Fire alarm systems
Analog multi detector 4300
???Constant sensitivity / Service signal at a fixed level of contamination
???New advanced algorithms and functions and yet compatible with older EBL systems
General
The multi detector contains one photo- electric (optical) smoke detector and one heat detector within the low profile housing. The latest IC technology will secure the highest reliability possible. It has unleaded soldering. In the smoke detection chamber is a
The heat sensing element is a thermistor. The detector is supplied with two LEDs that will light when the detector goes into alarm. The detector is plugged in the analog base 3312x / 4313. The COM loop is connected to the base, which also has terminals for an external LED, e.g. 2218. The detector is intended for indoor use in dry premises and in the systems EBL512 / 128 / 1000 / 2000 depending on the detector mode.
Constant sensitivity
The detector maintains a constant sensitivity regardless of its contamination. A service signal will be given when the detector has reached a service level.
Address / Detector mode
The address setting tool 3314 is used to set the detector's COM loop address and the detector mode NORMAL, 2330 or 2312. See Planning Instructions for the system respectively for more information about the modes and functions.
???NORMAL mode (analog): Detector 4300 is used in the systems EBL512 (SW version > 2.0) and EBL128, also as a spare part for the detector 3316 in NORMAL mode.
???2330 mode (conventional): Detector
4300 is used in the systems EBL512 /
1000 / 2000 as the best substitute for the detectors 2316 & 2317 + base 2330.
???2312 mode (analog): Not used for 4300.
The different modes have different functions and features, e.g. in the 2330 mode, the detector does the fire judgement but in the NORMAL mode this is done in the c.i.e. The detector is prepared for an "Advanced mode" to be used in conjunction with future EBLxxx SW versions.
AI function
In the 2330 mode is the AI function used, i.e.:
???Combined heat and smoke sensing will guarantee reliable and accurate fire alarm detection.
???Variable delay function, i.e. the delay time before an alarm is influenced by temporary temperature and/or smoke obscuration changes.
Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12,
Tel: +46 (0)40 697 70 00 ??? Fax: +46 (0)40 697 70 99
Type number
The detector is plugged in the analog base 3312x / 4313. The COM loop / Ext. LED are connected to the analog base.
Prepared for mechanical locking with analog base 3312x / 4313. One hexagon socket screw (Ls) is attached (1.5 mm Hex key to be used). The
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.