FLM???325???IM Contact Module

The FLM???325???IM Contact Module provides a variety of fire alarm functions, such as monitoring manual pull stations, waterflow devices, or other dry contact fire alarm activation applications. The module allows for alarm, trouble, and supervisory conditions. The module is mounted inside of a single???gang back box and is normally out of view.

System Overview

The FLM???325???IM Contact Module allows compatible fire alarm control panels (FACP) to supervise Form A or B dry contact devices in a polling circuit. The module has an eight???bit microprocessor and communicates with the control panel (both power and data) over a two-wire polling circuit. The initiating device circuit (NFPA Style B) connected to the module can have up to 20 normally-open (NO) dry contact devices. Each module can monitor one normally-closed (NC) device (NC devices must be non- alarm applications).

???Digital data communications and power provided over a two-wire circuit

???Advanced digital communications protocol compatible

???Class B circuit for dry contact devices

???Module address programming (1-254) with the D5070 Analog Device Programmer

Certifications and Approvals

Installation/Configuration Notes

The following products are compatible with the FLM???325???IM Contact Module:

www.boschsecurity.com

2 | FLM???325???IM Contact Module

Data Circuit Length

Data (or polling) circuit length is the distance over the circuit wire from the connection at the FACP to the most distant device and back to the FACP. Data circuit length must include the distance to any device connected to the circuit in a T tap. The screw terminals can accept up to 14 AWG (1.5 mm) wire, but this reduces the allowable length of the circuit.

Refer to the FPE???1000???SLC Installation Guide

(P/N: F01U078099) for specific wire instructions and specifications for the FPA???1000 series panels.

Initiating Device Circuit Connections

The initiating device circuit can use any number of UL- listed normally open (NO) contact closure devices. Device circuit wiring must not exceed 50 ??. Install contact closure devices according to the manufacturer???s installation instructions. All wiring must be supervised and power-limited.

Note Do not mix fire alarm initiating and supervisory devices on the same module.

Trademarks

Trademark names are used throughout this document. In most cases, these designations are claimed as trademarks or registered trademarks in one or more countries by their respective owners. Rather than placing a trademark symbol in every occurrence of a trademark name, Bosch Security Systems, Inc. uses the names only in an editorial fashion and to the benefit of the trademark owner with no intention of infringing the trademark.

Hochiki is a trademark of Hochiki America Corporation.

Ordering Information

FLM???325???IM Contact ModuleFLM-325-IM

Allows compatible fire alarm control panels (FACP) to supervise Form A or B dry contact devices in a polling circuit

Parts Included

Quant. Component

1Point contact module

1EOL resistor: Hochiki P/N 0400???01046,. 10 k??, ?? W, ?? in.

1Literature ??? Installation Guide

Technical Specifications