Fire alarm systems
Enclosed heat detectors 6295, 6296, 6297 and 6298
???Fixed temperature alarm level
??? ATEX compliance
???Waterproof (IP67)
Fixed temperature alarm level
The detectors are conventional fixed temperature heat detectors, i.e. they will give an alarm within a response temperature range in accordance with
The sensing element is a heat
An LED on the detector (not on 6298) will light up when the detector goes into alarm. The detector also has an output for an external LED 2216 / 2217.
The following types are available (static response temperature, class &
6295, 57??C, class A2 S (54 to 70??C). 6296, 72??C, class B S (69 to 85??C). 6297, 87??C, class C S (84 to 100??C). 6298, 117??C, class E S (114 to 130??C).
Latching
The detectors are latching, i.e. they will not be automatically reset if the temperature, after the alarm, falls below the detector's static response temperature. The detector's LED and a connected ext. LED will be lit until the detector is reset via the c.i.e.
ATEX classification
The detectors 6295 and 6296 complies with the ATEX classification Ex II 3GD EEx nA II T5. See also the opposite side of this page.
Waterproof connection box
The heat
Label holder
A label holder intended for a label showing "zone number", can be mounted in the connection box.
Miscellaneous
The detectors
Product applications
The detectors can be used in the systems EBL500 / 512 / 128 / 1000 / 2000 provided with some zone line inputs for the system respectively (e.g. an 8 zones expansion board 1580 / 4580 input, an addressable zone interface 2226 / 2335 input, an addressable multi purpose I/O unit 3361 input, etc.).
Heat detectors are normally used in rooms where the temperature can be expected to rise rapidly in case of a fire or places where smoke detectors can not be used.
The detectors are intended for outdoor use or indoor use in high humidity premises.
Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12,
Tel: +46 (0)40 697 70 00 ??? Fax: +46 (0)40 697 70 99
Detector mounting holes, 2x(4x7 mm) c/c = 70 mm. E+/E- = Ext. LED. A/B = zone line in/out (or
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.