Refrigeration
???Fresh air supply free of corrosive elements and flammable vapors.
???Ductwork is the same
11
INSTALLATION INSTRUCTIONS
Removing the Old Water Heater
6 1
MANUAL GAS
GROUND
JOINT
UNION
CHECK WITH
LOCAL UTILITY
5 2
DISCHARGE PIPE
(DO NOT CAP
OR PLUG)
4.Attach a hose to the water heater drain valve and put the other end in a ???oor drain or outdoors. (See Figures 2 and 5.) Open the water heater drain valve.
FIGURE 5.
FOR MINIMUM HEIGHT
DRIP LEG
FIGURE 2.
1.Turn ???OFF??? the gas supply to the water heater.
If the main gas line shutoff valve serving all gas appliances is used, also shut ???OFF??? the gas at each appliance. Leave all gas appliances
and 4.
3.Check again to make sure the gas supply is ???OFF??? to the water heater. Then disconnect the gas supply connection from the gas control valve.
6.If you have copper piping to the water heater, the two copper water pipes can be cut with a hacksaw approximately four inches away from where they connect to the water heater. See Figure 6. This will avoid cutting off pipes too short. Additional cuts can be made later if necessary. Disconnect the
FIGURE 6.
If you have galvanized pipes to the water heater, loosen the two galvanized pipes with a pipe wrench at the union in each line. Also disconnect the piping remaining to the water heater. See Figure 7. These pieces should be saved since they may be needed when reconnecting the new water heater. Disconnect the
FIGURE 7.
12
Location Requirements
WARNING
Carbon Monoxide Poisoning Hazard
Do not install in a mobile home.
Doing so can result in carbon monoxide poisoning and death.
The FVIR System is designed to reduce the risk of flammable
FIGURE 8.
FV Sensor
This heater is equipped with a FV sensor for detecting the presence of flammable vapors. When the sensor detects those vapors, the unit will shut down and not operate. Should this happen, please refer to the troubleshooting guide on pages
WARNING
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Storage of or use of gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance can result in serious injury or death.
Read and follow water heater warnings and instructions
Do not use or store flammable products such as gasoline, solvents, or adhesives in the same room or area near the water heater. If such flammables must be used, all gas burning appliances in the vicinity must be shut off and their pilot lights extinguished. Open the doors and windows for ventilation while flammable substances are in use.
If flammable liquids or vapors have spilled or leaked in the area of the water heater, leave the area immediately and call the fire department from a neighbor???s home. Do not attempt to clean the spill until all ignition sources have been extinguished.
WARNING
Fire or Explosion Hazard
???Read instruction manual before installing, using or servicing water heater.
???Improper use may result in fire or explosion.
???Maintain required clearances to combustibles.
Keep combustibles such as boxes, magazines, clothes, etc. away from the water heater area.
Site Location
???Select a location near the center of the water piping system. The water heater must be installed indoors and in a vertical position on a level surface. DO NOT install in bathrooms, bedrooms, or any occupied room normally kept closed.
???Locate the water heater as close to the chimney or gas vent as practical. Consider the vent system piping and combus- tion air supply requirements when selecting the water heater location. The venting system must be able to run from the water heater to termination with minimal length and elbows.
???Locate the water heater near the existing gas piping. If installing a new gas line, locate the water heater to minimize the pipe length and elbows.
???The water heater should be located in an area not subject to freezing temperatures. Water heaters located in unconditioned spaces (i.e., attics, basements, etc.) may require insulation of the water piping and drain piping to protect against freezing. The drain and controls must be easily accessible for operation and service. Maintain proper clearances as specified on the water heater.
???Do not locate the water heater near an
Flow reversal of flue gases may cause an increase of carbon monoxide inside of the dwelling (Figure 10).
???The water heater is to be located as close as possible to a 120VAC outlet. NOTE: all electrical wiring should be in accordance to the NEC and all local/state electrical codes (extension cord is not allowed).
NOTE: This water heater must be installed according to all local and state codes or, in the absence of local and state codes, the ???National Fuel Gas Code???, ANSI Z223.1(NFPA
13
IMPORTANT: The water heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the water heater or to lower floors of the structure. Due to the normal corrosive action of water, the tank will eventually leak after an extended period of time. Also any external plumbing leak, including those from improper installation, may cause early failure of the tank due to corrosion if not repaired. If the homeowner is uncomfortable with making the repair a qualified technician should be contacted. A suitable metal drain pan should be installed under the water heater as shown below, to help protect the property from damage which may occur from condensate formation or leaks in the piping connections or tank. The pan must limit the water level
to a maximum depth of
FIGURE 9.
Pipe to an adequate drain
Water heater life depends upon water quality, water usage, water temperature and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a metal drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water
pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:
???Sensors mounted in the metal drain pan that trigger an alarm or turn off the incoming water to the water heater when water is detected.
FIGURE 10.
Clearances and Accessibility
NOTE: Minimum clearances from combustible materials are stated on the label on the front of the heater adjacent to the gas control valve/thermostat of the water heater.
The water heater is certified for installation on a combustible floor.
???IMPORTANT: If installing over carpeting, the carpeting must be protected by a metal or wood panel beneath the water heater. The protective panel must extend beyond the full width and depth of the water heater by at least five inches (127mm) in any direction; or if in an alcove or closet installa- tion, the entire floor must be covered by the panel.
???Figure 11 may be used as a reference guide to locate the specific clearance locations. A minimum of 5 inches of front clearance should be provided for inspection and service.
0??? min. Back
0??? min. Sides
0??? min. Air Inlet Chamber
5??? min.
Front
Top View
???Sensors mounted in the metal drain pan that turn off the water supply to the entire home when water is detected in the metal drain pan.
???Water supply
???Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply.
Minimum Clearance Locations
FIGURE 11.
High Altitude Installation
This water heater should not be installed for operation at elevations above 10,100 ft. (3,078 m).
14
GAS SUPPLY
WARNING
Explosion Hazard
Manual Gas
Ground Joint Union
Install a readily acces- sible manual
Check with local utility for minimum height.
3??? Minimum
Drip Leg
Discharge Pipe (Do Not plug or cap)
6??? Max. Air Gap
Suitable Drain
Gas Requirements
IMPORTANT: Read the rating plate to be sure the water heater is made for the type of gas you will be using in your home. This information will be found on the rating plate located near the gas control valve/thermostat. If the information does not agree with the type of gas available, do not install or light. Call your dealer.
NOTE: An odorant is added by the gas supplier to the gas used by this water heater. This odorant may fade over an extended period of time. Do not depend upon this odorant as an indication
of leaking gas.
Gas Piping
The gas piping must be installed according to all local and state codes or, in the absence of local and state codes, the ???National Fuel Gas Code???, ANSI Z223.1(NFPA
Tables 1 and 2 on the following page provide a sizing reference for commonly used gas pipe materials. Consult the ???National Fuel Gas Code??? for the recommended gas pipe size of other materials.
NOTE: Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum gases (See Figure 12.)
1.Install a readily accessible manual
2.Install a drip leg (if not already incorporated as part of the water heater) as shown. The drip leg must be no less than three inches long for the accumulation of dirt, foreign material, and water droplets.
3.Install a ground joint union between the gas control valve/ thermostat and the manual
4.Turn the gas supply on and check for leaks. Test all connections by brushing on an approved noncorrosive leak- detection solution. Bubbles will show a leak. Correct any leak found.
FIGURE 12.
Gas Pressure
WARNING
Explosion Hazard
???Gas leaks can not always be detected by smell.
???Gas suppliers recommend that you use a gas detector approved by UL or CSA.
???For more information, contact your gas supplier.
???If a gas leak is detected, follow the ???What to do if you smell gas??? instructions on the cover of this manual.
IMPORTANT: The gas supply pressure must not exceed the maximum supply pressure as stated on the water heater???s rating plate. The
minimum supply pressure is for the purpose of input adjustment.
Gas Pressure Testing
IMPORTANT: This water heater and its gas connection must be leak tested before placing the appliance in operation.
???If the code requires the gas lines to be tested at a pressure exceeding 14??? W.C., the water heater and its manual
???If the gas lines are to be tested at a pressure less than 14??? W.C., the water heater must be isolated from the gas supply piping system by closing its manual
NOTE: Air may be present in the gas lines and could prevent the burner from lighting on initial
15
Gas Pipe Capacity Table
WARNING
Explosion Hazard
???Use a new CSA approved gas supply line.
???Install a
???Do not connect a natural gas water heater to an L.P. gas supply.
???Do not connect an L.P. gas water heater to a natural gas supply.
???Failure to follow these instructions can result in death, explosion, or carbon monoxide poisoning.
WARNING
Explosion Hazard
???Gas leaks can not always be detected by smell.
???Gas suppliers recommend that you use a gas detector approved by UL or CSA.
???For more information, contact your gas supplier.
???If a gas leak is detected, follow the ???What to do if you smell gas??? instructions on the cover of this manual.
16
COMBUSTION AIR & VENTILATION
WARNING
Carbon Monoxide Warning
Water heater must be vented to outdoors.
Vent must be installed by a qualified technician using the installation instructions.
Examples of a qualified technican include: gas technicians, authorized gas company personel, and authorized service persons.
Failure to so do can result in death or carbon monoxide poisoning.
IMPORTANT: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage.
The following types of installation (not limited to the following) will require outdoor air for combustion due to chemical exposure and may reduce but not eliminate the presence of corrosive chemicals in the air:
???beauty shops
???photo processing labs
???buildings with indoor pools
???water heaters installed in laundry, hobby, or craft rooms
???water heaters installed near chemical storage areas
Combustion air must be free of
Combustion and ventilation air requirements are determined by the location of the water heater. The water heater may be located in either an open (unconfined) area or in a confined area or small enclosure such as a closet or small room. Confined spaces are areas with less than 50 cubic feet for each 1,000 BTUH of the total input for all
Unconfined Space
A water heater in an unconfined space uses indoor air for combustion and requires at least 50 cubic feet for each 1,000 BTUH of the total input for all gas appliances. The table below shows a few examples of the minimum square footage (area) required for various BTUH inputs.
TABLE 3
IMPORTANT:
???The area must be open and be able to provide the proper air requirements to the water heater. Areas that are being used for storage or contain large objects may not be suitable for water heater installation.
???Water heaters installed in open spaces in buildings with un- usually tight construction may still require outdoor air to func- tion properly. In this situation, outside air openings should be sized the same as for a confined space.
???Modern home construction usually requires supplying out- side air into the water heater area.
Confined Space
For the correct and proper operation of this water heater, ample air must be supplied for the combustion, ventilation, and dilution of flue gases. Small enclosures and confined areas must have two permanent openings so that sufficient fresh air can be drawn from outside of the enclosure. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure as shown in Figure 13.
The size of each opening (free area) is determined by the total BTUH input of all gas utilization equipment (i.e., water heaters, furnaces, clothes dryers, etc.) and the method by which the air is provided. The BTUH input can be found on the water heater rating plate. Additional air can be provided by two methods:
1.All air from inside the building.
2.All air from outdoors.
17
12??? Max.
free area of the opening to which they connect. The minimum dimension of rectangular air ducts cannot be less than three inches.
Permanent openings to the outside or additional rooms within the building
The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 4 to calculate the minimum free area for each opening. Figures 15, 16, 17 and 18 are typical examples of each method.
Louvers and Grilles
In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect
of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 1/4??? mesh. If the free area through a particular
FIGURE 13.
All Air from the Building
When additional air is to be provided to the confined area from additional room(s) within the building, the total volume of the room(s) must be of sufficient size to properly provide the necessary amount of fresh air to the water heater and other gas utilization equipment in the area. If you are unsure that the structure meets this requirement, contact your local gas utility company or other qualified agency for a safety inspection. Each of the two openings shall have a minimum free area of 1 square inch per 1,000 BTUH of the total input rating of all gas utilization equipment in the confined area, but not less than 100 square inches (Figure 14).
Confined
Space
Permanent
Openings
1 Square inch/1000
BTUH (min. 100 sq. in.)
FIGURE 14.
All Air from Outdoors
Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside.
Ductwork must be of the same
design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area.
Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation.
Keep louvers and grilles clean and free of debris or other obstructions.
TABLE 4
Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only.
Based on total BTUH input rating for all utilizing equipment within the con???ned space.
Example: A water heater with an input rating of 50,000 BTUH using horizontal ducts would require each opening to have a minimum free area of 25 square inches.
Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in.
*These openings connect directly with the outdoors through a venti- lated attic, a ventilated crawl space, or through an outside wall.
Consult the local codes of your area for specific ventilation and combustion air requirements.
18
All Air From Outdoors: Inlet Air From Ventilated Crawl Space/Outlet Air To Ventilated Attic
FIGURE 15.
Alternative
Opening
Location
Confined
Space
1 sq. in. per
3000 BTUH
All Air From Outdoors - Using A Single Permanent Opening
FIGURE 18.
Vent Pipe System
This water heater uses a
Confined
Space
Gable Vent to Outdoors
Install Above
Outlet Air to the Attic 1 sq. in. per 4000 BTUH
Inlet Air Duct 1 sq. in. per 4000 BTUH
for combustion is taken from the immediate water heater location or is ducted in from the outside (see ???Combustion Air Supply and Ventilation???).
This water heater must be properly vented for the removal of exhaust gases to the outside atmosphere. Correct installation of the vent pipe system is mandatory for the proper and efficient operation of this water heater and is an important factor in the life of the unit.
The vent pipe must be installed according to all local and state codes or, in the absence of local and state codes, the ???National Fuel Gas Code???, ANSI Z223.1(NFPA
12??? Max.
All Air from Outdoors Through Ventilated Attic
FIGURE 16.
1 sq. in. per
2000 BTUH
Outdoor
Air Ducts
Inlet
1 sq. in. per
2000 BTUH
All Air From Outdoors Using Horizontal Ducts
FIGURE 17.
IMPORTANT: The use of vent dampers is not recommended by the manufacturer of this water heater. Although some vent dampers are certified by CSA International, this certification applies to the vent damper device only and does not mean they are certified for use on this water heater.
U.L. recognized fuel gas and carbon monoxide (CO) detectors are recommended in all applications and should be installed using the manufacturer???s instructions and local codes, rules, or regulations.
IMPORTANT: If you lack the necessary skills required to properly install this venting system, you should not proceed, but get help from a qualified technician.
Draft Hood Installation
FIGURE 19.
19
40 Gal. Water Heater: Align the reducer flue over top of baffle as
shown in Figure 19 (NOTE: reducer flue must be installed on 40 gal. water heater above elevation 5,400 Ft. (1,646 m) from sea level).
40 & 50 Gal. Water Heaters: Align the legs of the draft hood with the slots provided. Insert the legs and secure the draft hood to the water heater???s top with the four screws provided as shown
in Figure 19. Do not alter the draft hood in any way. If you are replacing an existing water heater, be sure to use the draft hood supplied with this water heater.
Vent Pipe Size
It is important that you follow the guidelines in these instructions for sizing a vent pipe system. If a transition to a larger vent size is required, the vent transition connection must be made at the draft hood outlet.
Vent Connectors
1.Type B, Double wall, U.L. Listed Vent Pipe.
2.Single wall Vent Pipe.
Maintain the manufacturer???s specified minimum clearance from combustible materials when using type B double wall vent pipe.
Vent connectors made of type B, double wall vent pipe material may pass through walls or partitions constructed of combustible material if the minimum listed clearance is maintained.
Maintain a six inch minimum clearance from all combustible materials when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used for water heaters located in attics and may not pass through attic spaces, crawl spaces or any confined or inaccessible location. A single wall metal vent connector cannot pass through any interior wall.
When installing a vent connector, please note the following (See Figures
???Install the vent connector avoiding unnecessary bends, which create resistance to the flow of vent gases.
???Install without dips or sags with an upward slope of at least
???Joints must be fastened by sheet metal screws or other approved means. It must be supported to maintain clearances and prevent separation of joints and damage.
???The length of the vent connector cannot exceed 75% of the vertical vent height.
???The vent connector must be accessible for cleaning, inspection, and replacement.
???Vent connectors cannot pass through any ceiling, floor, firewall, or fire partition.
???It is recommended (but not mandatory) that a minimum 12 inches of vertical vent pipe be installed on the draft hood prior to any elbow in the vent system.
IMPORTANT: Existing vent systems must be inspected for obstructions, corrosion, and proper installation.
Chimney Connection
IMPORTANT: Before connecting a vent to a chimney, make sure the chimney passageway is clear and free of obstructions. The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces. Also consult local and state codes for proper chimney sizing and application or, in the absence
of local and state codes, the ???National Fuel Gas Code???, ANSI
Z223.1(NFPA
???The connector must be installed above the extreme bottom of the chimney to prevent potentially blocking the flue gases.
???The connector must be firmly attached and sealed to prevent it from falling out.
???To aid in removing the connector, a thimble or slip joint may be used.
???The connector must not extend beyond the inner edge of the chimney as it may restrict the space between it and the opposite wall of the chimney (Figure 20).
Chimney Termination Vent System
FIGURE 20.
Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.
Vertical Exhaust Gas Vent
Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer???s instructions and the terms of its listing.
It must be connected to the water heater???s draft hood by a listed vent connector or by directly originating at the draft hood opening.
Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer???s instructions.
Gas vents must be supported to prevent damage, joint separation, and maintain clearances to combustible materials (Figures 21 and 22).
IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.
An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent (Figure 22).
Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation. CAUTION: DO NOT common vent this water heater with any power vented appliance.
Figures
20
Venting Gas Vent System With Type B Double Wall Vent Pipe.
Venting Through Chimney With Type B Double Wall Vent Pipe.
FIGURE 22.
*Maintain vent pipe clearance requirements to local, state and/or the ???National Fuel Gas Code???, ANSI Z223.1(NFPA
**NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid
WATER SYSTEM PIPING
Piping Installation
Piping, fittings, and valves should be installed according to the installation drawing (Figure 23). If the indoor installation area is subject to freezing temperatures, the water piping must be protected by insulation.
The water supply pressure should not exceed 80 psi. If this occurs, a pressure reducing valve with a bypass should be installed in the cold water inlet line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressures.
IMPORTANT: Heat cannot be applied to the water fittings on the heater as they may contain nonmetallic parts. If solder connections are used, solder the pipe to the adapter before attaching the adapter to the hot and cold water fittings.
IMPORTANT: Always use a good grade of joint compound and be certain that all fittings are drawn up tight.
1.Install the water piping and fittings as shown in Figure 23. Connect the cold water supply (3/4??? NPT) to the cold water inlet fitting. Connect the hot water piping (3/4??? NPT) to the hot water outlet fitting.
IMPORTANT: Some models may contain energy saving heat traps to prevent the circulation of hot water within the pipes. Do not remove the inserts within the heat traps.
2.The installation of unions in both the hot and cold water supply lines is recommended for ease of removing the water heater for service or replacement.
3.The manufacturer of this water heater recommends installing a mixing valve or an
4.If installing the water heater in a closed water system, install an expansion tank in the cold water line as specified under Closed System/Thermal Expansion.
5.Install a
6.A temperature and pressure relief valve must be installed in the opening marked ???Temperature and Pressure (T & P) Relief Valve??? on the water heater. A discharge line must be added to the opening of the T&P Relief Valve. Follow the instructions under Temperature and Pressure Relief Valve.
7.After piping has been properly connected to the water heater, remove the aerator at the nearest hot water faucet. Open the hot water faucet and allow the tank to completely fill with water. To purge the lines of any excess air, keep the hot water faucet open for 3 minutes after a constant flow of water is obtained. Close the faucet and check all connections for leaks.
21
FIGURE 23.
Mixed Water
To Fixtures
Unmixed
Hot Water
Cold Water
Inlet
Hot Water
Outlet
Mixing Valve
(Set To 1200 F)
Follow The Mixing Valve
Manufacturer???s Instructions
FIGURE 24.
Please note the following:
???The system should be installed only with piping that is suitable for potable (drinkable) water such as copper, CPVC, or polybutylene. This water heater must not be installed using iron piping or PVC water piping.
???Use only pumps, valves, or fittings that are compatible with potable water.
???It is recommend that only full flow ball or gate valves are used in water piping installations. The use of valves that may cause excessive restriction to water flow is not recommended.
???Use only 95/5
???Piping that has been treated with chromates, boiler seal, or other chemicals must not be used.
???Chemicals that may contaminate the potable water supply must not be added to the piping system.
Closed System/Thermal Expansion
As water is heated, it expands (thermal expansion). In a closed system, the volume of water will grow. As the volume of water grows, there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent
A
Temperature and Pressure Relief Valve
Explosion Hazard
???
??? Properly sized temperature- pressure relief valve must be installed in opening provided.
??? Can result in overheating and excessive tank pressure.
??? Can cause serious injury or death.
Temperature and
Pressure Relief Valve
(T&P)
Discharge line 3/4??? Min.
Do not cap or plug.
Metal Drain Pan
6??? Max.
Drain
FIGURE 25.
22
For protection against excessive pressures and temperatures, a temperature and pressure relief valve must be installed in the opening marked ???T & P RELIEF VALVE??? (see Figure 25). This valve must be design certified by a nationally recognized testing laboratory that maintains periodic inspection of the production of listed equipment or materials as meeting the requirements for Relief Valves for Hot Water Supply Systems, ANSI Z21.22. The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of excessive temperature or pressure developing in the water heater. The valve???s relief pressure must not exceed the working pressure of the water heater as stated on the rating plate.
IMPORTANT: Only a new temperature and pressure relief valve should be used with your water heater. Do not use an old or existing valve as it may be damaged or not adequate for the working pressure of the new water heater. Do not place any valve between the relief valve and the tank.
The Temperature & Pressure Relief Valve:
???Must not be in contact with any electrical part.
???Must be connected to an adequate discharge line.
???Must not be rated higher than the working pressure shown on the rating plate of the water heater.
The Discharge Line:
???Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line.
???Must not be capped, blocked, plugged or contain any valve between the relief valve and the end of the discharge line.
???Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommend- ed that the discharge pipe be terminated at an adequate drain inside the building.
???Must be capable of withstanding 250??F (121??C) without dis- tortion.
???Must be installed to allow complete drainage of both the valve and discharge line.
4.Locate the hot water (outlet) & cold water (inlet) pipes to the water heater.
5.Locate the slit running the length of a section of pipe insulation.
6.Spread the slit open and slip the insulation over the cold water (inlet) pipe. Apply gentle pressure along the length of the insulation to ensure it is fully seated around the pipe. Also ensure that the base of insulation is flush with the water heater. Once seated, secure the insulation with duct tape, electrical tape, or equivalent.
7.Repeat steps 5 through 6 for the hot water (outlet) pipe.
8.Add additional sections of pipe insulation as needed.
T&P Relief Valve and Pipe Insulation
1.Locate the temperature and relief valve on the water heater (also known as a T&P Relief Valve, Figure 26).
2.Locate the slit running the length of the insulation.
3Spread this slit open and slip it up under the T&P Relief Valve. See Figure 26. Apply gentle pressure to the insulation to ensure it is fully seated on the T&P Relief Valve. Once sealed secure the insulation with a section of duct tape, electrical tape, or equivalent.
IMPORTANT: The insulation or tape must not block the discharge opening or hinder access to the manual relief lever. Ensure a discharge pipe is installed into the T&P valve discharge opening per the instructions manual.
23
ELECTRICAL
Electrical Connections
IMPORTANT: Do not use an extension cord to connect the water heater to an electrical outlet.
Before plugging in the water heater, always make sure:
???The Voltage and frequency correspond to that specified on the water heater.
???The electrical outlet has the proper overload fuse or breaker protection.
???Unit is to connect to a 120VAC electrical supply outlet (extension cord is not allowed).
WARNING
Electric Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
???The water heater and the outlet are properly grounded.
???Installed in accordance with prevailing provisions of local codes, or in the absence of such, National Electric Code, ANSI/NFPS 70 current edition.
Completely fill the tank with water and check all connections for leaks. Open the nearest hot water faucet and let it run for three (3) minutes to purge the water lines of air and sediment and to ensure complete filling of the tank. The electrical power may then be turned on. Verify proper operation after servicing.
Solar Installation
If this water heater is used as a solar storage heater or as a backup for the solar system, the water supply temperatures to the water heater tank may be in excess of 120??F. A mixing valve or other temperature limiting valve must be installed in the water supply line to limit the supply temperature to 120??F.
NOTE: Solar water heating systems can often supply water with temperatures exceeding 180??F and may result in water heater malfunction.
OPERATING YOUR WATER HEATER
Operating Instructions
Read and understand these directions thoroughly before attempting to operate the water heater. Make sure the view port is not missing or damaged (See Figure 36). Make sure the tank is completely filled with water before operating the water heater. The gas control valve/thermostat has a ???On/Off Switch??? and needs to be turned on before water heater is operational. Check the label on the front of heater near the gas control valve/ thermostat for the correct gas. Do not use this water heater with any gas other than the one listed on the label. If you have any questions or doubts, consult your gas supplier or gas utility company.
WARNING
Explosion Hazard
Replace view port if glass is missing or damaged.
Failure to do so can result in death, explosion or fire.
FOR YOUR SAFETY READ BEFORE OPERATING
OPERATING INSTRUCTIONS
ON
ON/OFF
SWITCH
"GAS CONTROL"
1.STOP! Read the safety information
above on the label.
2.Turn on all electrical power to the appliance.
3.Set the ON/OFF switch on the gas control to the "ON" position.
4.Set the Electronic Display to the lowest setting by first pressing the COOLER and HOTTER buttons together and holding for 1 second. Then press the COOLER button to the lowest setting.
5.Set the ON/OFF switch on the gas control to the "OFF" position.
6.This appliance is equipped with a device which automatically lights the burner.
DO NOT TRY TO LIGHT THE BURNER BY HAND.
the safety information above on this label. If you don't smell gas, go to the next step.
"ELECTRONIC DISPLAY"
8.Set the ON/OFF switch on the gas control to the "ON" postition.
9.Set the Electronic Display to the desired setting by first pressing the COOLER and HOTTER but- tons together and holding for 1 second. Then press the HOTTER button until the desired setting is reached.
DANGER: Hotter water increases the risk scald injury. Consult the instruction manual before changing temperature.
10.If the appliance will not operate, follow the instruc- tions "TO TURN OFF GAS TO APPLIANCE" and call your technician or gas supplier.
WARNING: TURN OFF ALL
ELECTRIC POWER BEFORE SERVICING.
TO TURN OFF GAS TO APPLIANCE
1. Set the Electronic Display to the lowest setting by first pressing the COOLER and HOTTER but- tons together and holding for 1 second. Then press the COOLER button to the lowest setting.
2.Set the ON/OFF switch on the gas control to the "OFF" postition.
3.Turn off all electrical power to the appliance if service is to be performed.
25
Water Heater Operation
Figure 29 below shows the water heater???s sequence of operation when a call for heat is initiated. The ignition control module will attempt to light the burner three times. If the ignition control does not detect ignition it will enter lockout mode, indicated by display flashing status code (see status code 3 page 38 and/or status code 8 page 39).
Checking the Draft
WARNING
Burn Hazard
Do not touch vent.
Doing so can result in burns.
SEQUENCE OF OPERATION
After successfully lighting the water heater, allow the unit to operate for 15 minutes and check the draft hood relief opening for proper draft (Figure 30). Make sure all other appliances in the area are operating and all doors/windows are closed when
Call for heat indicated by flashing of display screen status codes.
Gas valve/thermostat will open for 4 second trial for ignition and fan will turn on.
performing the draft test. Pass a match flame or smoke around the relief opening of the draft hood. A steady flame or smoke drawn into the opening indicates proper draft.
Gas valve/thermostat will do a relay check (relay clicks will be heard).
Display will show temperature set point during call for heat.
Draft Blower is energized.
System will verify pressure switch operation and start a 5 second
Ignitor will start a 12 second warm up period. ???IGN??? will show on display.
Main burner flame is detected by flame sense rod. Air intake fan and main burner will continue to operate until water temperature inside the tank reaches temperature set point.
Gas valve/thermostat is de- energized and air intake fan continues for a post purge time of approximately 5 seconds.
Water heater returns to standby mode.
Flue Products Vented
to Ouside of Building
Dilution Air
Draft Hood
Dilution Air
(Relief Opening)
Dilution Air
Match
Air is drawn in for combustion. Keep area clean and free from combustibles and flammable vapors.
FIGURE 29.
6??? Maximum
Air Gap
Floor Drain
Outer Door
The water heater must be installed according to all local and state codes or in the adsence of local and state codes, the ???National Fuel Code?????? ANSI Z223.1(NFPA 54)- current edition.
FIGURE 30.
If the flame flutters or is blown out, combustion products are escaping from the relief opening. If this occurs, do not operate the water heater until proper adjustments or repairs are made to the vent pipe system and/or air supply requirements.
26
Burner Flames
Inspect the burner flames through the viewport and compare them to the drawings in Figure 31. A properly operating burner should produce a soft blue flame. Blue tips with yellow inner cones are satisfactory. The tips of the flame may have a slight yellow tint. The flame should not be all yellow or have a sharp
FIGURE 31.
Emergency Shut Down
IMPORTANT: Should overheating occur or the gas supply fails to shut off, turn off the heater???s manual gas control valve and the electrical power. Call a qualified technician.
Water Temperature Regulation
Water temperature over 125??F (52??C) can cause servere burns instantly resulting in severe injury or death.
Children, the elderly, and the physically or mentally disabled are at highest risk for scald injury.
Feel water before bathing or showering.
Temperature limiting valves are available.
Read instruction manual for safe temperature setting.
Due to the nature of the typical gas water heater, the water temperature in certain situations may vary up to 30??F (16.7 ??C) higher or lower at the point of use such as, bathtubs, showers, sink, etc.
HOTTER WATER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm, or physically/mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfies your hot water needs, a means such as a mixing valve,
should be used at the hot water taps used by these people or at the water heater. Mixing valves are available at plumbing supply or hardware stores, see Figure 24. Follow manufacturer???s instructions for installation of the valves. Before changing the factory setting on the thermostat see Table 5 and Figure 32. Using the lowest hot water temperature that meets your needs will also provide the most energy efficient operation of the water heater. Never allow small children to use a hot water tap, or to draw their own bath water. Never leave a child or handicapped person unattended in a bathtub or shower.
NOTE: A water temperature range of
The thermostat of this water heater has been factory set at its lowest position. It is adjustable and must be reset to the desired temperature setting to reduce the risk of scald injury. The electronic control display temperature should be set at approximately 120??F (49??C) and this is the preferred starting point, see Table 5. Some states have a requirement for a lower
setting. If you need hotter water, follow directions for temperature adjustment, but beware of the warnings in this section.
(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978)
TABLE 5
Pressing the ???COOLER???button decreases temperature and pressing the ???HOTTER???button increases the temperature.
To avoid any unintentional changes in water temperature settings, the control has a tamper resistant feature for changing the temperature setting. To change the temperature setting follow these instructions:
1.???Unlock??? the temperature indicators by holding down both ???COOLER??? and ???HOTTER??? temperature adjustment buttons at the same time for one second (See Figure 32). The dis- play will light up. The display will only remain on for 30 sec- onds if no further buttons are pressed. After 30 seconds the control will go back to ???Lock??? mode (???Lock??? mode indicates a temperature setting is locked into the control memory).
2.Release both of the temperature adjustment buttons.
A.To decrease the temperature press and release the ???COOLER???button until the desired setting is reached.
B.To increase the temperature press and release the ???HOTTER???button until the desired setting is reached.
NOTE: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
NOTE: During low demand periods when hot water is not being used, a lower thermostat setting will reduce energy losses and
27
may satisfy your normal hot water needs. If hot water use is expected to be more than normal, a higher thermostat setting may be required to meet the increased demand. When leaving your home for extended periods (vacations, etc.) Set the electronic control display temperature ???COOLER???button to its lowest setting. This will maintain the water at low temperatures with minimum energy losses and prevent the tank from freezing during cold weather.
Gas Control Valve/Thermostat Settings
HOTTER COOLER
Electronic Control Display
FIGURE 32.
Powered Anode Operation
To protect the
If the powered anode rod has been damaged then the powered anode rod should be removed from the water heater tank and replaced. IMPORTANT: If the damaged powered anode rod has not been replaced but has been removed permanently, this will void any warranties.
FIGURE 33.
NOTE: Whether
To replace the powered anode rod:
1.Set the gas control valve/thermostat to its lowest setting by pressing the ???COOLER??? and ???HOTTER??? buttons together at the same time holding for 1 second. Then press the ???COOLER??? button to the lowest setting (Figure 32).
2.Turn gas control switch to the ???OFF??? position (located right side of the gas control valve/thermostat (Figure 28), and turn off the gas supply to the unit.
3.Disconnect the electric connection by unplugging the water heater from the wall outlet.
4.Shut off the incoming water supply to the water heater and open a nearby hot water faucet to depressurize the water tank.
5.Remove the manifold cover outer door and connect a hose to the drain valve and terminate it to adequate drain or to the exterior of the building. Open the drain valve and allow at least 5 gallons of water from the tank to drain. Close drain and remove hose.
6.Unplug the electrical connection on top of the powered anode by pulling the wire connector up and off of the powered anode rod electrical connector (Figure 33).
7.Remove the powered anode rod by using a ratchet and a
8.Use Teflon?? tape or an approved pipe sealant on threads of the new powered anode rod.
9.Prior to installing, it will be necessary to use pliers to bend up approximately 90?? the electrical male connector on the top of the powered anode rod. The electrical connector should be bent upward in order to allow the
10.Place the powered anode rod in the spud (top of the tank) and turn clockwise until the threads are hand tight. Using a ratchet and
11.Open a nearby hot water faucet to purge air from the water line. Fill water heater tank completely (Note: To assure the water heater tank is full, keep the hot water faucet open for 3 minutes after a constant flow of water is obtained).
12.After turning off the hot water faucet, check for water leaks around powered anode rod and immediately correct any if found.
13.Upon determining there???s no water leak at the newly installed powered anode rod, reconnect the electrical plug connector to the top of the anode male terminal.
14.Plug the electric transformer in the wall outlet and turn the gas supply back on to the gas control valve/thermostat.
15.Turn the gas control switch to the ???ON??? position (located on the side of the gas control valve/thermostat (Figure 28).
16.To restart the water heater, follow the directions on the ???Lighting and Operating Instructions??? label located on the front of the water heater near the gas control valve/ thermostat (Figure 28).
17.Upon verifying proper operation of the water heater, replace the manifold cover outer door.
TEFLON?? is a registered trademark of E.I. Du Pont De Nemours and Company
28
SERVICE AND ADJUSTMENT
Draining and Flushing
It is recommended that the tank be drained and flushed every 6 months to remove sediment which may build up during operation. The water heater should be drained if being shut down during freezing temperatures. To drain the tank, perform the following steps:
1.Turn off the gas to the water heater at the manual gas shut- off valve and turn off the electrical power to the gas control/ thermostat valve.
2.Open a nearby hot water faucet until the water is not longer hot.
3.Close the cold water inlet valve.
4.Connect a hose to the drain valve and terminate it to an adequate drain or external to the building.
5.Open the water heater drain valve and allow all the water to drain from the tank. Flush the tank with water as needed to remove sediment.
6.Close the drain valve, refill the tank, and restart the heater as directed in this manual.
If the water heater is going to be shut down for an extended period, the drain valve should be left open.
IMPORTANT: Condensation may occur when refilling the tank and should not be confused with a tank leak.
Routine Preventive Maintenance
At least annually, a visual inspection should be made of the venting and air supply system, piping systems, and main burner. Check the water heater for the following:
???Obstructions, damage, or deterioration in the venting system. Make sure the ventilation and combustion air supplies are not obstructed.
???Clean any dust or debris from the screen of the air intake chamber.
Temperature and Pressure Relief Valve
Explosion Harzard
???
??? Properly sized temperature- pressure relief valve must be installed in opening provided.
??? Can result in overheating and excessive tank pressure.
??? Can cause serious injury or death.
Manually operate the temperature and pressure relief valve at least once a year to make sure it is working properly. To prevent water damage, the valve must be properly connected to a discharge line which terminates at an adequate drain. Standing clear of the outlet (discharged water may be hot), slowly lift
and release the lever handle on the temperature and pressure relief valve to allow the valve to operate freely and return to its closed position. See Figure 34. If the valve fails to completely reset and continues to release water, immediately shut off the electrial power, manual gas control valve and the cold water
inlet valve and call a qualified technician. Contact Sears Service
TEMPERATURE AND PRESSURE
RELIEF VALVE
MANUAL RELIEF
VALVE
DISCHARGE LINE TO DRAIN
FIGURE 34.
???Soot and/or carbon on the main burner. Contact a qualified technician.
???Leaking or damaged water and gas piping.
???Presence of flammable or corrosive materials in the installation area.
???Presence of combustible materials near the water heater.
???After servicing this water heater, check to make sure it is working properly. (See ???Operating Your Water Heater??? section of this manual.)
IMPORTANT: If you lack the necessary skills required to properly perform this visual inspection, you should not proceed, but get help from a qualified technician.
29
MAINTENANCE OF YOUR WATER HEATER
Replacement Parts
IMPORTANT: The following maintenance procedures are for the FVIR System components and should be performed by a qualified technician.
Replacement parts may be ordered from Sears Parts and Service Centers or by calling
1.model, serial, and product number
2.type of gas
3.item number
4.parts description
See ???Parts Order List??? section for a list of available repair parts.
Removing the Manifold/Burner Assembly
1.Turn off the gas supply to the water heater at the manual gas
2.Disconnect power supply to the heater.
3.Remove the outer door. Remove the 2 screw securing the manifold door assembly to the skirt.
4.Disconnect all wiring connectors from the gas control valve/ thermostat (Figure 35). Disconnect the manifold tube at the gas control valve/thermostat.
5.Grasp the manifold tube and push down slightly to free the manifold from the gas control valve/thermostat.
6.Carefully remove the manifold assembly from the burner com- partment. NOTE: Be sure not to damage internal parts (Figure 39).
7.Check the burner to see if it is dirty or clogged. The burner may be cleaned with soap and hot water.
Gas Control Valve/
Thermostat
FIGURE 35.
Removing the Burner from the Manifold/ Burner Assembly
Natural Gas Burner
1.Take off the burner by removing the two (2) screws located underneath the burner.
2.Check the burner to see if it is dirty or clogged. The burner may be cleaned with soap and hot water (Figure 36).
Screws
Igniter/Flame
Sense Connector
Burner
(Bottom View)
FIGURE 36.
Replacing the Flame Sense/Hot Surface igniter Assembly
1.Remove the manifold/burner assembly. See Removing the Manifold/Burner Assembly.
2.Lift the retainer clip straight up from the back of the manifold component block (using a
3.Remove and keep the screw securing the flame sense/hot surface igniter assembly (Figure 37)
4.Remove and discard the old flame sense/hot surface igniter assembly.
5.Route the new flame sense/hot surface igniter connector wire through manifold/burner door opening as shown in figure 37. Secure assembly to bracket using screw removed earlier.
6.Reposition the manifold component block in the
7.See Replacing the Manifold/Burner Assembly.
External Inspection & Cleaning of the
Air Intake Chamber Screen
1.At least twice annually inspect the air intake chamber screen (Figure 38) for any dust or debris that may have accumulated on the louvers. NOTE: If the water heater is located in an area that is subjected to lint and dirt, it may be necessary to check the air intake chamber screen
more frequently.
2. Use a vacuum cleaner with a hose attachment to remove any dust or debris that may have accumulated on the screen.
Air Intake Chamber
Screen
FIGURE 38.
Cleaning the Combustion Chamber and Air
Diverter Assembly
1.Follow procedure outlined in ???Removing the Manifold/Burner Assembly???.
2.Use a vacuum cleaner/shop vac to remove all loose debris in the combustion chamber (Figure 39). Use compressed air to clear any dust or debris that may have accumulated on the air diverter assembly.
3.Reassemble following the procedure under ???Replacing the Manifold/Burner Assembly???
Replacing the Manifold/Burner Assembly
WARNING
Explosion Hazard
???Remove any fiberglass between gasket and combustion chamber.
???Replace viewport if glass is missing or damaged.
???Replace two piece wire connector if missing or removed.
???Replace door gasket if damaged.
???Tighten both manifold door screws securely.
???Failure to follow these instructions can result in death, explosion, or fire.
1.Check the door gasket for damage or imbedded debris prior to installation.
2.Inspect the view port for damage and replace as required.
3.Insert the manifold/burner assembly into the burner compartment making sure that the tip of the manifold tube engages in the slot of the bracket inside the combustion chamber (Figure 40).
4.Inspect the door gasket and make sure there is no fiberglass insulation between the gasket and the
combustion chamber.
5.Replace the two screws, which secure the manifold/ burner assembly door to the combustion chamber and tighten securely. Once the manifold/burner assembly door is tightened, visually inspect the door gasket between the manifold/burner assembly door and the combustion chamber for spaces or gaps that would prevent a seal. IMPORTANT: Do not operate the water heater if the door gasket does not create a seal between the manifold door and the combustion chamber.
6.During the following procedure, do not
7.Reconnect the flame sense/hot surface igniter wire to the gas control valve/thermostat (Figure 35).
8.Turn gas supply on and refer to the Lighting Instructions.
9.With the burner lit, check the gas control valve/thermostat supply line, two piece wire connector, and manifold tube connections for leaks. Check for leaks by brushing on an approved noncorrosive leak detection solution. IMPORTANT:
Do Not splash solution onto the electrical connections.
Bubbles forming indicate a leak. Correct any leak found. All leaks must be fixed immediately.
31
10. Replace the outer door (see item K page 10).
Removing and Replacing the Gas Control
Valve/Thermostat
IMPORTANT: Use only factory authorized replacement parts.
Removing the Gas Control Valve/Thermostat:
1.Set the gas control valve/thermostat to its lowest setting by first depressing the COOLERand HOTTER buttons together and hold for 1 second. Then press the COOLER button until the VAC indicator light appears (Figure 32).
2.Unplug the water heater from the wall outlet.
3.Turn off the gas supply to the water heater at the manual gas
4.Drain the water heater. Refer to the section of ???Draining and Flushing??? section and follow the procedure.
5.Disconnect the the flame sense/hot surface igniter wire, power supply transformer, pressure switch/fan and display connector wires from the thermostat (Figure 35). Disconnect the manifould tube at the thermostat (Figure 35).
6.Refer to ???Gas Piping??? section (Figure 12) and disconnect the ground joint union in the gas piping. Disconnect the remaining pipe from the gas control valve/thermostat.
7.To remove the gas control valve/thermostat, thread a correctly sized pipe into the inlet and use it to turn the gas control valve/ thermostat (counterclockwise.) Do not use pipe wrench or equivalent to grip body. Damage may result, causing leaks. Do not insert any sharp objects into the inlet or outlet connections. Damage to the gas control valve/thermostat may result.
Replacing the Gas Valve:
1.To replace the gas control valve/thermostat, reassemble in reverse order. When replacing the gas control valve/ thermostat, thread a correctly sized pipe into the inlet and use it to turn the gas valve (clockwise.) DO NOT OVER TIGHTEN or damage may result. NOTE: Use an approved TEFLON?? tape or pipe compound only on the threaded section of the gas control valve/thermostat that screws into the tank.
2.Reconnect the gas piping to the gas control valve/ thermostat. NOTE: Use an approved Teflon tape or pipe compound on the gas piping connections.
3.Reconnect the manifold tube, flame sense/hot surface igniter wire, power supply transformer, pressure switch/fan and display connector wires (Figure 35).
4.Fill the tank completely with water. NOTE: To purge the lines of any excess air, keep the hot water faucet open for 3 minutes after a constant flow of water is obtained.
5.Turn on the gas supply and test the gas supply connections by brushing on an approved noncorrosive leak detection solution. IMPORTANT: Do Not splash solution onto the electrical connections. Bubbles forming indicate a leak. Correct any leak found.
6.Check the operation of the burner by following the lighting instructions on the front of the water heater. With the burner lit, check the gas control valve/thermostat supply line, manifold tube connections for leaks.
7.Verify proper operation and then replace the outer door.
TEFLON?? is a registered trademark of E.I. Du Pont De Nemours and Company
32
TROUBLESHOOTING GUIDE
Start Up Conditions
NOTE: Expansion tanks are
Thermal Expansioncharge. If the inlet water pressure is higher than 40 psi, the expansion tank???s air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.
As water is heated, it expands (thermal expansion). In a closed system, the volume of water will grow. As the volume of water grows, there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent
A properly sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Thermal expansion tanks are available from Sears stores and through the Sears Service Centers. Contact the local plumbing inspector, water supplier and/or the Sears Service Center for assistance in controlling these situations. See Figure 41.
Thermal Expansion Tank Specifications
TABLE 6
Expansion Tank Sizing Chart
TABLE 7
*Highest recorded inlet water pressure in a 24 hour period or regulated water pressure.
FIGURE 41.
Strange Sounds
Possible noises due to expansion and contraction of some metal parts during periods of
Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal. See ???Condensation??? section.
Draft Hood Operation
Check draft hood operation by performing a worst case depressurization of the building. With all doors and windows closed, and with all air handling equipment and exhaust fans operating such as furnaces, clothes dryers, range hoods and bathroom fans, a match flame should still be drawn into the draft hood of the water heater with its burner firing. If the flame is not
drawn toward the draft hood, shut off water heater and make necessary air supply changes to correct.
33
Condensation
Whenever the water heater is filled with cold water, some condensate will form while the burner is on. A water heater may appear to be leaking when in fact the water is condensation. This usually happens when:
???A new water heater is filled with cold water for the first time.
???Burning gas produces water vapor In water heaters, particularly high efficiency models where flue temperatures are lower.
???Large amounts of hot water are used in a short time and the refill water in the tank is very cold.
Moisture from the products of combustion condense on the cooler tank surfaces and form drops of water which may fall onto the burner or other hot surfaces to produce a ???sizzling??? or ???frying??? noise.
Because of the suddenness and amount of water, condensation water may be diagnosed as a ???tank leak???. After the water in the tank warms up (about
Do not assume the water heater is leaking until there has been enough time for the water in the tank to warm up.
An undersized water heater will cause more condensation. The water heater must be sized properly to meet the family???s
demands for hot water including dishwashers, washing machines and shower heads.
Excessive condensation may be noticed during the winter and early spring months when incoming water temperatures are at their lowest.
Good venting is essential for a gas fired water heater to operate properly as well as to carry away products of combustion and water vapor.
Smoke Odor
It is not uncommon to experience a small amount of smoke and odor during the initial
Operational Conditions
???AIR??? In Hot Water Faucets
HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely ???ammable and explosive. To prevent the possibility of injury under these conditions, we recommend the hot water faucet, located farthest away, be opened for several minutes before any electrical appliances which are connected to the hot water system are used (such as a dishwasher or washing machine). If hydrogen gas is present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking or open ???ame near the faucet at the time it is open.
Do not remove the anode, leaving the tank unprotected. By doing so, all warranty on the water heater tank is voided.
Safety
This water heater is designed to automatically
1.The burner flame is extinguished for any reason.
2.The water temperature exceeds 195??F (91??C).
3.Excessive build up of dust on the louvers of the air intake chamber. See Maintenance of your Water Heater Section.
This unit is also equipped with a flammable vapor sensor (FV Sensor), designed to shut off the gas supply in the event the water heater has been exposed to flammable vapors (e.g., spilled gasoline). NOTE: If the
A high temperature limit switch or ECO (Energy Cut Off) in the tank is used to shut off the unit if the water temperature exceeds 195??F (91??C). The ECO is a
Service
Before calling for repair service, please read the Troubleshooting Guide in this manual. If a condition persists or you are uncertain about the operation of the water heater, let the Sears Service Center check it out. Contact Sears Service
34
Leakage Checkpoints
B.*Condensation may be seen on pipes in humid weather or pipe connections may be leaking.
C.*The anode rod fitting may be leaking.
D.Small amounts of water from
E.*The
F.Water from a drain valve may be due to the valve being slightly opened.
G.*The drain valve may be leaking at the tank fitting.
H.Combustion products contain water vapor which can condense on the cooler surfaces of the tank. Droplets form and drip onto the burner or run on the floor. This is common at the time of
I.Water in the water heater bottom or on the floor may be from condensation, loose connections, or the relief valve. DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken.
Leakage from other appliances, water lines, or ground seepage should also be checked.
*To check where threaded portion enters tank, insert cotton swab between jacket opening and fitting. If cotton is wet, follow draining instructions in the ???Draining and Flushing??? section and then remove fitting. Put pipe dope or teflon tape on the threads and replace. When you are finished, follow the steps in ???Filling the Water Heater??? in the Installation Instructions earlier in this manual.
Teflon?? is a registered trademark of E.I. Du Pont De Numours and Company.
Read this manual first. Then, before checking the water heater, make sure the gas supply has been turned ???OFF???, and never turn the gas ???ON??? before the tank is completely full of water.
Never use this water heater unless it is completely filled with water. To prevent damage to the tank, the tank must be filled with water. Water must flow from the hot water faucet before turning ???ON??? gas to the water heater.
A.Water at the draft hood is water vapor which has condensed out of the combustion products. This is caused by a problem in the vent. Contact a qualified technician.
35
Pressurized Combustion Chamber System
Operational Checklist
1.Manifold gasket properly sealed.
2.Viewport not damaged or cracked.
3.Combustion chamber free of debris and undamaged.
4.Manifold component block properly installed.
5.No leaks at manifold connection.
6.Manifold door screws securely tightened.
TROUBLESHOOTING CHART
36
continued:
37
ELECTRONIC CONTROL DISPLAY TROUBLESHOOTING
ELECTRONIC CONTROL DISPLAY
Please check guidelines below. For your safety, water heater service should be performed only by a qualified service person. Read the GENERAL SAFETY INFORMATION supplied by the water heater manufacturer.
38
39
40
TROUBLESHOOTING FLOWCHART
APPLY POWER TO
APPLIANCE
41
PARTS ORDER LIST
Now that you have purchased your gas water heater, should a need ever exist for repair parts or service, simply contact any Sears Service Center or call
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE
FOLLOWING INFORMATION:
THIS IS A REPAIR PARTS LIST, NOT A PACKING LIST.
42
NOTES
43
Get it fixed, at your home or ours!
Your Home
For troubleshooting, product manuals and expert advice:
www.managemylife.com
For repair ??? in your home ??? of all major brand appliances, lawn and garden equipment, or heating and cooling systems, no matter who made it, no matter who sold it!
For the replacement parts, accessories and owner???s manuals that you need to
For Sears professional installation of home appliances and items like garage door openers and water heaters.
Call anytime, day or night (U.S.A. and Canada)
www.sears.com www.sears.ca
Our Home
For repair of
Sears Parts & Repair Service Center
To purchase a protection agreement on a product serviced by Sears:
Para pedir servicio de reparaci??n a domicilio, y para ordenar piezas:
Au Canada pour service en fran??ais:
??Registered Trademark / TM Trademark of KCD IP, LLC in the United States, or Sears Brands, LLC in other countries
??Marca Registrada / TM Marca de F??brica de KCD IP, LLC en Estados Unidos, o Sears Brands, LLC in otros pa??ses MC Marque de commerce / MD Marque d??pos??e de Sears Brands, LLC