GP Series
Portable Generator
Owner???s
Manual
???SAFETY
???ASSEMBLY
???OPERATION
???TROUBLESHOOTING
???WARRANTY
COMMERCIAL ??? INDUSTRIAL ??? RESIDENTIAL
MODELS:
AUTHORIZED DEALER SUPPORT:
www.generac.com or
Table of Contents
INTRODUCTION
Thank you for purchasing this model by Generac Power Systems, Inc.?? This model is a compact, high performance,
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest Authorized Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
DANGER
After this heading, read instructions that, if not strictly complied with, will result in serious personal injury, including death and/or property damage.
After this heading, read instructions that, if not strictly complied with, may result in serious personal injury and/or property damage.
After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows:
???This symbol points out important safety information that, if not followed, could endanger personal safety and/or property of others.
???This symbol points out potential explosion hazard.
???
???This symbol points out potential electrical shock hazard.
The operator is responsible for proper and safe use of the equipment. We strongly recommend that the operator read this manual and thoroughly understand all instructions before using the equipment.
We also strongly recommend instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
DANGER
???Using a generator indoors WILL KILL YOU IN MINUTES. Exhaust contains carbon monoxide, a poison gas you cannot see or smell.
???NEVER use in the home, or in partly enclosed areas such as garages. ONLY use outdoors and far from open windows, doors, vents, and in an area that will not accumulate deadly exhaust gas.
???Always disconnect the spark plug wire and place the wire where they cannot contact the spark plug to prevent accidental starting when setting up, transporting, adjusting or making repairs to the generator.
???The generator produces dangerously high voltage that can cause extremely hazardous electrical shock. Avoid contact with bare wires, terminals, etc. Never permit any unqualified person to operate or service the generator.
??? Never handle any kind of electrical cord or device while standing in water, while barefoot or while hands or feet are wet. Dangerous electrical shock will result.
???The National Electric Code requires the frame and external electrically conductive parts of the generator be properly connected to an approved earth ground. Local electrical codes may also require proper grounding of the generator. Consult with a local electrician for grounding requirements in the area.
???Do not use worn, bare, frayed or otherwise damaged electrical cord sets with the generator.
???Operate generator only on level surfaces and where it will not be exposed to excessive moisture, dirt, dust or corrosive vapors.
???Gasoline is highly FLAMMABLE and its vapors are EXPLOSIVE. Do not permit smoking, open flames, sparks or heat in the vicinity while handling gasoline. Avoid spilling gasoline on a hot engine. Comply with all laws regulating storage and handling of gasoline.
???Never add fuel while unit is running. Allow unit to cool entirely before adding fuel.
???Do not overfill the fuel tank. Always allow room for fuel expansion. If tank is
???Never store generator with fuel in tank where gasoline vapors might reach an open flame, spark or pilot light (as on a furnace, water heater or clothes dryer). FIRE or EXPLOSION may result.
???Generator exhaust gases contain DEADLY carbon monoxide gas. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. Operate this equipment only in the open air where adequate ventilation is available.
1
IMPORTANT SAFETY INSTRUCTIONS
???SAVE THESE INSTRUCTIONS ??? The manufacturer suggests that these rules for safe operation be copied and posted near the unit's installation site. Safety should be stressed to all operators and potential operators of this equipment.
???Never start or stop the unit with electrical loads connected to receptacles AND with connected devices turned ON. Start the engine and let it stabilize before connecting electrical loads. Disconnect all electrical loads before shutting down the generator.
???Do not insert objects through unit's cooling slots.
???Never operate generator: Indoors or in any enclosed compartment; in rain; if connected electrical devices overheat; if electrical output is lost; if engine or generator sparks; if flames or smoke are observed while unit is running; if unit vibrates excessively.
NOTE:
This generator is equipped with a spark arrestor muffler. The spark arrestor must be maintained in effective working order by the owner/ operator. In the State of California, a spark arrestor is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner???s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
WARNING:
The engine exhaust from this product contains chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not
DANGER
???Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
???Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
???Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
??????GENERAL HAZARDS ???
???Never operate in an enclosed area or indoors.
???For safety reasons, the manufacturer recommends that the maintenance of this equipment is carried out by an Authorized Dealer.
???The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust system must be properly maintained. Do nothing that might render the exhaust system unsafe or in noncompliance with any local codes and/or standards.
???Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
???Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be operated outdoors.
???When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
???Inspect the generator regularly, and contact the nearest Authorized Dealer for parts needing repair or replacement.
???Before performing any maintenance on the generator, disconnect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or
???Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
2
IMPORTANT SAFETY INSTRUCTIONS
??? ELECTRICAL HAZARDS ???
???All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages as does the generator when it is in operation. Avoid contact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
???Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL
SHOCK MAY RESULT.
???The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground. Local electrical codes also may require proper grounding of the generator electrical system.
???In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a
???Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.
??? EXPLOSION HAZARDS ???
???Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
???Gasoline is extremely EXPLOSIVE.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws, the published information listed below may be used as a guideline for operation of this equipment. Always reference the latest revision available for the standards listed.
1.NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC CODE.
2.Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
3.AGRICULTURAL WIRING HANDBOOK, available from the Food and Energy Council, 909 University Avenue, Columbia, MO 65201.
4.ASAE
5.NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.
??? FIRE HAZARDS ???
???For fire safety, the generator must be operated and maintained properly. Operation must always comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is operated in accordance with the manufacturer???s instructions and recommendations. Do not alter the construction of the generator or change controls which might create an unsafe operating condition.
???Keep a fire extinguisher near the generator at all times. Extinguishers rated ???ABC??? by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extinguisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.
???Avoid spilling gasoline on a hot engine. NEVER add fuel while the unit is running. Allow unit/engine to cool entirely before adding fuel. DO NOT overfill the fuel tank. Always allow room for fuel expansion. NEVER fill fuel tank indoors.
3
Section 1 ??? General Information
1.1UNPACKING
???Set the palleted carton on a rigid flat surface.
???Remove staples along bottom of carton that fasten carton to pallet. Open carton from top.
???Remove all packaging material.
???Remove separate accessory box.
???Lift carton off the generator.
???Remove generator from shipping pallet by removing bolts through the shipping brackets (Figure 1).
Figure 1 - Bracket Removal
Shipping
Bracket (x4)
1.1.1 ACCESSORY BOX
Check all contents. If any parts are missing or damaged locate an authorized dealer at
4
1.2ASSEMBLY
The generator requires some assembly prior to using it. If problems arise when assembling the generator, please call the Generator Helpline at
1.2.1 ASSEMBLING THE WHEEL KIT
The wheel kit is designed to greatly improve the portability of the generator. A socket wrench with a 9/16??? socket, a 1/2??? socket, a 1/2??? wrench and a pair of pliers are the tools that will be needed for assembly of the wheel kit.
NOTE:
The wheel kit is not intended for
???Refer to Figure 2 and install the wheel kit as follows:
???Place the generator on a hard flat surface.
???Stand at the engine end of the unit and gently tilt the generator forward, high enough to place wooden blocks beneath the cradle. This will allow space to install the wheel assemblies.
???Attach an axle bracket assembly with attached sleeve to either side of the frame. Ensure the sleeve faces outward.
???Slide the axle through the sleeves on the axle brackets.
???Slide one wheel with flat washer to the outside and a spacer to the inside onto each end of the axle. Make sure the air inflation valve on the wheel is facing outward.
???Insert retaining pins and using pliers, bend out the ends to prevent the pins from falling out of the axle. Remove the wooden blocks.
1.2.2 ASSEMBLING THE HANDLE
???Attach the handle by aligning one side of the handle on the cradle, then spread the handle around the cradle and let it spring into place. Secure the handle to the frame using the 5/16??? hex head bolts provided. Check each fastener to ensure that it is secure.
???Using the handle, lift the unit high enough to place wooden blocks under the unit. Attach the front support foot to the underside of the cradle using the 3/8??? carriage bolts provided.
???Remove the shipping brackets from the cradle, if it has not already been done.
Section 1 - General Information
Figure 2 - Handle Assembly
1.2.3 BATTERY CONNECTION
???The battery shipped with the generator has been provided fully charged. Caution must be taken when connecting the battery.
NOTE:
A battery may lose some of it???s charge when not in use for prolonged periods of time.
???Cut the tie wrap cable holding the RED and BLACK battery cables to the stator.
???Connect the RED battery cable to the battery Positive terminal (+). After making sure that the connection is tight, slip the rubber boot over the terminal connection.
???Connect the BLACK battery cable to the battery Negative terminal
???Double check all connections to ensure they are in the correct location and secure. See Figure 3.
Figure 3 - Battery Connections
55
Section 2 ??? Operation
2.1KNOW THE GENERATOR
Figure 5 - Generator Controls
Read the Owner???s Manual and Safety Rules before operating this generator.
Compare the generator to Figures 4 through 6 to become familiarized with the locations of various controls and adjustments. Save this manual for future reference.
Figure 4 - Control Panel
1.12 Volt DC, 10 Amp Receptacle ??? This receptacle allows the capability to recharge a 12 volt DC storage battery with provided battery charge cables.
2.120 Volt AC, 20 Amp, Duplex Receptacle ??? Supplies electrical power for the operation of 120 Volt AC, 20 Amp,
3.120 Volt AC, 20A Duplex GFCI Receptacle ??? Supplies ground fault protected electrical power for operation of 120 volt AC 20 amp,
4.120 Volt AC, 30 Amp Locking Receptacle ??? Supplies electrical power for the operation of 120 Volt AC, 30 Amp,
5.120/240 Volt AC, 30 Amp Locking Receptacle ??? Supplies electrical power for the operation of 120 and/or 240 Volt AC, 30 Amp, single- phase, 60 Hz, electrical lighting, appliance, tool and motor loads.
6.120/240 Volt AC, 50 Amp Receptacle (17.5kW, Located on underside of control panel)??? Supplies electrical power for the operation of 120/240 Volt AC, 50 Amp,
7.Air Cleaner ??? Filters intake air as it is drawn into the engine.
8.Choke Knob ??? Used when starting a cold engine.
9.Winter/Summer Valve ??? See ???Cold Weather
10.Circuit Breakers (AC) ??? Each receptacle is provided with a push-
11
7
11.Fuel Tank ??? Tank holds 16 U.S. gallons of fuel.
12.Grounding Lug ??? Ground the generator to an approved earth ground here. See "Grounding the Generator" for details.
13.Idle Control Switch ??? The idle control runs the engine at normal (high) speeds when there is an electrical load present and runs the engine at idle (low) speeds when a load is not present.
14.Start/Run/Stop Switch ??? Controls the operation of the generator.
15.Oil Fill ??? Use this point to add oil to engine.
16.Fuse - 10 Amp (Located at rear of control panel) ??? Protects the DC control circuit from overload. If this fuse element has melted open the engine will not be able to crank and start.
17. Hourmeter - Tracks hours of operation.
Figure 6 - Engine Control Panel
6
Section 2 ??? Operation
2.2HOURMETER
The Hourmeter tracks hours of operation for scheduled maintenance:
There will be a one time break in "CHG OIL" message that flashes with the elapsed time in hours and tenths after the first 30 hours of operation.
This message will actually begin flashing at 29 hours and disable itself at 31 hours providing a two hour window to perform the service.
There will be a subsequent "CHG OIL" message every 100 hours. The message will flash one hour before and one hour after each 100 hour interval, again providing a two hour window to perform service.
Every 200 hours the "SVC" icon on the lower left hand corner of the display will flash. The message will flash one hour before and one hour after each 200 hour interval providing a two hour window to perform service.
When the hour meter is in the Flash Alert mode, the maintenance message will always alternate with elapsed time in hours and tenths. The hours will flash four times, then alternate with the maintenance message four times until the meter resets itself.
???30 hours - CHG OIL ???
???100 hours - CHG OIL ??? Oil Change Interval (Every 100 hrs)
???200 hours - SVC ??? Air Filter Interval (Every 200 hrs)
2.3CORD SETS AND CONNECTION
PLUGS
2.3.1 120 VAC, 20 AMP, DUPLEX RECEPTACLE
This is a 120 Volt outlet protected against overload by a 20 Amp push-
Keep extension cords as short as possible, preferably less than 15 feet long, to prevent voltage drop and possible overheating of wires.
Figure 7 - 120 Volt AC, 20 Amp, Duplex Receptacle
2.3.2 120 VAC, 20 AMP, GFCI RECEPTACLE
This unit is equipped with a ground fault circuit interrupter (GFCI). This device meets applicable federal, state and local codes (Figure 8).
A GFCI receptacle is different from conventional receptacles. In the event of a ground fault, a GFCI will trip and quickly stop the flow of electricity to prevent serious injury.
Definition: Instead of following its normal safe path, electricity passes through a persons body to reach the ground. For example, a defective appliance can cause a ground fault.
A GFCI receptacle does NOT protect against circuit overloads, short circuits, or shocks. For example, electric shock can still occur if a person touches charged electrical wires while standing on a
Figure 8 - 120 VAC, 20 Amp GFCI Receptacle
Testing the GFCI: Test the GFCI outlet every month as follows:
???Plug a test lamp into the receptacle.
???Start the generator, the test lamp should be on.
???Press the ???Test??? button located on the front of the receptacle to trip the device.
???This should stop the flow of electricity making the lamp shut off. The yellow trip indicator should now be on.
???To restore the flow of electricity, press the ???Reset??? button on the front of the receptacle. If the GFCI does not perform in this manner, do not use the receptacle. Contact a local service dealer.
???This outlet is protected against overload by a 20A
77
Section 2 ??? Operation
Use a NEMA
Figure 9 - 120 VAC, 30 Amp Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps. The outlet is protected by a 30 Amp
2.3.4 120/240 VAC, 30 AMP RECEPTACLE
Use a NEMA
Figure 10 - 120/240 VAC, 30 Amp Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps or 240 Volt AC, 60 Hz, single phase loads requiring up to 7200 watts (7.2 kW) of power at 30 Amps. The outlet is protected by two 30 Amp
2.3.5 12 VOLT DC, 10 AMP RECEPTACLE
This receptacle permits recharging a
2.3.6 120/240 VAC, 50 AMP RECEPTACLE
Use a NEMA
Figure 12 - 120/240 VAC, 50 Amp Receptacle
50 A
Use this receptacle to operate 120/240 Volt AC, 60 Hz electrical loads requiring up to 12,000 watts (12.0 kW) of power. This receptacle is protected by a 50 Amp
2.4HOW TO USE THE GENERATOR
If there are any problems operating the generator, please call the generator helpline at
2.4.1 GROUNDING THE GENERATOR
The National Electrical Code requires that the frame and external electrically conductive parts of this generator be properly connected to an approved earth ground (Figure 13). Local electrical codes may also require proper grounding of the unit. For that purpose, generally, connecting a No. 10 AWG (American Wire Gauge) stranded copper wire to the grounding wing nut and to an
8
Section 2 ??? Operation
The Wattage Reference Guide is provided to assist in determining how many items the generator can operate at one time.
Generator Ground Lug
Proper grounding of the generator will help prevent electrical shock in the event of a ground fault condition in the generator or in connected electrical devices. Proper grounding also helps dissipate static electricity, which often builds up in ungrounded devices.
2.4.2 CONNECTING ELECTRICAL LOADS
DO NOT connect 240 Volt loads to 120 Volt receptacles. DO NOT connect
???Let engine stabilize and warm up for a few minutes after starting.
???Plug in and turn on the desired 120 or 240 Volt AC, single phase, 60 Hz electrical loads.
???Add up the rated watts (or amps) of all loads to be connected at one time. This total should not be greater than (a) the rated wattage/ amperage capacity of the generator or (b) circuit breaker rating of the receptacle supplying the power. See "Don't Overload the Generator" below.
2.5DON???T OVERLOAD THE
GENERATOR
Overloading a generator in excess of its rated wattage capacity can result in damage to the generator and to connected electrical devices. Observe the following to prevent overloading the unit:
???Add up the total wattage of all electrical devices to be connected at one time. This total should NOT be greater than the generator's wattage capacity.
???The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances and motors can usually be found on a data label or decal affixed to the device.
???If the appliance, tool or motor does not give wattage, multiply volts times ampere rating to determine watts (volts x amps = watts).
???Some electric motors, such as induction types, require about three times more watts of power for starting than for running. This surge of power lasts only a few seconds when starting such motors. Make sure to allow for high starting wattage when selecting electrical devices to connect to the generator:
NOTE:
All figures are approximate. See data label on appliance for wattage requirements.
2.6WATTAGE REFERENCE GUIDE
Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Running Watts
*Air Conditioner (12,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . . 1700 *Air Conditioner (24,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . . 3800 *Air Conditioner (40,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . . 6000 Battery Charger (20 Amp). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500 Belt Sander (3") . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000 Chain Saw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200 Circular Saw
99
Section 2 ??? Operation
*Table Saw (10") . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1750 to 2000 Television . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200 to 500 Toaster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1000 to 1650 Weed Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500 * Allow 3 times the listed watts for starting these devices.
2.7BEFORE STARTING THE
GENERATOR
Prior to operating the generator, engine oil and gasoline will need to be added, as follows:
2.7.1 ADDING ENGINE OIL
All oil should meet minimum American Petroleum Institute (API) Service Class SJ, SL or better. Use no special additives. Select the oil's viscosity grade according to the expected operating temperature (also see chart).
???Above 40?? F, use SAE 30
???Below 40?? F and down to 10?? F, use
???Below 10?? F, use synthetic
???Any attempt to crank or start the engine before it has been properly serviced with the recommended oil may result in an engine failure.
???Place generator on a level surface.
???Clean area around oil fill and remove oil fill cap and dipstick.
???Wipe dipstick clean.
???Slowly fill engine with oil through the oil fill opening until it reaches the full mark. Stop filling occasionally to check oil level. (Engine oil is full when level is up to the threads of the oil fill plug.) Do not overfill.
???Install oil fill cap and finger tighten securely.
???Check engine oil level before starting each time thereafter.
2.7.2 ADDING GASOLINE
???Never fill fuel tank indoors. Never fill fuel tank when engine is running or hot. Allow unit/engine to cool entirely before adding fuel. DO NOT light a cigarette or smoke when filling the fuel tank.
10
???Do not overfill the fuel tank. Always leave room for fuel expansion.
???To reduce lead and carbon deposits use high quality UNLEADED gasoline with the generator engine. Leaded REGULAR grade gasoline is an acceptable substitute. Do not use premium gasoline. Do not mix oil with gasoline.
???Clean area around fuel fill cap, remove cap.
???Slowly add unleaded regular gasoline to fuel tank. Be careful not to overfill. Allow about 1/2" of tank space for fuel expansion, as shown in Figure 14.
???Install fuel cap and wipe up any spilled gasoline.
Figure 14 - Fuel Tank
IMPORTANT: It is important to prevent gum deposits from forming in fuel system parts such as the carburetor, fuel hose or tank during storage.
???The manufacturer does not recommend using any gasoline containing alcohol (such as ???gasohol???). If using any gasoline containing alcohol, it must not contain more than 10 percent ethanol, and it must be removed from the generator during storage. Do NOT use any gasoline containing methanol. If using gasoline with alcohol, inspect more frequently for fuel leaks and other abnormalities.
2.8TO START THE ENGINE
???Never start or stop engine with electrical devices plugged into the receptacles AND devices turned on.
???Unplug all electrical loads from the unit's receptacles before starting the engine.
???Make sure the unit is in a level position.
Section 2 ??? Operation
??? Open the fuel
Figure 15 - Fuel
???To start engine, press and hold the Start/Run/Stop switch in the ???Start??? position. The engine will crank and attempt to start. When the engine starts, release the switch to the run position.
???When the engine starts, move choke knob to ???1/2 Choke??? position until the engine runs smoothly and then fully in to the ???Run??? position. If engine falters, move choke knob back out to ???1/2 Choke??? position until the engine runs smoothly and then to ???Run??? position.
NOTE:
???Locate the Idle Control ON/OFF switch on the control panel and set it to the ???OFF??? position (Figure 16).
Figure 16 - Idle Control Switch
???Move engine CHOKE knob outward to ???Full Choke??? position (Figure 17).
Figure 17 - Full Choke Position
If engine fires, but does not continue to run, move choke lever to ???Full Choke??? and repeat starting instructions.
IMPORTANT: Do not overload the generator. Also, do not overload individual panel receptacles. These outlets are protected against overload with
2.9STOPPING THE ENGINE
???Shut off all loads, then unplug the electrical loads from generator panel receptacles. Never start or stop the engine with electrical devices plugged in and turned on.
???Turn ???Off??? the Idle Control switch (if on).
???Let engine run at
???Move Start/Run/Stop switch to ???Off??? position.
???Close fuel valve.
2.10 AUTOMATIC IDLE CONTROL
This feature is designed to greatly improve fuel economy. When this switch is turned ???On,??? the engine will only run at its normal fast governed engine speed when electrical load is connected. When the load is removed, the engine will run at a reduced speed of 2100 RPM. With the switch ???Off,??? the engine runs at the normal fast engine speed all the time. Always have the switch OFF when starting and stopping the engine.
2.11 COLD WEATHER OPERATION/
Under certain weather conditions (temperatures below 40?? F (4?? C) and a high dew point), the engine may experience icing of the carburetor and/or the crankcase breather system. To eliminate this problem, this generator engine is fitted with a winter/summer valve. This directs hot air into the carburetor during cold weather operation. Always make sure the winter/summer valve is in the correct location relative to the weather conditions.
2.12 LOW OIL PRESSURE
SHUTDOWN SYSTEM
The engine is equipped with a low oil pressure sensor that shuts down the engine automatically when the oil pressure drops below 10 psi. If the engine shuts down by itself and the fuel tank has enough gasoline, check engine oil level.
1111
Section 3 ??? Maintenance
If the system senses low oil pressure during operation, the engine shuts down.
2.12.3 RESTARTING
If trying to restart the engine within 10 seconds after it shuts down, the engine may NOT start. The system needs five (5) to 10 seconds to reset.
If the engine is restarted after such a shutdown and the low oil pressure has not been corrected, the engine will run for about 10 seconds as described above and then stop.
NOTE:
Use an automotive hydrometer to test battery state of charge and condition. Follow the hydrometer manufacturer's instructions carefully. Generally, a battery is considered to be at 100% state of charge when specific gravity of its fluid (as measured by hydrometer) is 1.260 or higher.
3.1MAINTENANCE SCHEDULE
Follow the calendar intervals. More frequent service is required when operating in adverse conditions noted below.
2.13 CHARGING A BATTERY
DANGER
???Storage batteries give off explosive hydrogen gas while recharging. An explosive mixture will remain around the battery for a long time after it has been charged. The slightest spark can ignite the hydrogen and cause an explosion. Such an explosion can shatter the battery and cause blindness or other serious injury.
DANGER
???Do not permit smoking, open flame, sparks or any other source of heat around a battery. Wear protective goggles, rubber apron and rubber gloves when working around a battery. Battery electrolyte fluid is an extremely caustic sulfuric acid solution that can cause severe burns. If spill occurs flush area with clear water immediately.
This generator has the capability of recharging a discharged 12 Volt automotive or utility style storage battery. Do not use the unit to charge any 6 Volt batteries. Do not use the unit to crank an engine having a discharged battery.
This battery charger is a pulse type designed to provide a quality charge current into the battery. The voltage measured at the outlet should be
To recharge 12 Volt batteries, proceed as follows:
???Check fluid level in all battery cells. If necessary, add ONLY distilled water to cover separators in battery cells. Do not use tap water.
???If the battery is equipped with vent caps, make sure they are installed and are tight.
???If necessary, clean battery terminals.
???Connect battery charge cable connector plug to panel receptacle identified by the words
??? Change oil after first 30 hours of operation then every season.
*Change oil and oil filter every month when operating under heavy load or in high temperatures.
**Clean more often under dirty or dusty operating conditions. Replace air filter parts if they cannot be adequately cleaned.
***Check valve clearance and adjust if necessary after first 50 hours of operation and every 100 hours thereafter.
3.2PRODUCT SPECIFICATIONS
3.2.1 GENERATOR SPECIFICATIONS
12
Section 3 ??? Maintenance
3.2.2 ENGINE SPECIFICATIONS
3.3.2 TO CLEAN THE GENERATOR
???Use a damp cloth to wipe exterior surfaces clean.
???A soft, bristle brush may be used to loosen caked on dirt, oil, etc.
???A vacuum cleaner may be used to pick up loose dirt and debris.
???Low pressure air (not to exceed 25 psi) may be used to blow away dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
3.3.3 ENGINE MAINTENANCE
DANGER
???When working on the generator, always disconnect negative cable from battery. Also disconnect spark plug wires from spark plugs and keep wire away from spark plugs.
3.3GENERAL RECOMMENDATIONS
The warranty of the generator does not cover items that have been subjected to operator abuse or negligence. To receive full value from the warranty, the operator must maintain the generator as instructed in this manual.
Some adjustments will need to be made periodically to properly maintain the generator.
All adjustments in the Maintenance section of this manual should be made at least once each season. Follow the requirements in the "Maintenance Schedule" chart.
NOTE:
Once a year, replace the spark plug and replace the air filter. A new spark plug and clean air filter assure proper
3.3.1 GENERATOR MAINTENANCE
Generator maintenance consists of keeping the unit clean and dry. Operate and store the unit in a clean dry environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air slots in the generator must not become clogged with snow, leaves, or any other foreign material.
Check the cleanliness of the generator frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior surface.
???Never insert any object or tool through the air cooling slots, even if the engine is not running.
NOTE:
DO NOT use a garden hose to clean generator. Water can enter the engine fuel system and cause problems. In addition, if water enters the generator through cooling air slots, some water will be retained in voids and crevices of the rotor and stator winding insulation. Water and dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings.
3.3.4 CHECKING OIL LEVEL
See the ???BEFORE STARTING THE GENERATOR??? section for information on checking the oil level. The oil level should be checked before each use, or at least every eight hours of operation. Keep the oil level maintained.
???Hot oil may cause burns. Allow engine to cool before draining oil. Avoid prolonged or repeated skin exposure with used oil. Thoroughly wash exposed areas with soap.
3.3.5 CHANGING THE OIL AND OIL FILTER
Change the oil and filter after the first 30 hours of operation. Change the oil every 100 hours thereafter. If running this unit under dirty or dusty conditions, or in extremely hot weather, change the oil more often.
NOTE:
Whenever possible, run engine for approximately five (5) minutes to get the engine oil hot. This will aid in draining the oil.
Use the following instructions to change the oil while the engine is still warm:
???Clean area around oil drain hose and plug.
???Remove oil drain plug from end of hose and oil fill plug to drain oil completely into a suitable container.
???When oil has completely drained, install oil drain plug and tighten securely.
???Place a suitable container beneath the oil filter and turn filter counterclockwise to remove. Discard according to local regulations.
???Coat gasket of new filter with clean engine oil. Turn filter clockwise until gasket contacts lightly with filter adapter. Then tighten an additional 3/4 turn.
???Fill oil sump with recommended oil. (See ???Before Starting the Generator??? for oil recommendations).
???Wipe up any spilled oil.
???Dispose of used oil at a proper collection center.
13
13
Section 3 ??? Maintenance
3.3.6 REPLACING THE SPARK PLUGS
Use Champion RC14YC spark plug or equivalent. The correct air gap is 1.01 mm (0.040 in.). Replace the plugs once each year. This will help the engine start easier and run better.
1.Stop the engine and pull the spark plug wire off of the spark plug.
2.Clean the area around the spark plug and remove it from the cylinder head.
3.Set the spark plug's gap to 1.01 mm (0.040 in.). Install the correctly gapped spark plug into the cylinder head.
Figure 18 - Spark Plug Gap
3.4SERVICE AIR CLEANER
The engine will not run properly and may be damaged if using a dirty air cleaner. Clean or replace the air cleaner paper filter every 200 hours. Clean or replace more often if operating under dusty conditions. Clean foam pre- cleaner every month or more often under dusty conditions.
Figure 19 - Air Cleaner
Cover
Base
Filter
To clean or replace foam
???Remove air cleaner cover, then foam
???Wash
???Clean air cleaner cover before
14
To clean or replace paper air filter:
???Remove air cleaner cover; then remove foam
???Clean paper filter by tapping it gently on a solid surface. If the filter is too dirty, replace it with a new one. Dispose of the old filter properly.
???Clean air cleaner cover then slip
NOTE:
To order a new air filter, please contact the nearest authorized service center at
3.5CLEAN SPARK ARRESTOR
SCREEN
The engine exhaust muffler has a spark arrestor screen. Inspect and clean the screen at least once each year (Figure 20). If unit is used regularly, inspect and clean more often.
NOTE:
If using the generator on any
Clean and inspect the spark arrestor as follows:
???Remove the screen retaining bracket by removing the screw.
???Slide the spark arrestor screen out from the tail pipe.
???Inspect screen and replace if torn, perforated or otherwise damaged. DO NOT USE a defective screen. If screen is not damaged, clean it with commercial solvent.
???Replace the screen and the retaining bracket.
Figure 20 - Spark Arrestor
Section 3 ??? Maintenance
3.6ADJUSTING VALVE CLEARANCE
After the first 50 hours of operation, check the valve clearance in the engine and adjust if necessary.
Important: If feeling uncomfortable about doing this procedure or the proper tools are not available, please take the generator to the nearest service center to have the valve clearance adjusted. This is a very important step to insure longest life for the engine.
To check valve clearance:
???Make sure the engine is at room temperature (60?? - 80?? F).
???Make sure that the spark plug wire is removed from the spark plug and out of the way.
???Remove the four screws attaching the valve cover.
???Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, remove the intake screen at the front of the engine to gain access to the flywheel nut. Use a large socket and socket wrench to rotate the nut and hence the engine in a clockwise direction while watching the piston through the spark plug hole. The piston should move up and down. The piston is at TDC when it is up as high as it can go.
???Insert a 0.002 - 0.004 inch (0.05 - 0.1mm) feeler gauge between the rocker arm and valve stem. Correct clearance is when a slight drag is felt when sliding the gauge back and forth. If the clearance is either excessively loose or tight the rocker arms will need adjusting.
To adjust valve clearance:
???Loosen the rocker jam nut (Figure 21). Use an 10mm allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge. Correct clearance is
Figure 21 - Valve Clearance Adjustment
NOTE:
The rocker arm jam nut must be held in place as the pivot ball stud is turned.
When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change.
???Install new valve cover gasket.
???
NOTE:
Start all four screws before tightening or it will not be possible to get all the screws in place. Make sure the valve cover gasket is in place.
???
???Repeat the process for the other cylinder.
3.7GENERAL
The generator should be started at least once every seven days and be allowed to run at least 30 minutes. If this cannot be done and the unit must be stored for more than 30 days, use the following information as a guide to prepare it for storage.
DANGER
???NEVER store engine with fuel in tank indoors or in enclosed, poorly ventilated areas where fumes may reach an open flame, spark or pilot light as on a furnace, water heater, clothes dryer or other gas appliance.
3.8LONG TERM STORAGE
It is important to prevent gum deposits from forming in essential fuel system parts such as the carburetor, fuel hose or tank during storage. Also, experience indicates that
To avoid engine problems, the fuel system should be emptied before storage of 30 days or longer, as follows:
??? Remove all gasoline from the fuel tank.
DANGER
??????Drain fuel into approved container outdoors, away from open flame. Be sure engine is cool. Do not smoke.
???Start and run engine until engine stops from lack of fuel.
???While engine is still warm, drain oil from crankcase. Refill with recommended grade.
???Remove spark plugs and pour about 1/2 ounce (15 ml) of engine oil into the cylinders. Cover spark plug hole with rag. Press the ???Start??? button and allow engine to crank for 2 seconds. Then press the ???Stop??? button.
1515
Section 3 ??? Maintenance
???Avoid spray from spark plug holes when cranking engine.
???Install and tighten spark plugs. Do not connect spark plug wires.
???Clean the generator outer surfaces. Check that cooling air slots and openings on generator are open and unobstructed.
???Store the unit in a clean, dry place.
16
3.9OTHER STORAGE TIPS
???Do not store gasoline from one season to another.
???Replace the gasoline can if it starts to rust. Rust and/or dirt in the gasoline will cause problems with the carburetor and fuel system.
???If possible, store the unit indoors and cover it to give protection from dust and dirt. BE SURE TO EMPTY THE FUEL TANK.
???If it is not practical to empty the fuel tank and the unit is to be stored for some time, use a commercially available fuel stabilizer added to the gasoline to increase the life of the gasoline.
???Cover the unit with a suitable protective cover that does not retain moisture.
DANGER
???NEVER cover the generator while engine and/or exhaust area are warm.
Section 4 ??? Troubleshooting
4.1TROUBLESHOOTING GUIDE
1717
Section 5 ??? Warranty
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission Control System warranty on your new engine. In California, new
Your emission control system may include parts such as the carburetor, ignition system, exhaust system and crankcase ventilation system. Generac will repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER???S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 2001 and later model year LSI engines are warranted for two years as hereinafter noted. If, during such warranty period any
PURCHASER'S/OWNER'S WARRANTY RESPONSIBILITIES:
As the engine owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner's Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect, improper maintenance or unapproved modifications, or the use of counterfeit and/or "grey market" parts not made, supplied or approved by Generac.
You are responsible for contacting a Generac Authorized Warranty Dealer as soon as a problem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Dealer. To locate the Generac Authorized Warranty Service Dealer nearest you, call our toll free number:
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the "Generac Limited Warranties for Generac Power Systems, Inc.," which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty service, evidence must be presented showing the date of the sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at one of the following addresses:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 297 ??? WHITEWATER, WI 53190
Part 1
18
Section 5 ??? Warranty
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS warranty) for 2001 and later model year LSI engines:
(a)Applicability: This warranty shall apply to 2001 and later model year engines. The ECS Warranty period shall begin on the date the new engine or equipment is purchased by/delivered to its original,
(b)General Emissions Warranty Coverage: Generac warrants to the original,
(1)Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its authority, and
(2)Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a warranted emissions- related part to fail to be identical in all material respects to the part as described in the engine manufacturer's application for certification.
The ECS Warranty pertains only to
(1)Any warranted,
(2)Any warranted,
(3)Any warranted,
(4)Repair or replacement of any warranted,
(5)When the engine is inspected by a Generac Authorized Warranty Service Facility, the purchaser/owner shall not be held responsible for diagnostic costs if the repair is deemed warrantable.
(6)Generac shall be liable for damages to other original engine components caused by a failure under warranty of any
(7)Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted
(8)Any Generac authorized and approved
(9)Unapproved,
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
1.2) LPG/Natural Gas carburetion assembly and its internal components.
a)Fuel controller (if so equipped)
b)Mixer and its gaskets (if so equipped)
c)Carburetor and its gaskets (if so equipped)
d)Primary gas regulator (if so equipped)
e)LP liquid vaporizer (if so equipped)
2) Air Induction System including:
a)Intake pipe/manifold
b)Air cleaner
3)Ignition System including: a) Spark plug
b) Ignition module
4)Catalytic Muffler Assembly (if so equipped) including: a) Muffler gasket
b) Exhaust manifold
5)Crankcase Breather Assembly including:
a) Breather connection tube
* Generac engine types covered by this warranty statement include the following:
1)Prepackaged Standby Generator
2)Auxiliary Power Unit (APU) Generator
3)Portable Generator
19
Section 5 ??? Warranty
GENERAC POWER SYSTEMS ???TWO YEAR??? LIMITED WARRANTY FOR
GP SERIES PORTABLE GENERATORS
For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) warrants its GP Series generators will be free from defects in materials and workmanship for the items and period set forth below. Generac will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective. Any equipment that the purchaser/owner claims to be defective must be returned to and examined by the nearest Generac Authorized Warranty Service Dealer. All transportation costs under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies only to Generac GP Series portable generators and is not transferable from original purchaser. Save your
WARRANTY SCHEDULE
Consumer applications are warranted for two (2) years. Commercial and Rental applications are warranted for one (1) year or 1000 hours maximum, whichever comes first.
CONSUMER APPLICATION
YEARS ONE and TWO - 100% (one hundred percent) coverage on Labor and Part(s) listed (proof of purchase and maintenance is required):
???Engine- All Components
???Alternator- All Components
COMMERCIAL/RENTAL APPLICATION
YEAR ONE ??? 100% (one hundred percent) coverage on Labor and Part(s) listed (proof of purchase and maintenance is required):
???Engine- All Components
???Alternator- All Components
NOTE: For the purpose of this warranty ???consumer use??? means personal residential household or recreational use by original purchaser. This warranty does not apply to units used for Prime Power in place of utility where utility power service is present or where utility power service does not normally exist. Once a generator has experienced commercial or rental use, it shall thereafter be considered a
All warranty expense allowances are subject to the conditions defined in Generac???s Warranty Policies, Procedures and Flat Rate Manual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
???Generac built portable generators built prior to May 2008.
???Generac portable generators that utilize
???Costs of normal maintenance and adjustments.
???Failures caused by any contaminated fuels, oils or lack of proper oil levels.
???Repairs or diagnostics performed by individuals other than Guardian/Generac authorized dealers not authorized in writing by Generac Power Systems.
???Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper use. As with all mechanical devices, the Generac engines need periodic part(s) service and replacement to perform as designed. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine.
???Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning,
???Damage related to rodent and/or insect infestation.
???Products that are modified or altered in a manner not authorized by Generac in writing.
???Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).
???Failure due to misapplication.
???Telephone, cellular phone, facsimile, internet access or other communication expenses.
???Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.
???Expenses related to ???customer instruction??? or troubleshooting where no manufacturing defect is found.
???Rental equipment used while warranty repairs are being performed.
???Overnight freight or special shipping costs for replacement part(s).
???Overtime, holiday or emergency labor.
???Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. GENERAC???S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC???S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you. This warranty gives you specific legal rights. You also have other rights from state to state.
GENERAC POWER SYSTEMS, INC.
P.O. BOX 8 ??? Waukesha, WI 53187
Ph: (888) GENERAC
To locate the nearest Authorized Dealer visit our website www.generac.com