1.0 Description
These instructions cover the installation of Bosch FMM-7045 (Single Action)/FMM-7045-D (Dual Action) Multiplex (single-action) Multiplex Addressable Pull Station in a fire system supervised by a Bosch D7024 Series or DS9400 Series Fire Alarm Control Panel (FACP) with firmware revision 2.0 or greater and a D7039 or DS9431 Multiplex Expansion Module.
Install, test and maintain the FMM-7045/FMM-7045-D according to these instructions, NFPA 72, Local Codes and the Authority Having Jurisdiction (AHJ). Failure to follow these instructions may result in failure of the device to operate properly. Bosch is not responsible for improperly installed, tested or maintained devices.
These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.
NFPA 72 requires a complete system-wide functional test be performed following any modifications, repair, upgrades or adjustments made to the system???s components, hardware, wiring, programming and software/firmware.
The FMM-7045/FMM-7045-D Multiplex Addressable Manual Pull Station is a UL Listed fire alarm initiating device. It can be connected along with other Multiplex devices on the D7039/DS9431 Multiplex Expansion Module.
The D7024/DS9400 Series FACP supervises the entire multiplex loop, including the FMM-7045/FMM-7045- D, for troubles, alarms and ground fault conditions.
Since the FMM-7045/FMM-7045-D occupies only one address on the multiplex bus, the module can be addressed for any point within the 9 to 255 range allowed by the D7039/DS9431 Multiplex Expansion Module.
The FMM-7045/FMM-7045-D is generally installed near building exits such as stairways and doors, allowing persons evacuating the building to activate the fire alarm. It is equipped with glass break rods and a pull handle that locks in the activated position, to allow easy identification of alarm activation point.
2.0Installation
2.1Operation
The FMM-7045/FMM-7045-D (single-action) Multiplex Addressable Manual Pull Station is a UL Listed fire alarm initiating device with a multiplex input module connected to each pull station.
Rotary switches are provided for convenient address setting. These switches eliminate the need for an external programmer.
The FMM-7045/FMM-7045-D is a single-action device with a white pull-down lever in its center. The lever is easily accessible to persons standing or in wheelchairs. Pulling down on the lever breaks the glass rod. The lever then latches in the down position and activates the multiplex point, which then trips the fire alarm control panel (FACP).
The lever cannot be reset until the proper key is inserted in the lock. This feature allows emergency personnel to determine the source of the alarm.
2.2Setting the address
The FMM-7045/FMM-7045-D???s address is set by positioning three rotary switches located on the front side of the device. The switches click when turned. The valid address range is 9 to 255. Check with the control panel???s operation and installation manual for additional address limitations.
Use a flat-bladed screwdriver to position each switch when setting the FMM-7045/FMM-7045-D???s address. See Figure 1 for details.
Figure 1: Setting the Address
1 - Hundreds
2 - Use these addresses if using the D7024 Series FACP with the D7039 Module.
3 - Use these addresses if using the DS9400 Series FACP with the DS9431 Module.
4 - Tens
5 - Ones
Example: