g
GE
SG Series 10, 20, 30 and 40 kVA
OPERATING MANUAL
UNINTERRUPTIBLE POWER SUPPLY
Digital Energy TM
SG Series
10 ??? 20 ??? 30 ??? 40 kVA Series 0
g
GE
COPYRIGHT ?? 2003 by GE
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
g
GE
Dear Customer,
We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE.
We trust that the use of the SG Series Uninterruptible Power Supply system, developed and produced to the highest standards of quality, will give you complete satisfaction.
Please carefully read the Installation Guide. It contains all the necessary information about the installation of the UPS.
Thank you for choosing GE !
START UP AND COMMISSIONING
A GE Global Services Field Engineer must perform
g
GE
GE DIGITAL ENERGY SA
6595 Riazzino (Locarno)
Switzerland
g
Preface
GE
Congratulations on your choice of a SG Series Uninterruptible Power Supply (UPS). It will help eliminate Load disturbances due to unexpected power problems.
This Manual describes the function of the UPS module, the purpose and location of the switches, the meaning of the system events related to the front panel indication, and provides procedures for starting and stopping the equipment.
Please refer to the accompanying Installations Guide, which describes how to prepare the installation site, and it provides weight, dimensions and procedures for moving, installing and connecting the UPS.
While every care has been taken to ensure the completeness and accuracy of this manual, GE assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.
WARNING!
SG Series 10, 20, 30 and 40 kVA, is a product that needs to be installed by a licensed and knowledgeable contractor.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please contact your Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE.
Some of the information contained in this manual may be changed without notice to reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the installation of the UPS, options and Battery System.
Pay attention to the rectangular boxes included in the text:
They contain important information and warning concerning electrical connections and personnel safety.
Parallel version secured with RPA
When included in the text, this symbol refers to operation needed only for parallel system.
g
Table of contents
GE
Page
g
GE
g
GE
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models SG Series 50 and 80 kVA that should be followed during installation and maintenance of the UPS and battery.
GENERAL
-Move the UPS in an upright position in its original package to the final destination room. To lift the cabinets, use a forklift or lifting belts with spreader bars.
-Check for sufficient floor and elevator loading capacity.
-Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS. Contact the nearest Service Center immediately.
-WARNING! RISK OF ELECTRICAL SHOCK: Do not remove covers; there are no user serviceable parts inside.
-All maintenance and service work should be performed by qualified service personnel. The UPS contains its own energy source (battery).
-The
-Dangerous voltages may be present during battery operation.
The battery must be disconnected during maintenance or service work.
-This UPS contains potentially hazardous voltages.
-Be aware that the inverter can restart automatically after the utility voltage is restored.
INSTALLATION
-This UPS must be installed and connected only by trained personnel.
-Verify accurately during Commissioning and Maintenance of the UPS, for the following: Damaged components, squeezed wires and cables, or not correctly inserted plugs.
-After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are correctly reattached
-This UPS is intended for use in a controlled indoor environment free of conductive contaminants and protected against animals intrusion.
-HIGH GROUND LEAKAGE CURRENT: Ground connection is essential before connecting to AC input!
-Switching OFF the unit does not isolate the UPS from the utility.
-Do not install the UPS in an excessively humid environment or near water.
-Avoid spilling liquids on or dropping any foreign object into the UPS.
-The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104??F (40??C).
-Optimal battery life is obtained if the ambient temperature does not exceed 77??F (25??C).
-It is important that air can move freely around and through the unit. Do not block the air vents.
-Avoid locations in direct sunlight or near heat sources.
STORAGE
-Store the UPS in a dry location; storage temperature must be within
-If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time depending on storage temperature).
BATTERY
-The
-When replacing the battery, use the same number, voltage (V) and capacity (Ah).
-Proper disposal or recycling of the battery is required. Refer to your local codes for disposal requirements.
-Never dispose of battery in a fire: They may explode.
-Do not open or mutilate battery: Their contents (electrolyte) may be extremely toxic. If exposed to electrolyte, wash immediately with plenty of water.
-Avoid charging in a sealed container.
-Never short circuit battery.
When working with battery, remove watches, rings or other metal objects, and only use insulated tools.
g
GE
Safety instructions when working with battery
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE
UPS BY QUALIFIED SERVICE PERSONNEL.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION AND
REFER TO THE BATTERY MANUFACTURERS INSTALLATION MANUAL
BEFORE HANDLING THE UPS AND BATTERY.
UPS INTENDED TO BE USED WITH A REMOTE BATTERY SUPPLY ??? ALL MODELS:
???PLEASE REFER TO THE BATTERY MANUFACTURER???S INSTALLATION MANUAL FOR
BATTERY INSTALLATION AND MAINTENANCE INSTRUCTIONS???.
DANGER!
Full voltage and current are always present at the Battery Terminals.
The Battery used in this system can provide dangerous voltages, extremely high currents and a risk of electric shock.
They may cause severe injury if the terminals are shorted together or to ground.
You must be extremely careful to avoid electric shock and burns caused by contacting Battery Terminals or shorting terminals during battery installation.
Do not touch
A qualified service person that is familiar with Battery systems and required precautions must install and service the Battery.
The installation must conform to national and local codes. Keep unauthorized personnel away from Battery.
The qualified service person must take these precautions:
1Wear protective clothing, such as rubber gloves and boots and protective eye wear. Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated. Remove rings and metal wristwatches or other metal objects and jewelry.
Do not carry metal objects in your pockets where the objects can fall into the Battery Cabinet.
2Tools must have insulated handles and must be insulated so that they will not short Battery Terminals.
Do not allow a tool to short between individual or separate Battery Terminals or to the cabinet or rack.
Do not lay tools or metal parts on top of the Battery, and do not lay them where they could fall onto the Battery or into the cabinet.
3Install the Battery as shown on the drawing provided with the Battery.
When connecting cables, never allow a cable to short across a Battery???s Terminals, the string of batteries, or to the cabinet or rack.
4Align the cables on the Battery Terminals so that the cable lug will not contact any part of the cabinet or rack, even if the Battery is moved.
Keep the cable away from any sharp metal edges.
5Install the Battery Cables so the UPS or Battery Cabinet Doors cannot pinch them.
6Do not connect the Battery Terminal to Ground.
If any Battery Terminal is inadvertently grounded, remove the source of the ground. Contacting any part of a grounded Battery can cause a risk of electric shock.
7To reduce the risk of fire or electric shock, install the Battery in a temperature and humidity controlled indoor area, free of contaminants.
8Battery System Chassis Ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduit, this ground conductor must be routed in the same conduit as the Battery Conductors.
9Where conductors may be exposed to physical damage, protect the conductors in accordance with all applicable codes.
10If you are replacing Battery or repairing Battery Connections, shut OFF the UPS and remove the
Battery Fuses or open the Battery System disconnect.
g
GE
Safety symbols and warnings
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to the UPS system and the supplied critical loads.
The
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
WARNING, if instruction is not followed injury or serious equipment damage may occur!
CAUTION, internal parts have dangerous voltage present.
Risk of electric shock!
PE (Earth) ??? GND (Ground)
PROTECTIVE GROUNDING TERMINAL:
A terminal which must be connected to earth ground prior to making any other connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or supplied.
This symbol indicated the word ???phase???.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.
g
2 INTRODUCTION
GE
An Uninterruptible Power Supply (UPS) provides the power for critical loads that need a reliable, continuous, disturbance free supply.
In case the power provided by the Utility Fails, or exceeds the permitted tolerances, the power to supply the Load is provided by the Battery for the specified time at the rated Load (or longer at a reduced Load) or until the Utility power returns.
SG Series is a true double conversion
In case of trouble on the Inverter Output Voltage, or when overload or
The UPS automatically returns to normal mode when the failure condition is restored.
Key features:
???More Critical equipment supported
Rated at 0.8 Power Factor, SG Series delivers more real power than other UPS in the market.
With today???s trend toward power factor corrected loads, SG Series can support more total Load than any other UPS available, allowing you to support a greater number of today???s enterprise computing Power Factor Corrected (PFC) equipment.
???No single point of failure
Redundant Parallel Architecture (RPA) is an exclusive GE technology.
With RPA, SG Series UPS are controlled in a true
SG Series is designed to be the most reliable power protection system available on the market today.
???High Efficiency
Using IGBT technology and Space Vector Modulation (SVM) strategy, SG Series offers low output voltage distortion and provides efficiencies up to 93%.
???Fully digital
Digital Signal Processor (DSP), Flash memory and SVM strategy, are the technology corner stones of new age of power quality and power reliability.
???Extremely flexible
Tailor made power protection to meet your individual installation requirements; SG Series offers various options like input harmonic filters and our comprehensive JUMP software suite for mission control and data protection to cover all your application needs.
g
3 DESCRIPTION
GE
3.1BLOCK DIAGRAM AND MAIN ELEMENTS
processing circuits. The interface between the operator and the unit is provided by the monitoring system on the front panel.
This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.
RectifierThe standard Rectifier consists of a
This regulated
InverterThe Inverter converts the DC voltage into a
Automatic Bypass The Automatic Bypass consists of a static
Inverter to Utility.
This protection works automatically by opening contactor K6 and K8 (in series with the thyristors of the static switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong manipulations on the Manual Bypass Q2.
Manual Bypass The Manual Bypass consists of a pair of manual switches (Q1 and Q2), which removes the UPS from the Load for maintenance, while still supplying the Load with power directly from the Utility.
BatteryThe Battery supplies the DC power to the Inverter when the Utility is out of accepted tolerances.
g
GE
3.2OPERATION MODES
3.2.1 Normal operation mode
During normal operation, the Rectifier converts input AC power to DC.
The DC power provides input power for the Inverter and charging power for the Battery. The Inverter converts the DC power to continuous and regulated AC power, which supplies the critical load.
The control panel reports the Battery charge status and the expected backup time with the actual load.
3.2.2 Utility failure operation
When the Utility is no longer within acceptable tolerances, the Battery will provide the DC power to the Inverter.
The Inverter will maintain continuous AC power to the Load until the Battery Voltage reaches the lower limit of the Inverter operation capability.
During the discharge, the LCD screen displays the estimated time the Battery can support the critical load.
Prior to the Battery completely discharging, the "stop operation" alarm (shutdown imminent) warns the operator that the Battery is almost discharged and the UPS is about to shut down.
Fig.
Fig.
In case of parallel operation
With a parallel system for power capacity (see Section 3.3)
???With the Bypass Utility power available, a low Battery warning on any unit will cause the Load to be transferred to Utility (after a selectable time delay).
???With Bypass Utility power not available, a low Battery warning on any unit will start the ???stop operation??? timer (adjustable).
The Load will shut down at the end of the ???stop operation??? time period.
With a parallel system for redundancy (see Section 3.3)
???When a Battery low warning occurs on a unit not necessary to support the present load, this unit will shut down after a timeout period (selectable).
The Load is shared between the other units
???As the warning occurs on one unit necessary to support the present load, the system starts the "stop operation" timeout (selectable).
The Load will shut down at the end of the ???stop operation??? time period.
g
GE
3.2.3Utility recovery operation
As soon as the AC input power recovers, the
Rectifier will start automatically, supplying DC power to the Inverter and recharging the Battery.
If the Inverter was previously shut down due to low Battery, the Load will be initially powered by Utility through the Automatic Bypass.
When the Battery is recharged enough to ensure a minimum time of operation with the present load, the Inverter will start automatically and the Load will be transferred back to the Inverter.
Fig.
In case of parallel operation
When the AC input power recovers, the Rectifiers will start up sequentially, according to their number in the parallel system. This minimizes the initial inrush current.
The Inverters will start up automatically, but only when the Battery has recharged enough for a minimum runtime with the present load.
When enough Inverters to supply the Load have been restarted, the Load will be transferred from the Automatic Bypass back to the Inverter output.
3.2.4 Automatic Bypass
In normal operation, the Load is supplied by the
Inverter.
When the control system detects a fault in the Inverter, an overload condition or a
When the Inverter recovers, or the overload or
If the UPS is unable to return to normal mode following an automatic transfer to Bypass mode, an alarm condition will be initiated.
A Manual Bypass (operator initiated) will not be considered as an alarm condition.
FIG.
BYPASS
In case of parallel operation
Each unit has it???s own internal Bypass. These units are continuously exchanging information, enabling all of the internal Bypass circuits in a parallel system to operate simultaneously.
If the Inverter of a unit fails, it???s Bypass circuit remains available to the parallel system.
It is excluded only if the unit is separated from the common bus by opening it???s output switch Q1.
3.2.5Manual Bypass
The Manual Bypass circuit consists of Q1 and Q2 manual switches, which permits transfer of the Load directly to the unconditioned AC power without interruption, leaving the UPS available for maintenance.
Fig.
g
GE
3.3PARALLEL SYSTEM OPERATION
3.3.1 Introduction to the parallel system
Two or more equal power units can be paralleled to increase the output power (paralleling for capacity) or to improve the overall reliability of an UPS system (paralleling for redundancy). The outputs of parallel units are connected to a common power bus, and in normal operation the units connected on the parallel bus share the Load equally.
The modular concept of SG Series allows parallel operation of up to 8 units, without using paralleling switchgear, external bypass circuits or common control circuitry (see Fig.
Parallel units for power capacity
Several units can be paralleled in order to achieve output power greater than the maximum power of a single unit.
The maximum total power shared between the paralleled units is equal to the total installed nominal power.
In the event of a failure of one unit, the power supplied by the UPS system becomes insufficient and the Load will be transferred to the Utility Bypass source.
Parallel units for redundancy
The nominal power rating of the n+1 out of n redundant paralleled modules must be equal to or greater than the required Load power.
The Load will be equally shared by the n units connected on the output bus.
Should one of the n paralleled units trip
From this results higher reliability and security for the Load plus a higher MTBF (Mean Time Between Failures).
Fig.
g
GE
3.3.2 Features of RPA parallel system
The SG Series parallel system is designed to provide a complete Redundant Parallel Architecture, and is free from common equipment.
Not only the Inverters are redundant, but also the Bypass functions are designed with redundant modular concept.
When one UPS needs maintenance or service, the Load is powered by the other units supplying the Load bus.
The redundant communication bus to which all units are connected keeps each unit informed about the status of all the other units.
The control panel located on each unit allows controlling and monitoring the status of this unit.
3.3.3 System control
A
Each module controls it's own function and operational status and communicates with all other modules, in order to act or react if necessary, adapting it to the new conditions.
3.3.4 Synchronization
All units are identical, but one unit is arbitrarily selected as the reference and all the other units synchronize to this unit, which in turn, synchronizes to the Utility Bypass voltage, as long as the later is within tolerances.
In case of reference failure, another unit in the parallel system is automatically chosen to take over the reference role.
The Bypass Input for all the units of the parallel system must be supplied from the same AC source (no phase shift allowed between them).
3.3.5 Load sharing
On each unit of the parallel system, Inverter Output Voltage and Current are measured and applied to a Load sharing bus.
An eventual difference between the units is therefore automatically equalized.
It is strongly recommended that no transformers, automatic circuit breakers or fuses should be inserted between the unit???s output and the Load common bus bars.
However, it is recommended that a disconnect or isolation switch be inserted.
g
GE
3.4RECTIFIERS PARALLELED ON THE SAME BATTERY
A parallel system with a Common Battery for two or more Rectifiers, requires a particular installation and adequate setting of some parameters, (accessible only through password), and can therefore only be done by a qualified engineer from GE.
Usually each
In case of parallel units are running with a Common Battery (max. 4 UPS - see Fig
1 ??? Rectifier
2 ??? Inverter
3 ??? Automatic Bypass
4 ??? Manual Bypass
5 ??? Mains Power
6 ??? Load Bus Bar
7 ??? External Battery Fuse
8 ??? Battery
Fig.
Pay attention to the following recommendations:
???The units delivered for this functioning mode needs a special parameters setting, so they must be prepared in advance before the installation.
???The installation must be performed only with the UPS system must be completely shut down.
???The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each unit.
???Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation.
???It is recommended to install the fuses / MCB (7) on each line connecting the Rectifiers to the common Battery for maintenance / safety reasons.
???In case one must be powered down for maintenance,
???It is recommended to connect an external NO free contact ???Battery Fuses??? to the UPS and to enable the function by setting the parameter (see Section 7.1).
???If an emergency generator set supply the UPS, and the free contact ???Generator ON??? is connected to the Customer interface, connect a separate NO free contact on each parallel unit.
???The parameters enabling the Battery test, both manual and automatic, must be set in the same mode on all the units having the Rectifiers on Common Battery.
???Do not connect the temperature sensor for automatic battery floating voltage compensation.
???Do not enable the function Boost charge (parameter 87).
g
GE
3.5RECYCLING AT THE END OF SERVICE LIFE
NOTE!
This product has been designed to respect the environment, using materials and components respecting
It does not contain CFCs (Carbon Fluor Clorid) or HCFCs (Halogen Carbon Fluor Clorid).
Packing material recycling
GE, in compliance with environment protection, uses only environmentally friendly material.
UPS packing materials must be recycled in compliance with all applicable regulations.
WARNING!
Leads contained in the batteries is a dangerous substance for the environment, therefore it must be correctly recycled by specialized companies!
g
GE
4LAYOUT
4.1LAYOUT SG Series 10 AND 20 KVA
Fig.
Fig.
Fig.
P4 Customer Interface Board
Q1 UPS output switch
Q2 Manual Bypass switch
SNMP SNMP Card (option)
XA Terminals for 24VDC Auxiliary Power Supply connection
XB Terminals for EPO (Emergency Power Off) connection
g
GE
4.2LAYOUT SG Series 30 AND 40 KVA
Q1 Q2
Fig.
Fig.
g
5 CONTROL PANEL
GE
5.1CONTROL PANEL
Fig.
5.2TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL
inverter on/off
Key to switch the Inverter ON.
(This key is also used to reset ???total off??? if pressed simultaneously with total off push button).
inverter on/off
Key for Inverter shutdown.
Press key to transfers the Load to Utility.
Keep pressed for 5 seconds to shutdown the Inverter.
This key is also used as the EPO (Emergency Power Off) reset.
mute
Key to reset general alarm and buzzer.
The
By pressing it, you immediately separate the UPS from utility and the Load.
Attention: ???total off??? cannot disconnect the UPS from the Load with Q2 closed.
To reset ???total off???: push and hold the ???total off???
For parallel system, pressing ???total off??? on one unit connected on parallel bus (switch Q1 closed), all the units are separated from the load.
The ???total off??? reset must be done only on one unit connected on the parallel bus (switch Q1 closed).
Special care must be taken in using this command, in order to avoid accidental Load disconnection.
g
GE
alarm
service check
General alarm condition.
It blinks when one or more alarm is activated. The internal buzzer is ON. The LED remains lighted (with alarm condition still present) and the buzzer stops as the key ???mute??? has been pressed.
LED ON indicates that a regular maintenance service is needed. May be reset by a service technician only.
(See chapter 10 ??? Maintenance)
THE LED IS ON ALSO WHEN THE OUTPUT SWITCH Q1 IS OPEN,
INDICATING THAT THE INVERTER IS IN SERVICE MODE, NOT
SUPPLYING THE LOAD.
a) LED ON indicates that the Battery reserve lasts for only 3 more minutes (selectable).
b)LED ON in case of over temperature or overload >125% together with missing Utility.
After the timeout the Inverter will shut down.
All LED???s ON indicate that the Battery is fully charged.
LED???s ON indicate the Load status of the UPS.
Fig.
Fig.
(??? 100 % load) (100% load) (66% load) (33% load)
Definition of the LED???s on mimic diagram
User LCD Interface
Consist of a LCD screen, 4 lines with 20 characters each and six keys. It offers:
???UPS operating, AC and DC metering information.
???History of alarms and events.
???Functionality can be programmed to meet customer needs by changing parameters.
g
6 LCD SCREEN
GE
The user interface consists of a back lit LCD screen having:
???4 lines with 20 characters (standard version for Latin characters). And
???6 keys (the function is described for each operating mode).
The operation is extremely simple and is structured on three important main menus related to the UPS operation, as follows:
metering A UPS must offer some metering information for the user to be able to examine the operating status at any time.
alarms In the event of Utility failures or abnormal functioning, the UPS must keep a history of what has happened as a series of events.
parameters The user must be able to program certain functions of the UPS (user parameters, accessible without password) to his needs.
LCD screen standard version
The 3 buttons existing on the left side of the screen are used to activate the operating modes, while the buttons on the right side are used to carry out functions inside these operating modes.
g
GE
6.1METERING MODE
The metering mode is entered any time the metering button is pressed.
While in this mode the LCD will display a series of screens containing metering information. In this mode the buttons perform the following functions:
Main screen
This screen displays the current status of the UPS in a condensed form.
The information offered by this screen consists of:
???The type of the machine: Family name, series number (P + unit number for parallel version from 1 to 8) and power range.
???The status of the load.
???The Load amount as a percentage of the nominal Load (referred to the most loaded phase).
???The estimated Battery backup time in minutes with the present load.
Battery data screen
This screen displays:
???The Battery voltage.
???The Battery Current (negative values correspond to the discharge of the Battery).
???The temperature of the Battery (XXX indicates sensor disabled).
???The current charge level.
???The estimated backup time with the present load.
Bypass Utility data screen
This screen refers to the AC source supplying the Bypass. This screen displays:
???The frequency.
???The voltage levels of the three phase voltages.
g
GE
Rectifier Utility data screen
This screen refers to the AC source supplying the Rectifier.
This screen displays:
???Iout1 = output current Rectifier Bridge.
???Iout2 = output current 2nd Rectifier Bridge (optional 12 pulse Rectifiers only).
???The voltage levels between the three phases
???The input frequency of the Rectifier.
Inverter data screen
This screen displays:
???The voltage level of the three phase voltages
???The output frequency of the Inverter.
???The synchronization status of the Inverter with respect to Utility.
Status Load screen
This screen displays:
???The Load level in kVA (for RPA: only this unit).
???The Load level as a percentage of the nominal rated Load (for RPA: only this unit).
???The source of the power supplied to the Load.
Load on phases screen 1
This screen displays for each phase:
???The output phase voltage and current as RMS values (for RPA: total value of Parallel System).
???The output Load as percent (for RPA: respect to the rated power of Parallel System).
metering
alarms parameters
LOAD ON PHASES U1=277V I=30A 84% U2=277V I=26A 73% U3=277V I=27A 76%
+
???
ok
g
GE
Load on phases screen 2
This screen displays for each phase:
???The Load active power (kW) (for RPA: total value of Parallel System).
???The Load apparent power (kVA) (for RPA: total value of Parallel System).
Miscellaneous screen
This screen displays:
???The temperature of the Inverter Bridge.
???The total operating time for the UPS (in hours).
???The total operating time for the Inverter (in hours).
Utility Faults Statistics screen
This screen displays:
???The total number of minor Utility faults (Bypass Utility out of tolerance faults).
???The total number of major Utility faults (Rectifier Utility out of tolerance faults).
???The total number of detected output overloads.
UPS identification screen
This screen displays:
???The UPS family and the power range.
???The software version.
???The serial number.
g
GE
6.2ALARMS
The alarms mode is entered any time the alarms button is pressed.
The LCD will display a series of screens corresponding to the last 256 events, one event per screen.
The buttons perform the following functions:
The events displayed are the standard GE events as described in the Section 6.7 - EVENTS (Alarms and Messages).
The information displayed includes:
???The exact date and time when the event occurred.
???The number of the event, 255 being the most recent event, and 0 the oldest.
???The standard GE code for the event and the machine status word.
???An explicit text description of the event.
The initial screen of this mode is the one showing the most recent event.
g
GE
6.3PARAMETERS
The parameters mode is entered any time the parameters button is pressed.
The LCD will display a series of screens containing the user parameters, accessible without password protection.
The buttons perform the following functions:
During parameters mode there is no means to perform scroll back on the display.
Example of operation within parameters mode:
Purpose: to correct a wrong telephone number previously stored in Tel2.
1 ??? entering parameters mode (parameters). The first screen is displayed.
2 ??? scroll to the next screen (+). The second screen is displayed.
3 ??? scroll to the next screen (+). The third screen is displayed.
4 ??? move the selection (underscore cursor) to the next parameter in this page
5 ??? move the selection to the next parameter in page
6 ??? enter Edit mode for the currently selected parameter (ok).
1
2
g
3
4
5
6
GE
g
GE
6.4EDIT MODE
The EDIT MODE is entered from the parameters mode when the ok button is pressed. During this mode the LCD will display a special editing screen for the parameter being edited.
The screen contents during Edit mode is:
???On the first line of the screen it is clearly indicated the special operating mode.
???On the second line you will find the name of the parameter being edited.
???On the third line is displayed the current value of the parameter.
???The fourth line contains a condensed help text.
During the Edit mode the buttons perform the following functions:
Examples of operation during Edit mode
There are three types of parameters having differences in behavior during Edit mode. Depending the type of parameters, there are different ways to select and to change the needed values.
Type 1: Parameters having a large range of values (numeric value).
As continuation of the previous example, the telephone number stored in ???Tel2??? must be changed:
1 ??? move the selection (block cursor) to the next character. 2 ??? move the selection to the next character (+).
3??? change the selected character
4??? change the selected character
5??? press ok: the screen will return to parameters mode saving the new value.
1
2
g
3
4
5
GE
Type 2: Parameters having a limited range of values.
For example the parameter Printer Baud Rate has the range {600, 1200, 2400, 4800 and 9600}.
There is no need to edit this parameter digit by digit.
By pressing the
1 ??? enter Edit mode for Printer Baud Rate, initial value = 1200. 2 ??? change to 2400.
3 ??? change to 4800.
4 ??? press ok: the screen will return to parameters mode saving the new value.
1
2
g
3
4
GE
Type 3: Boolean parameters used to simulate command buttons.
The Boolean parameters have a range of Yes/No.
Only the user performs the modification of the value.
These ???Type 3??? parameters are used to initiate an action. There are two possibilities:
A1 ??? the user wants the UPS to start the action => the user sets the parameter to ???Yes???. 2 ??? the UPS finishes the action => the UPS sets the parameter to ???No???.
B1 ??? the user wants the UPS to start the action => the user sets the parameter to ???Yes???. 2 ??? the user wants to abort the action => the user sets the parameter to ???No???.
The actions that can be performed using such software buttons are:
???Print the metering information.
???Print the last 256 events.
???Print the values of the parameters.
???Print all the information obtainable from the UPS.
Returning from the Edit mode
Normally ok button is used to return from the Edit mode.
Then the UPS will perform some validity tests on the new value.
If these tests are successful then the new value is saved and used.
If these tests fail the Edit mode is not exited.
The validity tests performed by the UPS are not exhaustive. You should not rely exclusively on these tests.
Care should be taken when modifying the values of the parameters.
For all parameters except the LCD Contrast parameter the new value is saved and used after the ok button was pressed.
In the case of the LCD Contrast parameter the new value is used immediately in order to obtain a better visual feedback.
g
GE
6.5USER PARAMETERS
Pressing the Parameters button displays a series of screens containing the user parameters on the LCD panel.
This first parameter level in not protected by password, therefore the user can freely adapt these parameters to their needs.
The meaning of the user parameters and their use is described below (buttons performance is described to Section 6.3).
1.Date and Time
Time You can adjust the time of the real time clock existing in the UPS by means of this parameter.
The value you enter is thoroughly checked to be a correct time in the format ???hh.mm.ss???. The time is specified in
2.Protocol
Modem enabled You can enable/disable with Y/N the remote control through modem calls
g
GE
3.Telephone numbers
The telephone number has a maximum 39 characters and cannot contain blanks.
If the desired number is shorter than 39 characters, the string will finish with blanks.
4.LCD Display
UPS Name The user can choose the name of the UPS model shown on the main page (max. 7 characters).
LCD Contrast This parameter controls the contrast of the LCD screen in ten steps. It can be adapted depending on the room lighting.
LCD Language This parameter allows the choice of language used to display the information.
Valid choices are English, German, Italian, Spanish, French, Finnish, Tschech, Slovak, Polish and Portuguese.
g
GE
5.Printer
The UPS is capable of communicating to a serial printer, to printout disparate information. Please be sure to have a serial printer, that is a printer with a serial RS232 interface. This is the only
metering
alarms parameters
PRINTER SETUP
Baud=2400 Parity=O
Bits=8 Handshake=XON
Print All = N
+
???
ok
Please configure your printer with the following parameters: 2400/8/N (2400 bits/sec, 8 bits, no parity).
6.Printer commands
metering
alarms parameters
PRINTER COMMANDS
+
???
ok
Print Measures This Y/N parameter is used to print only the measurement data.
Print Alarms This Y/N parameter is used to print only the sequence of all
Alarms/Events.
Print Parameters This Y/N parameter is used to print only the list of User and Service
Parameters
After each printing command the corresponding parameter will be set again to N.
g
GE
6.6EVENTS (ALARMS AND MESSAGES)
Each of the following listed events can be displayed on the LCD screen or on PC where the
ARGUS/JumpManager - Control Network is installed.
Alarms and Messages are differently specified because the alarms are indicating an abnormal functioning of the UPS (which are additionally signaled with the LED alarm and acoustically with the buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list, but no activating the LED alarm and the buzzer).
When in the alarms mode, the LCD screen displays a time ordered sequence of screens corresponding to the last 256 alarms and messages, each screen indicating:
The number of the event (255 = the most recent). The date and time when the event occurred.
The standard code and the status word. An explicit text description of the events.
6.6.1Alarms list
g
GE
g
GE
g
GE
g
GE
6.6.2Messages list
g
GE
g
GE
6.6.3Event report SG Series
In case of failure or malfunctioning, before calling the nearest Service Center, please note the most important data of your UPS and the most recent events.
In order to make the diagnosis easier from our Diagnostic Center we suggest you make a copy of this page, fill it out with the requested data and send it by fax.
1.Record the exact UPS status on the panel 2. On the LCD panel, enter the alarms mode and
BATTERY _______ minutes
Description of repair actions taken:
....................................................???????????????.
....................................................???????????????.
....................................................???????????????.
Actual situation:
....................................................???????????????.
....................................................???????????????.
....................................................???????????????.
Remarks:
?????????????????????????????????????????????????????????????????????????????????????????????????????????????????????????????????..
?????????????????????????????????????????????????????????????????????????????????????????????????????????????????????????????????..
g
7 OPERATION
GE
This symbol refers to the operations of a parallel system.
Verify for correct input/output cabling before connecting Utility to the UPS.
Open only the front door, do not remove any panels.
Now you can initiate the
But we recommend, that at least the initial procedure, should be performed by an instructed person.
Check after every step for correct reaction of the UPS (LED???s on the panel), and correct voltage and current measurements, before you proceed to the next step.
If you encounter any problems during the following procedures, you should not continue, but contact GE Global Services.
Find on the following pages the descriptions of the various procedures of startup and shutdown for single and parallel UPS???s, divided into the following principal chapters:
7.1PROCEDURES FOR SINGLE UPS
7.2PROCEDURES FOR UPS FUNCTIONING AS FREQUENCY CONVERTER
7.3PROCEDURES FOR PARALLEL SYSTEM
7.4PROCEDURES FOR PARALLEL SYSTEM WITH COMMON BATTERY
g
GE
7.1PROCEDURES FOR SINGLE UPS
7.1.1
Verify with open front door: Switch Q1 and Q2 must be open (Pos. O).
1.Connect the Utility power on the UPS.
(In case of separate inputs for Rectifier and Bypass, connect both).
???Power supply starts up.
Indicated with flashing alarm and buzzer sound.
???LED???s as indicated will be lit.
???Press mute, to reset alarm and buzzer.
2.Close Q1 (Pos. I).
???Bypass Utility connects to the output.
???Rectifier starts automatically, blinking LED indicates
???At the end of Rectifier
3.Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of External Battery.
4.Press ???inverter on??? ( I ) key.
???
???At the end of
???Automatic transfer from Bypass to
Inverter.
???UPS output LED indicates Load on Inverter.
The LCD must display on the main screen the status ???LOAD ON INVERTER???.
End of procedure
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in the case of a Utility Failure.
g
GE
7.1.2 Maintenance shutdown (Load on Q2)
Initial status:
Load supplied from Inverter.
1.Press ???inverter off??? ( O ) key and hold until the LED inside the Inverter symbol turns OFF.
???Load is transferred to Utility.
???Inverter shuts down.
???LED Inverter must be OFF.
The LCD screen must display the status ???LOAD ON BYPASS???.
2.Close Q2 (Pos. I).
???Load is now supplied parallel through
Bypass and Q2.
???LED for Manual Bypass lights up.
3.Open Q1 (Pos. O) and then press ???total off??? button.
???Load is now supplied from Manual Bypass.
???Rectifier shuts down and all output and input contactors are opened.
The LCD panel must display the main screen, indicating the status ???LOAD OFF???.
4.Disconnect the Battery from the UPS in case of External Battery.
???Wait 5 minutes for
End of procedure
g
GE
7.1.3 From Manual Bypass (Q2) to normal function
Initial status:
Load supplied from Manual Bypass.
1.Close Q1 (Pos. I).
???Bypass connects to Load.
LED Load on Bypass lights up.
???Rectifier starts automatically and
LED in Rectifier symbol and LED Battery charge light up.
2.Open Q2 (Pos. O).
???LED Manual Bypass turns OFF.
3.Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of External Battery .
4.Press ???inverter on??? ( I ) key.
???
???At the end of
???Automatic transfer from Bypass to
Inverter.
???UPS output LED indicates Load on Inverter.
The LCD must display on the main screen the status ???LOAD ON INVERTER???.
End of procedure
g
GE
7.1.4Complete UPS shutdown (No Load supply)
The Load must be disconnected.
Initial status:
Load supplied from Inverter.
1.Press ???total off??? button.
???Load is disconnected from UPS.
???Rectifier is shut down and all output and input contactors will be opened.
???LED???s, Rectifier, Inverter and Load are OFF.
2.Open Q1 (Pos. O).
???LED service check lights up.
3.Disconnect the Battery from the UPS in case of External Battery.
???Wait 5 minutes for
4.Disconnect the Utility.
???All LED???s are OFF.
End of procedure
g
GE
7.1.5 Restore to normal operation after ???total off???
View of the panel after pressing the button ???total off???.
???All Contacts are open;
???Rectifier, Inverter and
1.Reset ???total off??? by pressing and holding the ???total off??? button and then the ???inverter on??? ( I ) key simultaneously until Load is supplied from Bypass and the Rectifier starts.
???Output connects to Bypass Utility.
???Rectifier starts with blinking LED.
???At the end of
???The LCD screen shows:
???LOAD ON BYPASS???.
???Press mute, to reset alarm and buzzer.
2.Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of External Battery.
3.Press ???inverter on??? ( I ) key.
???
???At the end of
???Automatic transfer from Bypass to
Inverter.
???UPS output LED indicates Load on Inverter.
The LCD must display on the main screen the status ???LOAD ON INVERTER???.
End of procedure
g
GE
7.1.6 Restore to normal operation after EPO (Emergency Power Off)
UPS panel after activation of
EPO (Emergency Power Off) with Utility not available, i.e. complete shutdown of the UPS. In this case wait until Utility is again available, then proceed to restart the UPS as described below. Points 1 through 3.
UPS panel after activation of EPO (Emergency Power Off) with Utility available.
???All Contacts are open;
???Rectifier, Inverter and
1.Reset the EPO (Emergency Power Off) button.
???Press mute, to reset alarm and buzzer.
2.Press ???inverter off??? ( O ) key.
???Output connects to Bypass Utility.
???Rectifier starts with blinking LED.
???At the end of
???The LCD screen shows:
???LOAD ON BYPASS???.
3.Press ???inverter on??? ( I ) key.
???Inverter starts with blinking LED.
???At the end of
???Automatic transfer from Bypass to
Inverter.
???UPS output LED and LCD screen indicate both: ???LOAD ON INVERTER???.
End of procedure
g
GE
7.2PROCEDURES FOR UPS FUNCTIONING AS FREQUENCY CONVERTER
When the SG Series functions as a Frequency Converter, the Automatic Bypass and
Manual Bypass functions are disabled.
Therefore the Load cannot be transferred to Utility in case of overload, short circuit, or Inverter failure.
In situations where the UPS needs to be shutdown for maintenance purposes, also the Load must be shutdown or disconnected
7.2.1
Verify with open front door: Switch Q1 must be open (Pos. O).
1.Connect the Utility power on the UPS.
???Power supply starts up.
Indicated with flashing alarm and buzzer sound.
???LED???s as indicated will be lit.
???Press mute, to reset alarm and buzzer.
2.Close Q1 (Pos. I).
???Rectifier starts automatically, blinking LED indicates
???At the end of Rectifier
3.Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of External Battery.
4.Press ???inverter on??? ( I ) key.
???
LED.
???At the end of
???UPS output LED indicates Load on Inverter.
The LCD must display on the main screen the status ???LOAD ON INVERTER???.
End of procedure
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in the case of a Utility Failure.
g
GE
7.2.2Complete UPS shutdown (No Load supply)
The Load must be disconnected.
Initial status:
Load supplied from Inverter.
1.Press ???total off??? button.
???Load is disconnected from UPS.
???Rectifier is shut down and all output and input contactors will be opened.
???LED???s, Rectifier, Inverter and Load are OFF.
2.Open Q1 (Pos. O).
???LED service check lights up.
3.Disconnect the Battery from the UPS in case of External Battery.
???Wait 5 minutes for
4.Disconnect the Utility.
???All LED???s are OFF.
End of procedure
g
GE
7.2.3 Restore to normal operation after ???total off???
View of the panel after pressing the button ???total off???.
???All Contacts are open;
???Rectifier, Inverter and
1.Reset ???total off??? by pressing and holding the ???total off??? button and the ???inverter on??? ( I ) key simultaneously until the Rectifier starts.
2.Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of External Battery.
3.Press ???inverter on??? ( I ) key.
???
???At the end of
???UPS output LED indicates Load on Inverter.
The LCD must display on the main screen the status ???LOAD ON INVERTER???.
End of procedure
g
GE
7.2.4 Restore to normal operation after EPO (Emergency Power Off)
UPS panel after activation of
EPO (Emergency Power Off) with Utility not available, i.e. complete shutdown of the UPS. In this case wait until Utility is again available, then proceed to restart the UPS as described below. Points 1 through 3.
UPS panel after activation of EPO (Emergency Power Off) with Utility available.
???All Contacts are open;
???Rectifier, Inverter and
1.Reset the EPO (Emergency Power Off) button.
???Press mute, to reset alarm and buzzer.
2.Press ???inverter off??? ( O ) key.
???Rectifier starts with blinking LED.
???At the end of
???The LCD screen shows: ???LOAD OFF???.
3.Press ???inverter on??? ( I ) key.
???Inverter starts with blinking LED.
???At the end of
???UPS output LED and LCD screen indicate both:
???LOAD ON INVERTER???.
End of procedure
g
GE
7.3PROCEDURES FOR PARALLEL SYSTEM
7.3.1 Parallel System
Verify on all Units, with open front door: Switches Q1 and Q2 must be open (Pos. O).
1.Connect the Utility power on all UPS???s.
(In case of separate inputs for Rectifier and Bypass, connect both).
???Power supply starts up. Indicated with flashing alarm and buzzer sounds.
???LED???s as indicated will be lit.
???Press mute, to reset alarm and buzzer.
2.Close Q1 (Pos. I) on all Units.
???When closing Q1 on the last unit of the parallel system, the Bypass of all Units connects to the Load.
???Rectifiers start automatically, blinking LED indicates
???At the end of Rectifier
???LED???s service check turn OFF.
3.Connect the Battery to all Units by closing the external Battery Switches or Fuses, in case of External Battery.
Continue ???
g
GE
4.Press ???inverter on??? ( I ) key on first unit.
???
???At the end of
???In case of sufficient output power, the output will transfer to Inverter.
???UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status ???LOAD ON INVERTER???.
5.Press ???inverter on??? ( I ) key on all other units.
(Do not start the next Inverter until the sequence of the previous ends)
???As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with running Inverter will transfer to Inverter.
???All LED???s Inverter, Load on Inverter and Load supplied are ON.
The LCD must display on the main screen on all Units the status
???LOAD ON INVERTER???.
End of procedure
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in the case of a Utility Failure.
g
GE
7.3.2 Maintenance system shutdown (Load supplied from Q2 on all Units)
Initial status: Load supplied from all Inverters.
g
GE
7.3.3 From Manual Bypass (Q2) to normal function
Initial status: Load supplied from Manual Bypass.
All Q2 of the system are closed.
1.Close Q1 (Pos. I) on all Units.
The Rectifiers will start automatically and at the closure of Q1 of the last Unit, the Bypass of all Units will be activated.
2.Connect the Battery to all Units by closing the external Battery Switches or Fuses, in case of External Battery.
3.Open Q2 (Pos. O) on all Units.
Continue ???
g
GE
4.Press ???inverter on??? ( I ) key on first unit.
???
???At the end of
???In case of sufficient output power, the output will transfer to Inverter.
???UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status ???LOAD ON INVERTER???.
5.Press ???inverter on??? ( I ) key on all other units.
(Do not start the next Inverter until the sequence of the previous ends)
???As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with running Inverter will transfer to Inverter.
???All LED???s Inverter, Load on Inverter and Load supplied are ON.
The LCD must display on the main screen on all Units the status
???LOAD ON INVERTER???.
End of procedure
g
GE
7.3.4 Separate a Unit from the parallel system (System Redundancy)
Initial status: Load supplied from all Inverters.
1.Press and hold ???inverter off??? ( O ) key on the Unit to separate, until the LED turns OFF.
Load supplied from Inverter(s) of the other Unit(s) of the parallel system.
2.Open Q1 (Pos. O) and, only when the LED service check is ON, press ???total off??? button on the Unit to separate.
3.Disconnect the Battery, in case of External Battery, from the Unit to separate.
??? Wait 5 minutes for
4.Disconnect the Utility supply from the separated Unit.
End of procedure
For any further intervention could nearest Service Center.
g
GE
7.3.5 Reconnect a Unit to a parallel system
1.Connect the Utility supply on the separated Unit.
??? Press mute, to reset alarm and buzzer.
2.Close Q1 (Pos. I) on the separated Unit.
Rectifier starts automatically.
3.Connect the Battery, in case of External Battery, to the UPS on the separated Unit by closing the external Battery Switch or Fuses.
4.Press ???inverter on??? ( I ) key on the separated Unit.
After
??? The LCD must display on the main screen the status ???LOAD ON INVERTER???.
End of procedure
g
GE
7.3.6 Parallel system shutdown (No Load supply)
The Load must be disconnected.
Initial status: Load supplied from all Inverters.
1.Press ???total off??? button on any one on the Units.
???Load is disconnected from UPS.
???Rectifier and Inverter are shut down and all output and input Contactors will be opened.
???LED???s, Rectifier, Inverter and Load are OFF.
2. Open Q1 (Pos. O) on all Units.
Continue ???
g
GE
3.Disconnect the Battery, in case of External Battery, from all Units.
??? Wait 5 minutes for
4.Disconnect the Utility supply from all Units.
??? All LED???s are OFF.
End of procedure
g
GE
7.3.7 Restore to normal operation after ???total off???
View of the panel after pressing the button ???total off???.
???All Contacts are open;
???Rectifier, Inverter and
1.Reset ???total off??? by pressing and holding the ???total off??? button and then the ???inverter on??? ( I ) key, on any of the Units simultaneously, until Load is supplied from Bypass and the Rectifiers start.
???System output connects to Bypass Utility.
???Rectifiers start with blinking LED.
???At the end of
???The LCD screen on all Units shows ???LOAD ON BYPASS???.
2.Connect the Battery to all Units by closing the external Battery Switches or Fuses, in case of External Battery.
Continue ???
g
GE
3Press ???inverter on??? ( I ) key on first unit.
???
???At the end of
???In case of sufficient output power, the output will transfer to Inverter.
???UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status ???LOAD ON INVERTER???.
4.Press ???inverter on??? ( I ) key on all other units.
(Do not start the next Inverter until the sequence of the previous ends)
???As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with running Inverter will transfer to Inverter.
???All LED???s Inverter, Load on Inverter and Load supplied are ON.
The LCD must display on the main screen on all Units the status
???LOAD ON INVERTER??????.
End of procedure
g
GE
7.3.8 Restore to normal operation after EPO (Emergency Power Off)
UPS panel after activation of EPO (Emergency Power Off) with Utility not available, i.e. complete shutdown of the UPS and LCD screen OFF.
In this case wait until Utility is again available, then proceed to restart the UPS as described below Points 1 through 3.
UPS panel after activation of EPO (Emergency Power Off) with Utility available.
All Contacts are open. Rectifier, Inverter and
1.Reset the EPO (Emergency Power Off) button.
??? Press mute, to reset alarm and buzzer.
2.Press ???inverter off??? ( O ) key on all Units.
???Rectifiers start with blinking LED.
???After pressing the ???inverter off??? key on the last unit of the parallel system, the output of all Units connect to Bypass Utility.
???The LCD screen shows: ???LOAD ON BYPASS???.
Continue ???
g
GE
3.Connect the Battery to all Units by closing the external Battery Switches or Fuses, in case of External Battery.
4.Press ???inverter on??? ( I ) key on first Unit.
???
???At the end of
???In case of sufficient output power, the output will transfer to Inverter.
???UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status ???LOAD ON INVERTER???.
5.Press ???inverter on??? ( I ) key on all other Units.
(Do not start the next Inverter until the sequence of the previous ends).
???As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with running Inverter will transfer to Inverter.
???All LED???s Inverter, Load on Inverter and Load supplied are ON.
The LCD must display on the main screen on all Units the status
???LOAD ON INVERTER???.
End of procedure
g
GE
7.4PROCEDURES FOR PARALLEL SYSTEM WITH COMMON BATTERY
ONLY FOR UPS WITH EXTERNAL BATTERY.
7.4.1 Parallel System
Verify on all Units, with open front door: Switches Q1 and Q2 must be open (Pos. O).
1.Connect the Utility power on all UPS???s.
(In case of separate inputs for Rectifier and Bypass, connect both).
???Power supply starts up. Indicated with flashing alarm and buzzer sounds.
???LED???s as indicated will be lit.
???Press mute, to reset alarm and buzzer.
2.Connect the Battery to all Units by closing the external Battery Switch(es) or Fuses.
3.Close Q1 (Pos. I) on all Units.
???Rectifiers start automatically, blinking LED indicates
???At the end of Rectifier
???When closing Q1 on the last Unit of the parallel system, the Bypass of all Units connects to the Load.
???LED???s service check turn OFF.
Continue ???
g
GE
4.Press ???inverter on??? ( I ) key on first unit.
???
???At the end of
???In case of sufficient output power, the output will transfer to Inverter.
???UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status ???LOAD ON INVERTER???.
5.Press ???inverter on??? ( I ) key on all other units.
(Do not start the next Inverter until the sequence of the previous ends)
???As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with running Inverter will transfer to Inverter.
???All LED???s Inverter, Load on Inverter and Load supplied are ON.
The LCD must display on the main screen on all Units the status
???LOAD ON INVERTER???.
End of procedure
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in the case of a Utility Failure.
g
GE
7.4.2 Maintenance system shutdown (Load supplied from Q2 on all Units)
Initial status: Load supplied from all Inverters.
g
GE
7.4.3 From Manual Bypass (Q2) to normal function
Initial status: Load supplied from Manual Bypass.
All Q2 of the system closed.
1.Connect the Battery to all Units by closing the external Battery Switch(es) or Fuses.
2.Close Q1 (Pos. I) on all Units.
The Rectifiers will start automatically and at the closure of Q1 of the last Unit, the Bypass of all Units will be activated.
3. Open Q2 (Pos. O) on all Units.
Continue ???
g
GE
4.Press ???inverter on??? ( I ) key on first unit.
???
???At the end of
???In case of sufficient output power, the output will transfer to Inverter.
???UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status ???LOAD ON INVERTER???.
5.Press ???inverter on??? ( I ) key on all other units.
(Do not start the next Inverter until the sequence of the previous ends)
???As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with running Inverter will transfer to Inverter.
???All LED???s Inverter, Load on Inverter and Load supplied are ON.
The LCD must display on the main screen on all Units the status
???LOAD ON INVERTER???.
End of procedure
g
GE
7.4.4 Separate a Unit from the parallel system (System Redundancy)
Initial status: Load supplied from all Inverters.
1.Press and hold ???inverter off??? ( O ) key on the Unit, to separate, until the LED turns OFF.
Load supplied from Inverter(s) of the other Unit(s) of the parallel system.
2.Open Q1 (Pos. O) and, only when the LED service check is ON, press ???total off??? button on the Unit to separate.
3.Disconnect the Battery from the Unit to separate.
??? Wait 5 minutes for
4.Disconnect the Utility supply from separated Unit.
End of procedure
For any further intervention could nearest Service Center.
g
GE
7.4.5 Reconnect a Unit to a parallel system
1.Connect the Utility supply on the separated Unit.
??? Press mute, to reset alarm and buzzer.
2.Connect the Battery to the UPS separated by closing the external Battery Switch or Fuses.
3.Close Q1 (Pos. I) on the separated Unit.
Rectifier starts automatically.
4.Press ???inverter on??? ( I ) key on the separated Unit.
After
End of procedure
g
GE
7.4.6 Parallel system shutdown (No Load supply)
The Load must be disconnected.
Initial status: Load supplied from all Inverters.
1.Press ???total off??? button on any one on the units.
???Load is disconnected from UPS.
???Rectifier and Inverter are shut down and all output and input contactors will be opened.
???LED???s, Rectifier, Inverter and Load are OFF.
2. Open Q1 (Pos. O) on all Units.
Continue ???
g
GE
3.Disconnect the Battery from all Units.
??? Wait 5 minutes for
4.Disconnect the Utility supply from all Units.
??? All LED???s are OFF.
End of procedure
g
GE
7.4.7 Restore to normal operation after ???total off???
View of the panel after pressing the button ???total off???.
???All Contacts are open;
???Rectifier, Inverter and
1.Reset ???total off??? by pressing and holding the ???total off??? button and then the ???inverter on??? ( I ) key, on any of the Units simultaneously, until Load is supplied from Bypass and the Rectifiers start.
???System output connects to Bypass Utility.
???Rectifiers start with blinking LED.
???At the end of
???The LCD screen on all Units shows: ???LOAD ON BYPASS???.
2.Connect the Battery to all Units by closing the external Battery Switch(es) or Fuses.
Continue ???
g
GE
3.Press ???inverter on??? ( I ) key on first unit.
???
???At the end of
???In case of sufficient output power, the output will transfer to Inverter.
???UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status ???LOAD ON INVERTER???.
4.Press ???inverter on??? ( I ) key on all other units.
(Do not start the next Inverter until the sequence of the previous ends)
???As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with running Inverter will transfer to Inverter.
???All LED???s Inverter, Load on Inverter and Load supplied are ON.
The LCD must display on the main screen on all Units the status
???LOAD ON INVERTER???.
End of procedure
g
GE
7.4.8 Restore to normal operation after EPO (Emergency Power Off)
UPS panel after activation of EPO (Emergency Power Off) with Utility not available, i.e. complete shutdown of the UPS and LCD screen OFF.
In this case wait until Utility is again available, then proceed to restart the UPS as described below Points 1 through 3.
UPS panel after activation of EPO (Emergency Power Off) with Utility available.
All Contacts are open. Rectifier, Inverter and
1.Reset the EPO (Emergency Power Off) button.
??? Press mute, to reset alarm and buzzer.
2.Connect the Battery to all Units by closing the external Battery Switch(es) or Fuses.
3.Press ???inverter off??? ( O ) key on all Units.
???Rectifiers start with blinking LED.
???After pressing the ???inverter off??? key on the last unit of the parallel system, the output of all Units connect to Bypass Utility.
???The LCD screen shows: ???LOAD ON BYPASS???.
Continue ???
g
GE
4.Press ???inverter on??? ( I ) key on first Unit.
???
???At the end of
???In case of sufficient output power, the output will transfer to Inverter.
???UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status ???LOAD ON INVERTER???.
5.Press ???inverter on??? ( I ) key on all other Units.
(Do not start the next Inverter until the sequence of the previous ends).
???As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with running Inverter will transfer to Inverter.
???All LED???s Inverter, Load on Inverter and Load supplied are ON.
???The LCD of the all Units, must display on the main screen the status
???LOAD ON INVERTER???.
The LCD must display on the main screen on all Units the status
???LOAD ON INVERTER???.
End of procedure
g
GE
8CUSTOMER INTERFACE
8.1CUSTOMER INTERFACE
Fig.
Serial port J3 - RS 232 (sub D - female 9 pin)
Suitable for JUMP protocol
J2
Signals on terminals X1 and on connector J2 are in parallel and therefore not separated galvanically from each other.
The programmable signals on X1 and J2 will be disabled with Q1 open, with the exception of the signals for ???16 - Manual Bypass ON??? and ???26 - EPO???.
XB - Terminals for EPO connection
X2 / 1, 2 or J2 / 12, 25 NC EPO (Emergency Power Off)
Note: to enable this function, remove cable
X1 ??? Output signals on voltage free contacts - terminals
Input contacts
The connectors J4 and J5 can be used for additional SNMP Card, Environmental Card (not available yet) or an additional Customer Interface (installation only when the UPS is switched Off).
g
GE
8.1.1 Serial Port J3
Serial port J3 -
???Total remote management of the system using new generation software JUMP (Java Universal Management Platform) for system protection and management of systems using GE UPS???s.
JUMP system is written in JAVA and supports virtually all platforms having JAVA runtime environment version 1.1 or higher.
The serial port J3 -
Serial port J3 connection to PC
Fig.
8.1.2Output free potential contacts
The interface board provide 6 voltage free relay contacts giving some UPS critical alarms and operation mode.
These signals are available either on connector J2- (sub D, female 25 pin) or terminal blocks X1.
The meaning of the alarms on the free contacts in standard configuration (default) is the following:
In case different alarms or operating status are required, they can be configured on the same terminals via software from the control panel.
The configuration can be changed in parameters mode by a trained operator using the appropriate password.
The programmable signals on X1 and J2 will be disabled with Q1 open, with the exception of the signals for ???16 - Manual Bypass ON??? and ???26 - EPO???.
g
GE
8.1.3 Programmable input free contacts
Some programmable UPS functions (indicated in Section 4.1), can be activated by closing an external contact, if connected, on:
8.1.4 Gen Set Signaling (GEN ON)
If an emergency generator set supplies the UPS in case of Utility Failure and the generator is particularly unstable in frequency, it should be suitable to install the signal ???Generator ON??? on X1/11, 22 or J2/11, 24 (this input is programmed as default for this function).
When this contact closes, it causes the change of certain functions (programmable) such as:
???Enabling or disabling of synchronization and consequently the Load transfer to generator.
???Reduction or elimination or delay of Battery recharging during the generator operation.
In a parallel system a separate NO (Normally Open) contact must be connected individually to each unit.
8.1.5AUX external Maintenance Bypass
If the UPS system is equipped with an external Maintenance Bypass Switch, it is possible to connect a NO (normally open) voltage free aux. contact from the External Bypass Switch to the programmable input
This function can be activated by changing a dedicated parameter (password required).
When this NO (Normally Open) contact closes, the output Inverter Contactor K7 it is automatically opened and the Load transfer back to Inverter will be inhibited.
In a parallel system, the input on customer interface of each unit must be connected to a separate AUX contact of the External Maintenance Bypass Switch.
8.1.6 Auxiliary Power Supply (APS) 24 VDC / 1A
1 2 3 4
Fig.
g
GE
8.1.7 EPO (Emergency Power Off) Input contact
1
2
3
4
1 2 3 4
JP3
J2
XB
An external Emergency switch (Normally Closed
Remove the cable
Fig.
To enable this function, remove cable
Terminal XB and the Jumper JP3 on P4 ??? Customer Interface, when the cables have been already connected on XB or J2.
In a parallel system a separate NC (Normally Closed) contact must be connected individually to each unit.
When opened, this contact causes the immediate opening of the Contactors K3, K4, K6, K7 and K8, as well as the shutdown of Rectifier, Inverter and
Be aware: The reliability of the system depends on this contact!
After closure of the Emergency contact, a reset is necessary to enable the restart of the UPS, by pressing the key ???O??? (inverter off) on the control panel.
In case of a parallel system press the key ???O??? (inverter off) on the control panel of each unit connected on parallel bus and having it???s output switch Q1 closed.
g
GE
9 OPTIONS
9.1BUILT IN UPS OPTIONS
RPA Kit
Redundant Parallel Architecture.
Up to 8 units parallel able for redundancy or capacity in
RPA configuration.
9.2COMMUNICATION OPTIONS
SNMP Card
Simple Network Management Protocol.
The SNMP Card is an Interface to the Ethernet Network, and provides UPS information via the standard SNMP protocol.
The UPS can therefore be managed by a Network Management System (NMS) or by our applications (for instance JUMP), which uses this information to determine the state of the UPS in order to guarantee safe and orderly shutdown of the server, when needed.
IRIS Service
Internet Remote Information System for UPS System.
9.3OPTIONS IN UPS CABINET
ARGUS / Power Flag / JUMP Software
Remote Signaling Box (RSB)
Equipped with mimic diagram, general alarm, stop operation, alarm reset and lamp.
The cable for connection to UPS not included.
5th harmonic filter
Located inside UPS cabinet.
FCC Filter
Located inside UPS cabinet. Meets FCC Class A, Part 15 Standard for EMI suppression.
g
GE
9.4CONNECTION FOR OPTIONS
The installation and cabling of the options must be performed a qualified service person.
9.4.1 Remote Signaling Box (RSB)
The optional Remote Signaling Box allows monitoring of the operation of the UPS, using the potential free contacts fitted on the ???P4 - Customer Interface Board??? of the UPS.
It can be used by simply putting the box on a desktop or on a wall or, removing the box, it can be surface mounted.
The remote panel contains an internal buzzer and the following status indicators:
The cable connecting the RSB to the UPS cabinet must be min. 16 wires / 0.25mm2.
The plug B is included in the delivery of the option RSB (cable connecting UPS with RSB not included). Maximal admitted length: 985 ft (300 m).
It must be wired at one end with a D - female plug- 25 pin (J2 ??? P4 Customer Interface Board).
The alarms on free potential contacts can be connected on terminals X1 instead J2 (see correlation X1 ??? J2 in chapter 8.1).
P.S.: The above mentioned colors are suitables only for XY standard cable
Fig.
ATerminals X3, X4 and X15 fitted inside the Remote Signaling Box.
BPlug J2 (sub D - male - 25 pin) must be connected to the connector J2 (sub D - female- 25 pin) located on ???P4 - Customer Interface Board???.
XA Terminals block XA for 24 VDC / 1A supply Remote Signaling Box.
If the remote signal panel is plugged on connector J2, the terminal blocks X1 cannot be used to drive an external alarms monitoring device, because it is supplied by the internal UPS low voltage power supply.
g
10 MAINTENANCE
GE
10.1MAINTENANCE
A UPS system, like other electrical equipment, needs periodic preventive maintenance.
A regular maintenance check of your installation guarantees higher reliability of your safe critical power supply.
Preventive maintenance work on the UPS can be done only by trained Service technicians.
We therefore recommend you sign a Maintenance and Service contract with GE Global Services @
10.1.1 Service check
If this lamp lights up during the normal operation, that means that the unit has not been serviced for the last 20,000 hours by a GE trained technician.
We highly recommend that you contact your Service Center for preventive maintenance work.
10.1.2 Fans and ventilation
We recommend a periodic cleaning of the ventilation channels and grids on the UPS system, in order to guarantee proper air circulation in the unit and in the Battery.
We recommend replacement of the fans in the units every 20,000 hours.
10.1.3 Other components with limited lifetime
We recommend the replacement of components such as Filter Capacitors and Lithium Battery for the backup of data on the control boards of the units every 50,000 hours.
10.1.4 Battery
We recommend a periodic Manual Battery Test, especially if the Automatic Battery Test is disabled, in order to verify if the Battery can provide the expected backup time in case of Utility Failure.
We recommend this test be performed at least every 3 months, especially if the Battery is not sufficiently discharged during normal operation.
The discharge time you use should be at least half of the Battery runtime.
For Automatic Battery Test setting, a special code is required to enter user
Please consider that, if you did a full Battery Test to verify the full runtime of the Battery, the charger needs at least 8 hours to recharge the Battery up to 90% of its capacity.
g
GE
10.1.5 Long
To guarantee that the Battery is fully charged, the UPS system should be in operation for at least
12 hours every 3 months.
If not the Battery may be permanently damaged.
10.1.6 UPS room conditions and temperature
The UPS room and the Battery Room have to be maintained clean and free from dust.
A high temperature of the UPS room and of the Battery Room affect the lifetime of several components inside the equipment.
The Battery is very sensitive to room temperatures above 77??F (25??C).
10.1.7 Long
a)Cleaning, a visual inspection and a mechanical inspection of the UPS modules.
b)Replacement of defective parts or the preventive replacement of parts with a defined lifetime
c)???Updating??? of the equipment (technical improvements subsequent to the delivery).
d)Check the calibration of DC voltage and Inverter Output Voltage and Frequency.
e)Check of the settings of the electronic regulation, the control and the alarm circuits of the
Rectifier(s) and Inverter(s).
f)Functional checks on Thyristors, Diodes, Transformers, Filter Components, e.g. to ensure that they are operating within the specified design parameters.
g)Overall performance test including a Utility Failure simulation with and without the Load.
h)Monitoring Battery operation in discharge and recharge mode including any boost charge duties.
g
11 NOTES
GE
11.1NOTES FORM
It is recommended to note in this section Notes, with date and short description all the operations performed on the UPS, as: maintenance, components replacement, abnormal situations, etc.
g
GE
RIDER FOR WARRANTY FOR SALE OF SiteProTM, DIGITAL ENERGYTM SG Series and LP Series UPS.
This Rider incorporates by reference the Terms and Conditions in GE Industrial Systems (herein called GE) GETC2003, and includes the following additional provisions contained herein.
In the event of conflict between this Rider and GETC2003, the Rider shall take precedence.
Limitation on use with life support equipment:
Customer understands and agrees that the products sold hereunder are not intended for application or use, and shall not be used: (i) in conjunction with or for life support equipment when failure of any product can be reasonably be expected to cause failure of or diminish the effectiveness of such life support Customer represents and warrants that it shall NOT USE THE
PRODUCTS FOR ANY SUCH PURPOSES, OR PERMIT
OTHERS TO USE THE PRODUCTS FOR ANY SUCH PURPOSES. If, in breach of the foregoing, any such use occurs, Seller shall have no liability for any resulting damage or injury, in addition to any other legal or equitable rights of Seller, Customer shall indemnify Seller against any such liability, whether arising as a result of breach of contract, warranty,
indemnity, tort (including negligence), strict liability or otherwise.
WARRANTY: Seller warrants to Customer that during the ???Warranty Period??? applicable for its SitePro, Digital EnergyTM SG Series and LP Series UPS Product furnished hereunder (the ???Product???) will be free from defects in material, workmanship and title.
The warranty period (???Warranty Period???) for the specified Product begins on the earlier of three (3) months after the delivery date or upon commissioning of the Product (if applicable) and ends at the end of the period as set forth below: The Warranty Period for the specified Product is as follows:
In no case does this warranty apply to any failure or nonconformance with specifications caused by or attributable to any associated or complementary products not supplied under these Terms and Conditions, nor shall it in any case apply to the quantity or quality of the product of Customer or the process of manufacture on which any products are used. The warranties and remedies set forth herein are conditioned upon (a) proper transportation, handling, storage, installation, commissioning, operation, use and maintenance in conformance with the operation instruction manuals (including revisions thereto) provided by Seller, any applicable recommendations of Seller and any applicable laws, regulations or codes (b) repair or modification pursuant to Seller???s instructions or approval and (c) Customer promptly notifying Seller of any defects and, if required, promptly making the Product available for correction at Customer???s expense. This warranty shall not apply (a) if Customer or any other unauthorized person has made any modifications, alterations or repairs to the Product not authorized by Seller, including Customer???s use of parts in conjunction with the Product (excluding batteries) not admitted or delivered by Seller, (b) to a Product with removed or altered serial numbers, (c) to a Product damaged by acts of God, sources external to the Product, misuse, accident, abuse, neglect, negligence, or use beyond rated capacity, and (d) if GE authorized field service technician does not commission Digital Energy?? SG Series UPS and SitePro UPS."
If any Product or service fails to meet the foregoing warranties (except title), Seller shall thereupon correct any such failure either, at its option, by (i) repairing any defective or damaged part or Product and/or reperforming any defective service or (ii) making available, F.O.B. at Seller???s facility, place of manufacture or other mutually agreed upon point of shipment, any necessary repaired or replacement parts; provided, however, that prior to repairing any defective or damaged part or Product, Seller shall have received, at Customer???s cost, such part or Product in need of repair or replacement.
If reperformance is not practicable, Seller will furnish without charge services in an amount essentially equal to those that, in the sole judgment of Seller, would have been required for reperformance. Where a failure cannot be corrected by Seller???s reasonable efforts, the parties will negotiate an equitable adjustment in price. In providing a replacement Product or parts, Seller reserves the right to use refurbished circuit boards, which shall be warranted in accordance with this Warranty Provision. The correction of any failure or the supply of repaired or replacement parts or Products pursuant to this Warranty Provision shall not extend the duration of the applicable Warranty Period.
Seller does not warrant the following items: (i) computer hardware, (ii) any computer software, including software provided by Seller with any Product, (iii) products or services obtained from others or (iv) any batteries used in conjunction with the products, including those provided by Seller, and in regard to these items, only the warranty of the manufacturer, if any, shall apply. Seller's obligation under this Provision entitled ???Warranty??? shall terminate immediately upon any modification of the Product by Customer unless made with the approval of Seller.
The Warranty Period applicable to each Product can be extended, if Customer purchases an extended warranty from Seller. If Customer purchases an extended warranty from Seller, the terms of such extended warranty shall supersede these warranty provisions.
THE PRECEDING PARAGRAPHS OF THIS WARRANTY
PROVISION SET FORTH THE EXCLUSIVE CLAIMS
(EXCEPT AS TO TITLE) BASED ON DEFECT IN OR
FAILURE OF A PRODUCT, WHETHER THE CLAIM IS IN
CONTRACT, INDEMNITY, WARRANTY, TORT
(INCLUDING NEGLIGENCE), STRICT LIABILITY OR
OTHERWISE.
Upon the expiration of the applicable Warranty Period, all such liability shall terminate and Customer shall have a reasonable time, not to exceed thirty (30) days after the applicable Warranty Period, to give written notice of any defects that appeared during the Warranty Period.
THE FOREGOING WARRANTIES ARE EXCLUSIVE AND
IN AND IN LIEU OF ALL OTHER WARRANTIES,
WHETHER WRITTEN, ORAL, IMPLIED OR
STATUTORY. NO IMPLIED STATUTORY WARRANTY
OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE SHALL APPLY.
INSTALLATION AND COMMISSIONING OF INSTALLABLE SYSTEMS: If the Products cannot be installed immediately after delivery, Customer is responsible for maintaining proper storage conditions according to operating manuals and any other instructions provided by Seller.
Installable Products may only be installed by certified electrical installers and must be installed according to Seller???s specifications, appropriate national electrical codes and accepted standards of workmanship. For purposes of these GE Terms and Conditions, ???installable Products??? shall mean Products that require the services of a certified electrical installer to be connected to the power grid.
The commissioning of installable Products may only be done by a technician authorized by Seller and must be done according to Seller???s specifications. For purposes of these GE Terms and Conditions, ???commissioning??? shall mean the
Any costs resulting from a delay in commissioning will be charged to Customer.